Plan Review Notes
Plan Review Notes For Permit 15111020
Permit Number 15111020
Review Stop E
Sequence Number 2
Notes
Date Text
2016-08-03 11:48:202ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 PENDING COMMENTS:
  
 1. MAIN ELECTRICAL ROOMS MUST COMPLY WITH NEC 110.26C2,
 THERE SHALL BE ONE ENTRANCE AT EACH END OF THE WORKING
 SPACE. SHOW TWO MEANS OF EGRESS. PER OUR MEETING,
 SECOND OPENING NOT REFLECTED. PLEASE SHOW LOCATION OF
 SECOND MEANS OF EGRESS.
 2. SHEET E2-01- IDENTIFY ALL AREAS ON FLOOR PLAN.
 MINIMUM CRITERIA FOR PLAN REVIEW, ALL PANEL AND CIRCUIT
 DESIGNATIONS FOR LIGHTING FIXTURES WITH CIRCUIT NUMBERS
 ASSIGNED TO EQUIPMENT SHOWN. SOME AREAS ARE STILL NOT
 DESIGNATED.
 3. FPL LETTER WILL BE PROVISO; WE WILL NEED COPY FOR
 OUR RECORDS. AIC CALCS PENDING NEC 110.9-10
 4. COULDN?T LOCATE VOLTAGE DROP CALCULATIONS FOR
 FEEDERS AND BRANCH PER FBC EC C405.7
 5. NOTE TO RISER INDICATING SELECTIVE COORDINATION
 REQUIRED FOR GFP OF MAINS SHOWN.
 6. NOTE THAT THE FIRE PUMP CONDUCTORS STATE COPPER ON
 RISER AND ALUMINUM ON PANEL SCHEDULE. FIRE PUMP BREAKER
 IN GDP PANEL TO COMPLY WITH NEC 695.6 AND 430.52 TABLE
 7. SHEET 2-54A- SEE KITCHEN AREAS NEXT TO CIRCUIT #7,
 ADDRESS COUNTERTOP AREAS SPACING TO COMPLY WITH NEC
 210.52C1- NOT ADDRESSED PLEASE ADD A GENERAL NOTE
 INDICATING NEC 210.52 KITCHEN SPACING REQUIREMENTS.
 8. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  