| 2016-08-29 17:12:53 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15111020 |
| | ADD: 1100 S. FLAGLER DR. |
| | CONT: SUFFOLK CONSTRUCTION CO. |
| | TEL: 561-832-1616 |
| | E-MAIL: [email protected] / ED HANRATTY |
| | |
| | 2010 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: SAT.- AUG. 26- /2016 |
| | ACTION: DENIED |
| | |
| | NOTE: THIS REVIEW IS GOING TO BE COMPLETED AS A MIXED |
| | USE BUILDING,(FEMA REGULATIONS) AND THE REQUIREMENTS AS |
| | SUCH. 2010 FBC-B 1612.4 DESIGN & CONSTRUCTION SHALL BE |
| | IN ACCORDANCE WITH ASCE 24-05. |
| | ASCE 24-05 TABLE 6-1 MINIMUM ELEVATION OF |
| | FLOODPROOFING, RELATIVE TO THE BASE FLOOD (BFE) OR |
| | DESIGN FLOOD ELEVATION (DFE)- OUTSIDE OF HIGH RISK |
| | FLOOD HAZARD AREAS. STRUCTURE CATEGORY- II (FOOTNOTE) |
| | C. (C) DRY FLOODPROOFING OF RESIDENTIAL BUILDINGS AND |
| | RESIDENTIAL PORTIONS OF MIXED USE BUILDINGS SHALL NOT |
| | BE PERMITTED. |
| | |
| | 1) SHEET 078-A2-0P2 PARKING 2 (LOWER LEVEL): |
| | |
| | 1A) COMPLIED2010 FBC-B 1612.4 DESIGN & CONSTRUCTION |
| | SHALL BE IN ACCORDANCE WITH ASCE 24-05. ASCE 24-05 |
| | TABLE 6-1. (FOOTNOTE) C. ( C ) DRY FLOODPROOFING OF |
| | RESIDENTIAL BUILDINGS AND RESIDENTIAL PORTIONS OF MIXED |
| | USE BUILDINGS SHALL NOT BE PERMITTED. |
| | |
| | 1B)2ND REQUEST. THE RESPONSE LETTER INDICATES THE |
| | ELEVATOR IS A TRACTION ELEVATOR AS IDENTIFIED. THERE IS |
| | NO REFERENCE TO THE ELEVATOR BEING A TRACTION ELEVATOR |
| | OR A REVISION NUMBER AND BEING CLOUDED, BUBBLED OR A |
| | DELTA. |
| | ELEVATOR # 9 IS NOT IDENTIFIED ON SHEET 012-LS-P1/ P2. |
| | SHEET 176-A5.15 DOES NOT INDICATE IF THIS ELEVATOR IS A |
| | HYDRAULIC ELEVATOR? PLEASE IF THE ELEVATOR IS HYDRAULIC |
| | SHOW COMPLIANCE WITH 2010 FBC-B 3011. (1-4). IF THIS |
| | ELEVATOR IS HYDRAULIC IN WILL THE SUMP PUMP BE TIED |
| | INTO THE EMERGENCY ELECTRICAL PANEL TO KEEP DAMAGE TO |
| | THE HYDRAULIC SYSTEM AND CAB A MINIMUM. FEMA BULLETIN |
| | 4-93. |
| | |
| | 1C) 2ND REQUEST. THE RESPONSE LETTER INDICATES THE |
| | ELEVATOR IS A TRACTION ELEVATOR, WHICH IS MACHINE |
| | ROOMLESS ELEVATOR AS IDENTIFIED. THERE IS NO REFERENCE |
| | TO THE ELEVATOR BEING A TRACTION ELEVATOR OR A REVISION |
| | NUMBER AND BEING CLOUDED, BUBBLED OR A DELTA. |
| | ELEVATOR # 9 PLEASE IDENTIFY WHERE THE MACHINE ROOM FOR |
| | ELEVATOR # 9 IS LOCATED? PLEASE SHOW COMPLIANCE WITH |
| | 2010 FBC-B 3006.4. 1 HOUR FIRE RATING. |
| | |
| | 1D) 2ND REQUEST. THE RESPONSE INDICATES THE ELEVATOR TO |
| | BE A OTIS GEN 2 AND INCLUDES FLOAT SWITCH AND SOFTWARE, |
| | IT WOULD APPEAR THERE WOULD BE PRODUCT LITERATURE |
| | SUBMITTED, RESEARCHED THE EQUIPMENT SPEC SHEETS 33 |
| | SHEETS NOT INCLUDED IN THIS FILE. |
| | THE OTHER ISSUE WITH ALL OF THE OTHER ELEVATORS THAT |
| | TRAVEL TO THE LOWER P2 PARKING LEVEL DEALS WITH THE |
| | FEMA TECHNICAL BULLETIN 4-93. FEMA REGULATION |
| | 60.3(A)(3) IF A PROPOSED BUILDING SITE WILL BE |
| | REASONABLY SAFE FROM FLOODING. IF A PROPOSED BUILDING |
| | SITE IS IN A FLOOD PRONE AREA, ALL NEW CONSTRUCTION AND |
| | SUBSTANTIAL IMPROVEMENTS SHALL? BE CONSTRUCTED WITH |
| | MATERIALS RESISTANT TO FLOOD DAMAGE,(III) BE |
| | CONSTRUCTED BY METHODS AND PRACTICES THAT MINIMIZE |
| | FLOOD DAMAGES, AND (IV) BE CONSTRUCTED WITH |
| | ELECTRICAL... EQUIPMENT AND OTHER SERVICES FACILITIES |
| | THAT ARE DESIGNED AND / OR LOCATED SO AS TO PREVENT |
| | WATER DAMAGE FROM ENTERING OR ACCUMULATING WITHIN THE |
| | COMPONENTS DURING CONDITIONS OF FLOODING. |
| | TO KEEP THE ELEVATOR CABS FROM HAVING SUBSTANTIAL |
| | DAMAGE FROM FLOODWATERS, IS THERE A INTERLOCKING |
| | CONTROL OR FLOAT SWITCH THAT WHEN ACTIVATED WILL KEEP |
| | THE CAB FROM DESCENDING INTO THE FLOODWATERS. |
| | THE OTHER QUESTION, IS NORMALLY WITH LOSS OF POWER THE |
| | ELEVATOR CABS DESCEND TO THE LOWEST LEVEL , WILL THE |
| | INTERLOCK AND OR FLOAT SWITCH ALLOW THE OVERRIDE? |
| | DURING TIMES OF FLOOD THIS WILL ENABLE ACCESSIBILITY TO |
| | THE LOWER PARKING GARAGE UNLESS THE OCCUPANT TRAVELS |
| | DOWN THE STAIRS. |
| | |
| | 1E) COMPLIED. SMOKE DOORS. DOORS P202/ ELEV. LOBBY 1, |
| | DOOR P203/ ELEV. LOBBY 2, DOOR P205 ELEV. LOBBY 3/ DOOR |
| | P206/ ELEV. LOBBY #4. , |
| | |
| | 1F) COMPLIED. FBC-B 905.3. STANDPIPES IN STAIRWELLS. |
| | |
| | 1G)SEMI-COMPLIED, SHEET 166-A5-01 IDENTIFIES VARIOUS |
| | WALLS WITH TAGS: |
| | |
| | 1G)(1) WALL IDENTIFICATION TAGGED WALLS 70, 71, 73, 74 |
| | & 75 ALL SHOW AN ANGLE IRON BRACING SYSTEM ATTACHED TO |
| | THE UNDERSIDE OF THE NEXT CONCRETE SLAB AND A NOTE |
| | INDICATING A CONTINUOUS FIRE RESISTIVE JOINT SYSTEM. |
| | UL LISTING U905 & U906 ARE THE LISTING FOR THE WALL |
| | ONLY. PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 714.2 |
| | AN RATED ASSEMBLY FOR THE DISSIMILAR MATERIALS AT THE |
| | JOINT WALL /SLAB JOINT (FIRE ?RESISTANT JOINT SYSTEM). |
| | |
| | 1ST ROUND COMMENT. THE BUILDING CORES CONTAINING |
| | STAIRWELLS 1 & 2 AND 3 & 4 DO NOT HAVE WALL |
| | IDENTIFICATION TAGS AS THE WALLS SURROUNDING THE |
| | PERIMETER OF THE BUILDING. SHEET 012-A0-31 THE LIFE |
| | SAFETY SHEET FOR THE PARKING GARAGES INDICATES FIRE |
| | RATED WALLS. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 1H) SEMI-COMPLIED. THE RESPONSE INDICATES THE VOID |
| | SPACE BETWEEN THE INTERSTITIAL FLOOR OF THE FPL VAULT |
| | WILL BE FILLED WITH STRUCTURAL GEOFOAM. PLEASE PROVIDE |
| | TESTING IN COMPLIANCE WITH 2603.3 SURFACE BURNING |
| | CHARACTERISTICS. ASTM E84 OR UL 723. |
| | |
| | 1ST ROUND OF COMMENTS. THE EAST WALL OF THE FPL VAULT |
| | DOES NOT INDICATE A WALL TAG. THE FLOOR ELEVATION IS |
| | INDICATED AT ELEVATION 6?-0? THIS WALL WILL STILL BE ON |
| | THIS LEVEL. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED, WALL NOT IDENTIFIED AS TO TYPE. |
| | |
| | NEW COMMENTS: |
| | 1I) COMMON COMMENT TO ALL FLOORS THE DOOR SCHEDULES |
| | FOUND ON SHEETS 331_A8.11 & 332_A8.12 LABEL ALL FIRE |
| | RATED DOORS AS B OR C LABEL. PLEASE RATE THEM IN |
| | MINUTES AND HOURS AS FBC-B TABLE 715.5. |
| | |
| | 2) SHEET 079-A2-0P1 (PARKING LEVEL 1 UPPER LEVEL): |
| | |
| | 2A-D) COMPLIED |
| | |
| | |
| | |
| | |
| | 2E) SEMI-COMPLIED. PLEASE BE AWARE THIS IS A EUROPEAN |
| | SYSTEM THAT PROBABLY DOES NOT HAVE AN UL LISTING, NOR |
| | WILL THE 50 HZ 3-PHASE HOOK UP TO THE US STANDARD 60 HZ |
| | ELECTRICAL SYSTEM. |
| | ELECTRICAL NOTE # 6 INDICATES THE NEED OF A CORNER PIT |
| | IN THE FLOOR. ADDITIONAL INFORMATION REQUIRED WHEREAS |
| | THE PIT LOCATION AND THE SIZE OF THE PIT. 107.2.1.3. |
| | 1ST REVIEW COMMENT. THIS LEVEL SHOWS STACKED PARKING, |
| | PLEASE PROVIDE DETAILS FOR THIS TYPE OF LIFT. HOW THE |
| | LIFT WILL OPERATE, MANUFACTURERS SPEC, ANCHORAGE FOR |
| | LIFT, IS THERE A VALET THAT PUTS THE CARS ON THE LIFT, |
| | ETC. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2F-G) COMPLIED |
| | |
| | 3) SHEET 013-A)-32 & 080-A2-01 LEVEL 1 (LOBBY): |
| | |
| | 3A-D) COMPLIED. |
| | |
| | 3E) SEMI-COMPLIED. ON THE LOBBY LEVEL THE DOORS TO THE |
| | GUEST SUITES LABELED GS01 ARE NOT FOUND IN THE DOOR |
| | SCHEDULE PAGE 331_A8-11. |
| | |
| | 1ST ROUND COMMENT. PLEASE BE AWARE THAT THE DOORS ARE |
| | NOT IDENTIFIED ON THIS SHEET, NOR ARE THEY IDENTIFIED |
| | ON SHEET 166-A5-01. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 3F)SEMI-COMPLIED. SHEET 098_A2-51A GUEST SUITE 1 COMMON |
| | WALL BATHROOM TO ATRIUM IS LABELED A WALL TYPE 3A. THIS |
| | WALL IS A 1 HOUR WALL AND HAS A STC RATING OF 47. |
| | PLEASE SEE FBC-B 1207.2 AIR-BORNE SOUND MINIMUM STC OF |
| | 50, ASTM E90. |
| | 1ST ROUND COMMENTS. PLEASE BE AWARE THAT THE WALL |
| | IDENTIFICATION TAGS ON THIS SHEET ARE MISSING AS WELL |
| | AS ON SHEET 166-A5-01. 107.2.1.3 ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 3G)2ND REQUEST. PLEASE NOTE IS FOR ALL FLOORS WITH |
| | ELEVATOR DOOR OPENINGS. THE PLANS DO NOT INDICATE A |
| | FIRE RATED DOOR ON THE ELEVATOR SHAFT. FBC-B 3002.1.1 |
| | OPENING PROTECTIVES OPENINGS IN HOISTWAY ENCLOSURES |
| | SHALL BE PROTECTED AS REQUIRED IN CHAPTER 7. OPENING |
| | PROTECTIVES TABLE 715.5.EXCEPTION THE FLOOR LEVEL |
| | DESIGNATED FOR RECALL SHALL REMAIN OPEN DURING PHASE I |
| | EMERGENCY RECALL OPERATION. WHAT FLOOR LEVEL WILL BE |
| | THE LEVEL DESIGNATED FOR RECALL? |
| | 1ST ROUND OF COMMENTS. GUEST ROOM CORRIDOR 102 SHOWS |
| | THE WALLS TO BE A MINIMUM OF A 1 HOUR FIRE RATING WITH |
| | THE EXCEPTION OF THE ELEVATOR OPENING? PLEASE PROVIDE |
| | COMPLIANCE WITH 2010 FBC-B TABLE 1018.1. |
| | |
| | 3H-K) COMPLIED.. |
| | |
| | 3L) 2ND REQUEST. THE 1ST LEVEL SHEET 080-A2-01/ |
| | 013-A)-32 LIFE SAFETY AND 2ND LEVEL SHEET 081-A2-02/ |
| | 014-A0-33 LIFE SAFETY 2ND LEVEL. THESE SHEETS DEPICT A |
| | 2 STORY ATRIUM. I?M NOT SPEAKING OF THE STAIRWAY TO |
| | BELOW. THE LOBBY FLOOR SHEET 080_A2.01 AND THE SHEET |
| | 081_A2.02 LEVEL 2 OF AMENITIES CONSTITUTES AN ATRIUM, |
| | WHERE THE AIR COMMUNICATES BETWEEN 2 STORIES. THESE |
| | WALLS IN COMMON SHOULD BE FIRE RATED FBC-B 404.6 WITH |
| | OPENING PROTECTIVES IN ACCORDANCE WITH TABLE 715.5. |
| | |
| | 1ST ROUND OF COMMENTS. THE 1ST LEVEL SHEET 080-A2-01/ |
| | 013-A)-32 LIFE SAFETY AND 2ND LEVEL SHEET 081-A2-02/ |
| | 014-A0-33 LIFE SAFETY 2ND LEVEL. THESE SHEETS DEPICT A |
| | 2 STORY ATRIUM. WHAT THE LIFE SAFETY SHEETS FAIL TO |
| | PROVIDE IS THE 1 HOUR FIRE BARRIER (2010 FBC-B 404.6) |
| | CONSTRUCTED IN ACCORDANCE WITH SECTION 707. THE PLANS |
| | DO NOT SHOW A CUT SECTION WHERE ONE OF THE EXCEPTIONS |
| | WAS TAKEN. ONE HOUR FIRE RATED WALLS WOULD BE REQUIRED |
| | WITH ANY SPACE THAT COMMUNICATED WITH THE ATRIUM AND |
| | OPENING PROTECTIVE IN COMPLIANCE WITH 2010 FBC-B TABLE |
| | 715.4. SMOKE CONTROL IS NOT REQUIRED SINCE THIS IS A 2 |
| | STORY ATRIUM. |
| | |
| | 3M-O) COMPLIED. 2010 FBC-B 404.8 INTERIOR FINISHES. |
| | |
| | 3O)(6) SEMI-COMPLIED. SHEET 184A-A5-52, THE DESIGNER OF |
| | RECORD HAS PROVIDED THE CHART SHOWING THE EXIT STAIR & |
| | RESIDENTIAL UNIT DISTRIBUTION TABLE. THE QUESTION STILL |
| | IS HOW WILL THE FIRE FIGHTERS KNOW THIS CHART EXIST, |
| | WILL A COPY OF THIS CHART BE POSTED IN THE FIRE COMMAND |
| | ROOM OR IN AN OVERALL FIRE MANUAL? |
| | |
| | 1ST ROUND OF COMMENTS. A CUT SECTION THROUGH THE |
| | BUILDING SHOWING WHICH STAIRWELLS SERVICE WHICH SUITES |
| | SINCE THE FLOORS WITH 3 SUITES USE STAIRWELLS 2 & 3 SO |
| | FIRE FIGHTERS WILL KNOW WHICH STAIRWELLS AND FIREMENS |
| | ELEVATORS TO USE FOR FIREFIGHTING AND OR EMERGENCIES. |
| | 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 3P-R) COMPLIED. 2010 FBC-B SECTION 403.3.2 WATER SUPPLY |
| | TO REQUIRED FIRE PUMPS |
| | |
| | 3S) BUILDING PROVISO: THE PLANS SHOW AT THE ENTRY LEVEL |
| | OF THE LOBBY A RECEPTION/ REGISTRATION DESK. PLEASE |
| | PROVIDE COMPLIANCE WITH FAIR HOUSING SPECIFICATION OF |
| | ANSI 4.31 ALSO SEE REACH RANGES. |
| | |
| | 3T) 2ND REQUEST. THIS COMMENT WILL STAND FOR ALL FLOORS |
| | WITH MULTIPLE R2 DWELLING UNITS ON THE SAME FLOOR OR |
| | DWELLING UNITS ABOVE OR BELOW THE OCCUPIED UNIT. PLEASE |
| | NOTE ALL 3 TEST ARE REQUIRED FOR ANY FLOOR |
| | UNDERLAYMENT. IF THERE IS TO BE TILE AND OR MARBLE THE |
| | UNDERLAYMENT HAS TO BEEN TESTED ALL 3 TEST, THIS HOLDS |
| | TRUE FOR WOOD VENEERS AS WELL. PLEASE KEEP THE 3 TEST |
| | CRITERIA TOGETHER, IF THEY ARE POSTED ON THE SAME PLANS |
| | SHEET, WE CAN THEN LET THE ACTUAL TEST APPROVALS TO BE |
| | A DEFERRED SUBMITTAL AFTER THE ISSUANCE OF THE PERMIT. |
| | WE NEED THE CONTRACTOR OR SUB-CONTRACTORS OR VENDORS TO |
| | SEE THERE ARE 3 DIFFERENT CRITERIA IN THE SELECTING |
| | FLOOR UNDER-LAYMENTS. THANK YOU FOR YOUR HELP IN THIS |
| | MATTER. |
| | |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 3T)(1) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 3T)(2) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 3T)(3) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 3U) COMPLIED. |
| | |
| | |
| | 4) SHEET 014-A0-33/ 082-A2-03: 2ND LEVEL GUEST SUITES. |
| | |
| | 4A) COMPLIED. GUEST SUITES ARE PURCHASED BY THE CURRENT |
| | OWNERS TO BE USED AS A ALTERNATE SLEEPING ROOM. |
| | 4B)2ND REQUEST. THE SHAFT WALLS HAVE NOW BEEN |
| | IDENTIFIED AS WALL IDENTIFICATION TAGS, 1 & 52. PLEASE |
| | NOTE THESE WALLS ARE COMMON WITHIN THE TENANT SPACE AND |
| | ONLY HAVE A STC RATING OF 47 NOT THE REQUIRED 50. |
| | FBC-B 2010 SECTION 1207.2 AIR-BORNE SOUND. |
| | |
| | 1ST ROUND OF COMMENTS. THERE IS A DISCREPANCY IN PLANS |
| | IT WOULD APPEAR. SHEET 014-A0-33 LEVEL 2 GUEST SUITES |
| | IT APPEARS THE MECHANICAL UNIT HP-1IN GUEST SUITES 11 & |
| | 12 ARE LOCATED IN A ONE HOUR SHAFT WHEREAS THE UNITS 9 |
| | & 10 THE UNITS ARE NOT LOCATED IN A RATED WALL. IT |
| | APPEARS IN UNITS 11 & 12 THERE IS A VERTICAL 8X16 INCH |
| | EXHAUST DUCT NOT SHOWN IN A SHAFT, MECHANICAL SHEETS |
| | INDICATE THAT IN SOME AREA 2 HOUR FLAME BAR IS TO BE |
| | INSTALLED. PLEASE PROVIDE DETAILED INFORMATION IN |
| | RESPONSE AS TO WHAT AREAS ARE TO BE SHAFTS, HOUR RATING |
| | OF SHAFTS, WHERE THE FLAME BAR IS TO BE INSTALLED AND |
| | FIRE STOPPING ASSEMBLIES FOR THROUGH PENETRATIONS. THIS |
| | COMMENT WILL BE COMMON FOR THE 3 FLOORS OF GUEST |
| | SUITES. 2010 FBC-B 708.2.4 /716.6 HORIZONTAL |
| | ASSEMBLIES. THIS CONDITION APPEARS ON THE 3RD LEVEL OF |
| | GUEST SUITES AS WELL. |
| | |
| | 4C-D) COMPLIED |
| | . |
| | |
| | 5) SHEET 014-A)-33/ 098-A2-51A2: 2ND LEVEL AMENITIES/ |
| | 103-A2.53A THE 3RD LEVEL GUEST SUITES. |
| | |
| | 5A-B) COMPLIED. |
| | |
| | 5C)2ND REQUEST. SHEET 098_A2-51A2 &/ 103-A2.53A THE 3RD |
| | LEVEL GUEST SUITES IS MISSING BOTH THE WALL & DOOR |
| | IDENTIFICATION TAGS. CODE COMPLIANCE CANNOT BE |
| | DETERMINED. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 5D) 2ND REQUEST. SHEET 014-A)-33 IS THE 2ND LEVEL OF |
| | THE ATRIUM. THIS SHEETS DEPICTS THE 2ND FLOOR OF THE |
| | ATRIUM. WHAT THE LIFE SAFETY SHEETS FAIL TO PROVIDE IS |
| | THE 1 HOUR FIRE BARRIER (2010 FBC-B 404.6) CONSTRUCTED |
| | IN ACCORDANCE WITH SECTION 707. THE PLANS DO NOT SHOW A |
| | CUT SECTION WHERE ONE OF THE EXCEPTIONS WAS TAKEN. ONE |
| | HOUR FIRE RATED WALLS WOULD BE REQUIRED WITH ANY SPACE |
| | THAT COMMUNICATED WITH THE ATRIUM AND OPENING |
| | PROTECTIVE IN COMPLIANCE WITH 2010 FBC-B TABLE 715.4. |
| | SMOKE CONTROL IS NOT REQUIRED SINCE THIS IS A 2 STORY |
| | ATRIUM. PLEASE NOTE THE 3 LEVELS OF THE R2 GUEST ROOMS |
| | TRAVEL THROUGH A 1 HOUR FIRE RATED ACCESS CORRIDOR INTO |
| | THE ATRIUM. |
| | |
| | 5E) COMPLIED |
| | |
| | 5F) 2ND REQUEST. THIS SHEET INDICATES THE BRIDGE |
| | SECTION OF THE 2ND LEVEL IS INDICATED AS A MEZZANINE |
| | LOBBY. THE 2ND FLOOR AREA THAT IS OPEN AND COMMUNICATES |
| | IS OVER THE 1/3RD OF THE OPEN AREAS ALLOWED BY FBC-B |
| | 505.2 EXCEPTION # 2 FOR TYPE I TYPE II BUILDINGS. THIS |
| | IS A TRUE 2 STORY ATRIUM, FBC-B 404.6 ENCLOSURES OF |
| | ATRIUMS. |
| | |
| | 5G)2ND REQUEST. SHEET 014-A0-33 POOL DECK STAIR # 6 & 7 |
| | SHOW THE USE OF AN AREA OF RESCUE ASSISTANCE. |
| | THE RESPONSE INDICATES TWO-WAY COMMUNICATION SYSTEM HAS |
| | BEEN PROVIDED, SEE SHEET A0.33. |
| | PLEASE SHOW COMPLIANCE WITH ALL ASPECTS OF THE 2003 IBC |
| | 1007.6. |
| | |
| | AREA OF REFUGE. 2003 IBC-B 1007.6 .3 TWO-WAY |
| | COMMUNICATION. AREAS OF REFUGE SHALL BE PROVIDED WITH |
| | TWO-WAY COMMUNICATION SYSTEM BETWEEN THE AREA OF REFUGE |
| | AND A CONTROL POINT. IF THE CENTRAL CONTROL POINT IS |
| | NOT CONSTANTLY ATTENDED, THE AREA OF REFUGE SHALL ALSO |
| | HAVE CONTROLLED ACCESS TO A PUBLIC TELEPHONE SYSTEM. |
| | LOCATION OF THE CENTRAL CONTROL POINT SHALL BE APPROVED |
| | BY THE FIRE DEPARTMENT. TWO-WAY COMMUNICATION SYSTEM |
| | SHALL INCLUDE BOTH AUDIBLE AND VISIBLE SIGNALS. |
| | |
| | 1007.6.4 INSTRUCTIONS. IN AREAS OF REFUGE THAT HAVE A |
| | TWO-WAY EMERGENCY COMMUNICATIONS SYSTEM, INSTRUCTIONS |
| | ON THE USE OF THE AREA UNDER EMERGENCY CONDITIONS SHALL |
| | BE POSTED ADJOINING THE COMMUNICATIONS SYSTEM. THE |
| | INSTRUCTIONS SHALL INCLUDE ALL OF THE FOLLOWING; |
| | 1) DIRECTIONS TO FIND OTHER MEANS OF EGRESS. |
| | 2) PERSONS ABLE TO USE THE EXIT STAIRWAY DO SO AS SOON |
| | AS POSSIBLE, UNLESS THEY ARE ASSISTING OTHERS. |
| | 3) INFORMATION ON THE PLANNED AVAILABILITY OF |
| | ASSISTANCE IN THE USE OF STAIRS OR SUPERVISED OPERATION |
| | OF ELEVATORS AND HOW TO SUMMON SUCH ASSISTANCE. 4) |
| | DIRECTIONS FOR THE USE OF THE EMERGENCY COMMUNICATIONS |
| | SYSTEM. |
| | |
| | 1007.6.5 IDENTIFICATION. EACH DOOR PROVIDING ACCESS TO |
| | AN AREA OF REFUGE FROM AN ADJACENT FLOOR AREA SHALL BE |
| | IDENTIFIED BY A SIGN COMPLYING WITH ICC A117., STATING |
| | AREA OF REFUGE, AND INCLUDING THE INTERNATIONAL SYMBOL |
| | OF ACCESSIBILITY. WHERE EXIT SIGN ILLUMINATION IS |
| | REQUIRED BY SECTION 1011.2, THE AREA OF REFUGE SIGN |
| | SHALL BE ILLUMINATED. ADDITIONALLY, TACTILE SIGNAGE |
| | COMPLYING WITH ICC A117.1 SHALL BE LOCATED AT EACH DOOR |
| | TO AN AREA OF REFUGE. |
| | |
| | 1007.7. SIGNAGE. AT EXITS AND ELEVATORS SERVING A |
| | REQUIRED ACCESSIBLE SPACE BUT NOT PROVIDING AN APPROVED |
| | ACCESSIBLE MEANS OF EGRESS, SIGNAGE SHALL BE INSTALLED |
| | INDICATING THE LOCATION OF ACCESSIBLE MEANS OF EGRESS |
| | |
| | 1ST ROUND COMMENT. SHEET 014-A0-33 POOL DECK STAIR # 6 |
| | & 7 SHOW THE USE OF AN AREA OF RESCUE |
| | ASSISTANCE. THE 2010 FBC-B 1007.1 ACCESSIBLE MEANS OF |
| | EGRESS. ACCESSIBLE MEANS OF EGRESS SHALL BE PROVIDED IN |
| | ACCORDANCE WITH THE APPLICABLE SECTIONS OF THE FLORIDA |
| | BUILDING CODE, ACCESSIBILITY. |
| | 2010 FBC-ACCESSIBILITY CODE. ACCESSIBLE MEANS OF EGRESS |
| | . 207.1 GENERAL. MEANS OF EGRESS SHALL COMPLY WITH |
| | SECTION 1003.2.13 OF THE INTERNATIONAL BUILDING CODE |
| | (2000 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF |
| | THE INTERNATIONAL BUILDING CODE (2003 EDITION) |
| | (INCORPORATED BY REFERENCE, SEE "REFERENCED STANDARDS" |
| | IN CHAPTER 1). |
| | PLEASE SHOW FULL COMPLIANCE FOR THE AREA OF REFUGE |
| | ASSISTANCE, 2003 IBC-B REQUIREMENTS 1007.6.(1-7) & |
| | 1007.8(1-3). |
| | |
| | |
| | START REVIEWS MON. 8/29/16 |
| | |
| | |
| | 5H) COMPLIED. FAIR HOUSING. THE DINING ROOM, BEAUTY |
| | PARLOR AND GUEST ROOMS ARE UNDER FAIR HOUSING ACT. FAIR |
| | HOUSING IS TO BE APPLIED THEN ONLY ACCESS TO THE POOL |
| | DECK WILL BE REQUIRED. |
| | |
| | 5I) COMPLIED. FAIR HOUSING. AN ACCESSIBLE ROUTE TO THE |
| | LOWER POOL DECK AREA. FAIR HOSING ANSI A117.1 4.3 (C) |
| | CONNECTING ACCESSIBLE BUILDING OR FACILITY ENTRANCES |
| | WITH ACCESSIBLE SPACES AND ELEMENTS WITHIN THE BUILDING |
| | OR FACILITY, INCLUDING ADAPTABLE DWELLING UNITS. |
| | |
| | 5J) COMPLIED. FAIR HOUSING COMPLIANCE FOR THE STEAM |
| | ROOMS AND SAUNAS. FAIR HOUSING COMMON USE SPACES AND |
| | FACILITIES. WHEN ANSI DOES NOT CONTAIN SPECIFICATIONS |
| | FOR SPECIFIC FACILITIES OR FEATURE IN QUESTION RELATED |
| | HUMAN FACTORS AND PERFORMANCE SPECIFICATIONS MUST BE |
| | USED TO ACHIEVE ACCESSIBILITY. SUCH SPECIFICATIONS |
| | INCLUDE, BUT ARE NOT LIMITED TO, 4.2 SPACE ALLOWANCES |
| | AND REACH RANGES, 4.3 ACCESSIBLE ROUTE, 4.4 PROTRUDING |
| | OBJECTS, 4.5 GROUND & FLOOR SURFACES, AND 4.25 |
| | OPERATING MECHANISMS. |
| | |
| | 5K) 2ND REQUEST, SEMI-COMPLIED, THE RESPONSE INDICATES |
| | HOW COMPLIANCE CAN BE OBTAINED. COMPLIANCE WITH COMMENT |
| | 5G MUST BE MET FOR COMMENT TO BE COMPLIED WITH. |
| | 1ST ROUND COMMENT. SHEET 014-A0-33 THE LOWER POOL DECK |
| | IT APPEARS THERE IS ONLY ONE RAMP (NOT MARKED, NOR |
| | ELEVATION CHANGES GIVEN) BETWEEN THE POOL DECK AND POOL |
| | THERE ARE 116 OCCUPANTS AND WHAT APPEARS TO BE ONLY ONE |
| | ACCESSIBLE MEANS OF EGRESS. PLEASE SHOW COMPLIANCE |
| | WITH: 2010 FBC-BUILDING CODE 1007.1 ACCESSIBLE MEANS OF |
| | EGRESS. ACCESSIBLE MEANS OF EGRESS SHALL BE PROVIDED IN |
| | ACCORDANCE WITH THE APPLICABLE SECTIONS OF THE FLORIDA |
| | BUILDING CODE, ACCESSIBILITY. |
| | 2010 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF |
| | EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | |
| | |
| | |
| | 6) SHEETS 015-A0-34 LEVELS 5-10. 11-17 (TIER 1) LEVELS |
| | 18-19 TIER 2. / 083-A2-05 LEVEL 5/ 084-A2-06 LEVELS |
| | 6-9, 11 TIER 1; |
| | 6A) 2ND REQUEST. THIS COMMENT IS A COMMON COMMENT FOR |
| | ALL DWELLING UNITS TIER 1 LEVELS 5-9 &11. THE LIFE |
| | SAFETY PLAN SHOWS (2) REQUIRED MEANS OF EGRESS PER UNIT |
| | OVER 3 STORIES, COMMON PATH OF TRAVEL EXCEEDED WITH ONE |
| | MEANS OF EGRESS, BECAUSE THEY ARE OVER THE 125 FEET |
| | REQUIRED BY 2010 FBC-B 1014.3 EXCEPTION # 4. |
| | |
| | 6A)(1) COMPLIED. THE PLANS SHOW THE 1ST COMMON PATH OF |
| | TRAVEL EXITING THROUGH THE FRONT ENTRY DOORS THROUGH AN |
| | ELEVATOR LOBBY, THE LIFE SAFETY PLANS WILL NEED TO |
| | INDICATE IF THE ELEVATOR HOIST WAYS ARE PRESSURIZED TO |
| | ALLOW EXITING THROUGH THE ELEVATOR LOBBY. 2010 FBC-B |
| | 708.14.1 ELEVATOR LOBBIES. |
| | |
| | 6A)(2) 2ND REQUEST. THE RESPONSE INDICATES A ISSUE WITH |
| | LOCKABLE DOORS ONLY NOT THE CODE SECTION OF NO EGRESS |
| | THROUGH STORAGE ROOMS, CLOSETS OR SPACES USED FOR |
| | SIMILAR PURPOSES. |
| | |
| | 1ST ROUND COMMENTS. THE 2ND ISSUE IS THE COMMON PATH OF |
| | TRAVEL THROUGH THE LAUNDRY/ STORAGE/ UTILITY ROOM. |
| | PLEASE SEE THE 2010 FBC-B SECTION 1014.2.1(4) 4. EGRESS |
| | SHALL NOT PASS THROUGH KITCHENS, STORAGE ROOMS, CLOSETS |
| | OR SPACES USED FOR SIMILAR PURPOSES. NOTE THE EXCEPTION |
| | IS ONLY FOR A KITCHEN AREA SERVING ADJOINING ROOMS |
| | CONSTITUTING PART OF THE SAME DWELLING UNIT OR SLEEPING |
| | UNIT. |
| | |
| | 6B) COMPLIED. COMMON COMMENT FOR ALL FLOORS. EXITING |
| | CAPACITY ANALYSIS FOR ALL TIERS SHOW A 36 INCH DOORWAY |
| | AND THE EXIT CAPACITY AT 180 OCCUPANTS. THIS WOULD MEAN |
| | YOU HAVE OFFSET HINGES ON THE EXIT DOORS SO THERE IS A |
| | FULL 36 INCHES CLEAR WIDTH FROM THE FACE OF THE DOOR |
| | WHEN OPEN AT 90 DEGREES TO THE OPPOSING LATCH SIDE OF |
| | THE DOOR AND NOT INCLUDING THE DOOR STOP. SEE 2010 |
| | FBC-B 1008.1.1. CLEAR OPENINGS OF DOORWAYS WITH |
| | SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF |
| | THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. |
| | THE ACTUAL ALLOWABLE MAXIMUM OCCUPANT LOAD IS CLOSER TO |
| | 167. |
| | |
| | 7) 2ND REQUEST. SHEET 016-A0-35 LEVELS 20 & 21 / |
| | 090-A2-20 LEVEL 20 REFERS TO SHEET 089- A2.18 FOR UNITS |
| | A & B. SHEET 090-A2-20 FOR UNIT C. SAME COMMENTS AND |
| | ISSUES AS COMMENTS 6A AND 6B. |
| | |
| | 8)2ND REQUEST. SHEET 017-A0-36 LIFE SAFETY PLANS FOR |
| | LEVEL 22 & 23/ 092-A2-22 & 093-A2-23. SAME COMMENTS AND |
| | ISSUES AS COMMENTS 6A AND 6B. |
| | |
| | 9) PROVISO: SHEET 017-A0-36 LIFE SAFETY PLANS FOR LEVEL |
| | 23/ SHEET 093-A2-23. AT OWN RISK!!!!! |
| | THE COMMON PATH OF TRAVEL THROUGH THE LAUNDRY/ STORAGE/ |
| | UTILITY ROOM. PLEASE SEE THE 2010 FBC-B SECTION |
| | 1014.2.1(4) 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, |
| | STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR |
| | PURPOSES. NOTE THE EXCEPTION IS ONLY FOR A KITCHEN AREA |
| | SERVING ADJOINING ROOMS CONSTITUTING PART OF THE SAME |
| | DWELLING UNIT OR SLEEPING UNIT. |
| | |
| | 10) SHEET 018-A0-37 LEVELS 24 &25/ SHEET 094-A2-24 |
| | LEVEL 24 & 095-A2-25. |
| | |
| | 10A)2ND REQUEST. UNIT PH-24N & PH25N HAS THE SAME |
| | ISSUES AS COMMENT 6A)(1) ELEVATOR LOBBY & 6A)(2) EGRESS |
| | THROUGH STORAGE/ UTILITY CLOSET / LAUNDRY ROOM. THE |
| | 2010 FBC-B SECTION 1014.2.1(4) 4. EGRESS SHALL NOT PASS |
| | THROUGH KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED |
| | FOR SIMILAR PURPOSES. |
| | |
| | 10B) COMPLIED 2010 FBC-B 708.14.1 ELEVATOR SHAFTS ARE |
| | PRESSURIZED. |
| | |
| | 11) SHEET 019-A)-38 LEVEL 26 MECHANICAL FLOOR - ROOF / |
| | 096-A2-26 ARCH. MECHANICAL FLOOR |
| | PLAN. A122-A2-76ALEVEL 26 NORTH, 411-M2-26 & 374.S2-26 |
| | STRUCTURAL MECHANICAL ROOF FRAMING PLAN. |
| | |
| | |
| | |
| | 11A) NEW COMMENT.. SHEET 122-A2-76A ONE WALL THAT |
| | ENCLOSES STAIR # 2 IS IDENTIFIED WITH A WALL TAG # 78 |
| | THIS WALL DESIGNATION IS NOT FOUND ON SHEET 330-A8-02. |
| | 1ST ROUND OF COMMENTS. SHEET 122-A2-76A NONE OF THE |
| | ARCHITECTURAL NOR STRUCTURAL SHEETS, PROVIDE A ROOM & |
| | WALL IDENTIFICATION TAG FOR THE WALL IN THE UPPER RIGHT |
| | CORNER OF THE BUILDING, THE SAME WALL IS ALSO COMMON TO |
| | STAIR TOWER #2 AND FIREMANS VESTIBULE 2601. ADDITIONAL |
| | INFORMATION IS REQUIRED BOTH THE FIREMANS VESTIBULE |
| | (1HR.) AND THE STAIR SHAFT(2 HR.) ARE FIRE RATED |
| | PROTECTED. 3007.4.2 & 708.4. |
| | |
| | 11B-G) COMPLIED. |
| | |
| | 11H)COMPLIED. SHEET 122-A2-76A LEVEL 26 PLEASE NOTE |
| | ROOFTOP AND FLOOR ELEVATION TAGS ARE PROVIDED. |
| | |
| | 11I) 2ND REQUEST. SEMI-COMPLIED. RESPONSE INDICATES SEE |
| | SHEETS A2,56A AND A2.76B. SHEET A2-76B SHOWS THE DOORS |
| | WITH IDENTIFICATION TAGS BUR NOT THE WALLS. SHEET |
| | A2.56A IS THE FLOOR LEVELS 5-9, 11-17? DO YOU MEAN |
| | A2-26 NEITHER THE WALLS NOR DOORS ARE IDENTIFIED? |
| | 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. |
| | 1ST ROUND OF COMMENTS. SHEET 171-A5-06 PLEASE NOTE NONE |
| | OF THE WALLS NOR DOORS ARE PROVIDED WITH IDENTIFICATION |
| | TAGS, PLANS ARE INCOMPLETE, 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 11J) COMPLIED. SHEET 171-A5-06 AND 096-A2-26 ELEVATOR |
| | CONTROL ROOM 3, 4 &6. |
| | |
| | 11K-N) COMPLIED. |
| | |
| | 11O) 2ND REQUEST. THE SHEET 123_A2-76B DOES HAVE A NOTE |
| | WHERE THE VERTICAL BRACING OCCURS IN THE EXTERIOR |
| | CORRIDOR 2604 OUTLINE OF SCREEN WALL & STEEL BRACING |
| | ABOVE. THE STRUCTURAL SHEETS 374_S2-26 DOES NOT |
| | INDICATE SUCH DETAILS. A DIFFERENT VERSION IS FOUND ON |
| | SHEET 375_S2-27 WHERE THE VERTICAL LEG AND BRACING |
| | STILL APPEAR TO BE IN THE CORRIDOR. |
| | 1ST ROUND COMMENT. SHEET 096-A2-26 THE MECHANICAL |
| | EQUIPMENT SCREEN BRACING SYSTEM AS DRAWN HAS LEGS THAT |
| | GO INTO THE CORRIDOR 2604 BLOCKING ACCESS, BLOCKING |
| | ENTRY TO A EXTERIOR MECHANICAL ROOM 2603 AND ALSO TO |
| | ROOM 2606. PLEASE CORRECT THESE AREAS. |
| | |
| | 12) SEMI- COMPLIED. SHEET 431-M4-01 MECHANICAL DETAILS, |
| | DETAIL 20 COOLING TOWER VIBRATION ISOLATOR. |
| | RESPONSE INDICATES SEE SHEET 395_A-S5-31 SEE DETAIL # 4 |
| | FOR CONCRETE PIER FOR A/C ROOF TOP EQUIPMENT. PLEASE |
| | PROVIDE REQUIRED CLEARANCES BELOW RAISED ROOF MOUNTED |
| | MECHANICAL UNITS, SEE TABLE 1509.7 |
| | FBC-B. TAKE THE MEASUREMENTS FROM THE LOWEST HORIZONTAL |
| | FRAMING MEMBER. |
| | |
| | 1ST ROUND OF COMMENTS. SHEET 431-M4-01 MECHANICAL |
| | DETAILS, DETAIL 20 COOLING TOWER VIBRATION ISOLATOR |
| | DETAIL TO BE REVIEWED BY THE STRUCTURAL ENGINEER OF |
| | RECORD, AND WITH THEIR SHOP DRAWING STAMP OF APPROVAL. |
| | PLEASE NOTE THE STRUCTURAL BASE OR SUPPORT WILL NEED TO |
| | BE DESIGNED BY THE STRUCTURAL ENGINEER OR HIS DELEGATE |
| | WITH THE STRUCTURAL ENGINEERS APPROVAL BEFORE SUBMITTAL |
| | TO THE BUILDING DEPARTMENT FOR REVIEW. |
| | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. |
| | |
| | |
| | 13) BUILDING PROVISO: DEFERRED SUBMITTALS: SHEET |
| | 431-M4-01 MECHANICAL DETAILS EQUIPMENT SUPPORT CURB |
| | DETAIL & THYBAR VIBRATION CURB III DETAIL FOR OAU-1 & |
| | 2. PLEASE PROVIDE THE PRODUCT APPROVALS FOR CURB |
| | DETAILS. TO BE REVIEWED BY THE STRUCTURAL ENGINEER OF |
| | RECORD, AND WITH THEIR SHOP DRAWING STAMP OF APPROVAL. |
| | PLEASE NOTE THE STRUCTURAL ANCHOR TO THE BASE OR |
| | SUPPORT AS WELL AS THE UNIT TO THE CURB FOR MOMENT OF |
| | OVERTURNING, WILL NEED TO BE DESIGNED BY THE STRUCTURAL |
| | ENGINEER OR HIS DELEGATE WITH THE STRUCTURAL ENGINEERS |
| | APPROVAL BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT |
| | FOR REVIEW. |
| | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 14) SHEET 131-A3-21. |
| | 14A) COMPLIED. |
| | |
| | 14B) ELEVATORS 2/4 DO NOT CONTINUE THROUGH TO THE ROOF. |
| | PLEASE PROVIDE WHERE COMPLIANCE WITH SECTIONS OF THE |
| | 2010 FBC-B CAN BE FOUND: |
| | |
| | 14B)(1) 2ND REQUEST IDENTIFY THE SHAFT THAT GOES TO THE |
| | ROOF TOP. 3004.1 VENTS REQUIRED. HOISTWAYS OF ELEVATORS |
| | PENETRATING MORE THAN THREE STORIES SHALL BE PROVIDED |
| | WITH A MEANS FOR VENTING SMOKE AND HOT GASES TO THE |
| | OUTER AIR IN CASE OF FIRE. FOR R1 AND R2 OCCUPANCIES |
| | VENTING IS REQUIRED. |
| | |
| | 14B)(2) 2ND REQUEST IDENTIFY THE SHAFT AND ROOF TOP |
| | VENT, SIZE OF THE AREA VENTING. 3004.2 LOCATION OF |
| | VENTS. VENTS SHALL BE LOCATED AT THE TOP THE HOISTWAY |
| | AND SHALL OPEN EITHER DIRECTLY TO THE OUTER AIR OR |
| | THROUGH NONCOMBUSTIBLE DUCTS TO THE OUTER AIR. |
| | NONCOMBUSTIBLE DUCTS SHALL BE PERMITTED TO PASS THROUGH |
| | THE ELEVATOR MACHINE ROOM, PROVIDED THAT PORTIONS OF |
| | THE DUCTS LOCATED OUTSIDE THE HOISTWAY OR MACHINE ROOM |
| | ARE ENCLOSED BY CONSTRUCTION HAVING NOT LESS THAN THE |
| | FIRE-RESISTANCE RATING REQUIRED FOR THE HOISTWAY. HOLES |
| | IN THE MACHINE ROOM FLOORS FOR THE PASSAGE OF ROPES, |
| | CABLES OR OTHER MOVING ELEVATOR EQUIPMENT SHALL BE |
| | LIMITED AS NOT TO PROVIDE GREATER THAN 2 INCHES (51 MM) |
| | OF CLEARANCE ON ALL SIDES. |
| | |
| | 14)(3) 2ND REQUEST. 3004.3 AREA OF VENTS. EXCEPT AS |
| | PROVIDED FOR IN SECTION 3004.3.1, THE AREA OF THE VENTS |
| | SHALL NOT BE LESS THAN 31/2 PERCENT OF THE AREA OF THE |
| | HOISTWAY NOR LESS THAN 3 SQUARE FEET (0.28 M2) FOR EACH |
| | ELEVATOR CAR, AND NOT LESS THAN 31/2 PERCENT NOR LESS |
| | THAN 0.5 SQUARE FEET (0.047 M2) FOR EACH DUMBWAITER CAR |
| | IN THE HOISTWAY, WHICHEVER IS GREATER. OF THE TOTAL |
| | REQUIRED VENT AREA, NOT LESS THAN ONE-THIRD SHALL BE |
| | PERMANENTLY OPEN. CLOSED PORTIONS OF THE REQUIRED VENT |
| | AREA SHALL CONSIST OF OPENINGS GLAZED WITH ANNEALED |
| | GLASS NOT GREATER THAN 1/8 INCH (3.2 MM) IN THICKNESS. |
| | |
| | |
| | 15) SHEET 137-A3-31 DETAILS 1 & 2 & SHEET A0.23 |
| | EXTERIOR SYSTEMS. |
| | |
| | 15A)2ND REQUEST. THE SHEET 137-A3-31 SHOWS VARIOUS |
| | AREAS WHERE METAL PANELS ARE GOING TO BE INSTALLED ON |
| | THE EXTERIOR OF THE BUILDING. TO DATE NO PLANS HAVE |
| | BEEN SUBMITTED FOR COMPLIANCE. THE RESPONSE STATES |
| | THESE PANELS ARE METAL PLATE PANELS AND POSSIBLY THE |
| | USE OF MCM PANELS. THE SYSTEM IS GOING TO HAVE TO BE |
| | BETTER DEFINED AS TO USAGE WEATHER ABILITY, MATERIALS |
| | AND ANCHORAGE FOR THE COMPONENT PORTION OF THE |
| | BUILDING. |
| | AT THE 26TH LEVEL THERE ARE METAL SKINNED ARCHES |
| | ARCHITECTURAL ELEMENTS AS WELL AS LEVEL 1 FIN , THAT |
| | NEED STRUCTURAL DETAILS THE PAGES REFERENCED S5.31 ARE |
| | FOR THE A/C CHILLER SCREEN AND FOR PILLARS FOR THE A/C |
| | CHILLER. IS THIS AN ELEMENT THAT YOU WOULD LIKE TO A |
| | DEFERRED SUBMITTAL. |
| | |
| | BOTH INDICATE THE USE OF METAL WALL PANELS, THERE ARE |
| | NO CUT SECTIONS INDICATING MORE INFORMATION ON THE |
| | PANELS. COMPONENTS AND CLADDING FBC-B, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. PLEASE SEE THE 2010 FBC-B |
| | SECTION 1407.3 ARCHITECTURAL TRIM AND EMBELLISHMENTS. |
| | MCM USED AS ARCHITECTURAL TRIM OR EMBELLISHMENTS SHALL |
| | COMPLY WITH SECTIONS 1407.7 THROUGH 1407.14. |
| | 1407.4 STRUCTURAL DESIGN. MCM SYSTEMS SHALL BE DESIGNED |
| | AND CONSTRUCTED TO RESIST WIND LOADS AS REQUIRED BY |
| | CHAPTER 16 FOR COMPONENTS AND CLADDING. |
| | |
| | 1407.5 APPROVAL. RESULTS OF APPROVED TESTS OR AN |
| | ENGINEERING ANALYSIS SHALL BE SUBMITTED TO THE BUILDING |
| | OFFICIAL TO VERIFY COMPLIANCE WITH THE REQUIREMENTS OF |
| | CHAPTER 16 FOR WIND LOADS. 1407.6 WEATHER RESISTANCE. |
| | |
| | 15B) COMPLIED. BALCONY DIVIDER GLASS TO HAVE A ARTIC |
| | SNOW PVB INNER CORE, FBC-B 2407 |
| | |
| | 15C) COMPLIED. |
| | |
| | 16)2ND REQUEST. SHEETS 108-A2-68A & DETAIL # 2/ |
| | 278-A6-85C BALCONY DEMISING GLASS WALL. THE FLOOR PLAN |
| | 108-A2-68A DOES SHOW THE USE OF BALCONY DEMISING GLASS |
| | WALL AS WELL AS THE ELEVATION SHEET 137-A3-31. THE |
| | DETAIL 2 ON SHEET 278-A6-85C APPEAR TO BE FOR INSULATED |
| | SPANDREL PANEL BUT NOT FOR THE GLASSED DEMISING WALL IT |
| | WOULD APPEAR THIS IS THE WRONG DETAIL. |
| | |
| | 17) SHEET 157-A4-14 DETAIL 11 SHOWS THE INSTALLATION OF |
| | A TERRA COTTA RAIN SCREEN. REFERENCES DETAIL 11/ |
| | 157-A4-14 PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B |
| | SECTIONS: |
| | |
| | 17A) 2ND REQUEST, PLEASE PROVIDE PRODUCT TESTING. |
| | 1403.2 WEATHER PROTECTION. |
| | |
| | 17B) 2ND REQUEST. RESPONSE INDICATES REFER TO |
| | STRUCTURAL LOADS REPORT. THE PLANS DO NOT PROVIDE |
| | ANCHORAGE, TYPE OF ANCHOR, AT WHAT SPACING AN NO |
| | PRODUCT DATA HAS BEEN SUBMITTED FOR THIS SYSTEM. 1403.3 |
| | STRUCTURAL. EXTERIOR WALLS, AND THE ASSOCIATED |
| | OPENINGS, SHALL BE DESIGNED AND CONSTRUCTED TO RESIST |
| | SAFELY THE SUPERIMPOSED LOADS REQUIRED BY CHAPTER 16. |
| | |
| | 17C) 2ND REQUEST. THE PLANS DO NOT PROVIDE ANCHORAGE, |
| | TYPE OF ANCHOR, AT WHAT SPACING AN NO PRODUCT DATA HAS |
| | BEEN SUBMITTED FOR THIS SYSTEM. |
| | |
| | 1405.9 TERRA COTTA. ANCHORED TERRA COTTA OR CERAMIC |
| | UNITS NOT LESS THAN 15/8 INCHES (41 MM) THICK SHALL BE |
| | ANCHORED DIRECTLY TO MASONRY, CONCRETE OR STUD |
| | CONSTRUCTION. TIED TERRA COTTA OR CERAMIC VENEER UNITS |
| | SHALL BE NOT LESS THAN 15/8 INCHES (41 MM) THICK WITH |
| | PROJECTING DOVETAIL WEBS ON THE BACK SURFACE SPACED |
| | APPROXIMATELY 8 INCHES (203 MM) O.C. THE FACING SHALL |
| | BE TIED TO THE BACKING WALL WITH CORROSION-RESISTANT |
| | METAL ANCHORS OF NOT LESS THAN NO. 8 GAGE WIRE |
| | INSTALLED AT THE TOP OF EACH PIECE IN HORIZONTAL BED |
| | JOINTS NOT LESS THAN 12 INCHES (305 MM) NOR MORE THAN |
| | 18 INCHES (457 MM) O.C.; THESE ANCHORS SHALL BE SECURED |
| | TO 1/4-INCH (6.4 MM) CORROSION-RESISTANT PENCIL RODS |
| | THAT PASS THROUGH THE VERTICAL ALIGNED LOOP ANCHORS IN |
| | THE BACKING WALL. THE VENEER TIES SHALL HAVE SUFFICIENT |
| | STRENGTH TO SUPPORT THE FULL WEIGHT OF THE VENEER IN |
| | TENSION. THE FACING SHALL BE SET WITH NOT LESS THAN A |
| | 2-INCH (51 MM) SPACE FROM THE BACKING WALL AND THE |
| | SPACE SHALL BE FILLED SOLIDLY WITH PORTLAND CEMENT |
| | GROUT AND PEA GRAVEL. IMMEDIATELY PRIOR TO SETTING, THE |
| | BACKING WALL AND THE FACING SHALL BE DRENCHED WITH |
| | CLEAN WATER AND SHALL BE DISTINCTLY DAMP WHEN THE GROUT |
| | IS POURED. |
| | |
| | 18) 2ND REQUEST. SHEET 395-S5-33 HAS A CONCEPTUAL |
| | DRAWING INDICATING THE TYPE OF TUBE STEEL HSS20X12X |
| | ?(LSH) THERE ARE NO DIMENSION FOR ANY OF THE ELEMENTS, |
| | ANGLE BETWEEN FRAMING MEMBERS, WELDS, TYPE OF |
| | ATTACHMENT TO DECKS BOTH TOP AND BOTTOM. 197.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 1ST REVIEW. SHEETS 160-A4.15 PODIUM METAL FIN, |
| | 161-A4.16 PODIUM METAL FIN, THE DETAIL # 2 ON SHEET 160 |
| | INDICATES A HSS TUBE POST, REFER TO STRUCTURAL SHEETS. |
| | THE STRUCTURAL SHEETS DO NOT PROVIDE DETAILS OF THIS |
| | STRUCTURAL TUBE. SHEET 395-S5-33 HAS A CONCEPTUAL |
| | DRAWING INDICATING THE TYPE OF TUBE STEEL HSS20X12X |
| | ?(LSH) THERE ARE NO DIMENSION FOR ANY OF THE ELEMENTS, |
| | ANGLE BETWEEN FRAMING MEMBERS, WELDS, TYPE OF |
| | ATTACHMENT TO DECKS BOTH TOP AND BOTTOM. 197.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 19) SHEET 162-A4-31 ROOF DETAILS: |
| | 19A) DETAILS 1 & 2 SHOW THE USE OF POLYISOCYANURATE |
| | BOARD. WITH SINGLE PLY RECOVERY BOARD AND SINGLE PLY |
| | PVC ROOFING MEMBRANE ROOFING. PLEASE PROVIDE THE |
| | PRODUCT APPROVALS FOR EACH OF THE MEMBERS. FOR ALL |
| | ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING |
| | SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF |
| | ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF |
| | ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| | FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| | INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE |
| | WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION |
| | PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT. |
| | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 19B) DEFERRED SUBMITTALS. DETAILS 3 & 4 BOTH SHOW A |
| | TILE DECK ABOVE THE ROOFING SYSTEM. THE ROOFING SYSTEM |
| | WELL NEED TO PROVIDE PRODUCT APPROVALS FOR WIND AS WELL |
| | AS ENGINEERING FOR THE TILE DECK INSTALLATION THEY WILL |
| | MEET THE WIND LOADS FOR THE LOCATION ON THE |
| | BUILDING.2010 FBC-B COMPONENTS AND CLADDING. |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | |
| | 20) BUILDING PROVISO: SHEETS 164-A4-41 AND 165-A4-41A |
| | S2.02 PROVIDE A BASIC DESIGN FOR THE CANOPY SYSTEMS. |
| | ADDITIONAL ENGINEERING SHEETS (SHOP DRAWINGS) TO BE |
| | SUBMITTED AS A DEFERRED SUBMITTAL. PLEASE ALSO PROVIDE |
| | HOW CODE COMPLIANCE WITH 2010 FBC-B 2405.2 ALLOWABLE |
| | GLAZING MATERIALS AND LIMITATIONS WILL BE COMPLIED |
| | WITH. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 21) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. ROOF HATCHES. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, INTAKE AND |
| | EXHAUST FANS ? |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 22) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |