| 2016-08-03 11:48:20 | 2ND ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | PENDING COMMENTS: |
| | |
| | 1. MAIN ELECTRICAL ROOMS MUST COMPLY WITH NEC 110.26C2, |
| | THERE SHALL BE ONE ENTRANCE AT EACH END OF THE WORKING |
| | SPACE. SHOW TWO MEANS OF EGRESS. PER OUR MEETING, |
| | SECOND OPENING NOT REFLECTED. PLEASE SHOW LOCATION OF |
| | SECOND MEANS OF EGRESS. |
| | 2. SHEET E2-01- IDENTIFY ALL AREAS ON FLOOR PLAN. |
| | MINIMUM CRITERIA FOR PLAN REVIEW, ALL PANEL AND CIRCUIT |
| | DESIGNATIONS FOR LIGHTING FIXTURES WITH CIRCUIT NUMBERS |
| | ASSIGNED TO EQUIPMENT SHOWN. SOME AREAS ARE STILL NOT |
| | DESIGNATED. |
| | 3. FPL LETTER WILL BE PROVISO; WE WILL NEED COPY FOR |
| | OUR RECORDS. AIC CALCS PENDING NEC 110.9-10 |
| | 4. COULDN?T LOCATE VOLTAGE DROP CALCULATIONS FOR |
| | FEEDERS AND BRANCH PER FBC EC C405.7 |
| | 5. NOTE TO RISER INDICATING SELECTIVE COORDINATION |
| | REQUIRED FOR GFP OF MAINS SHOWN. |
| | 6. NOTE THAT THE FIRE PUMP CONDUCTORS STATE COPPER ON |
| | RISER AND ALUMINUM ON PANEL SCHEDULE. FIRE PUMP BREAKER |
| | IN GDP PANEL TO COMPLY WITH NEC 695.6 AND 430.52 TABLE |
| | 7. SHEET 2-54A- SEE KITCHEN AREAS NEXT TO CIRCUIT #7, |
| | ADDRESS COUNTERTOP AREAS SPACING TO COMPLY WITH NEC |
| | 210.52C1- NOT ADDRESSED PLEASE ADD A GENERAL NOTE |
| | INDICATING NEC 210.52 KITCHEN SPACING REQUIREMENTS. |
| | 8. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING |
| | THIS PROJECT. |
| | |