2016-08-29 17:12:53BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR.
 CONT: SUFFOLK CONSTRUCTION CO.
 TEL: 561-832-1616
 E-MAIL: [email protected] / ED HANRATTY
  
 2010 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: SAT.- AUG. 26- /2016
 ACTION: DENIED
  
 NOTE: THIS REVIEW IS GOING TO BE COMPLETED AS A MIXED
 USE BUILDING,(FEMA REGULATIONS) AND THE REQUIREMENTS AS
 SUCH. 2010 FBC-B 1612.4 DESIGN & CONSTRUCTION SHALL BE
 IN ACCORDANCE WITH ASCE 24-05.
 ASCE 24-05 TABLE 6-1 MINIMUM ELEVATION OF
 FLOODPROOFING, RELATIVE TO THE BASE FLOOD (BFE) OR
 DESIGN FLOOD ELEVATION (DFE)- OUTSIDE OF HIGH RISK
 FLOOD HAZARD AREAS. STRUCTURE CATEGORY- II (FOOTNOTE)
 C. (C) DRY FLOODPROOFING OF RESIDENTIAL BUILDINGS AND
 RESIDENTIAL PORTIONS OF MIXED USE BUILDINGS SHALL NOT
 BE PERMITTED.
  
 1) SHEET 078-A2-0P2 PARKING 2 (LOWER LEVEL):
  
 1A) COMPLIED2010 FBC-B 1612.4 DESIGN & CONSTRUCTION
 SHALL BE IN ACCORDANCE WITH ASCE 24-05. ASCE 24-05
 TABLE 6-1. (FOOTNOTE) C. ( C ) DRY FLOODPROOFING OF
 RESIDENTIAL BUILDINGS AND RESIDENTIAL PORTIONS OF MIXED
 USE BUILDINGS SHALL NOT BE PERMITTED.
  
 1B)2ND REQUEST. THE RESPONSE LETTER INDICATES THE
 ELEVATOR IS A TRACTION ELEVATOR AS IDENTIFIED. THERE IS
 NO REFERENCE TO THE ELEVATOR BEING A TRACTION ELEVATOR
 OR A REVISION NUMBER AND BEING CLOUDED, BUBBLED OR A
 DELTA.
 ELEVATOR # 9 IS NOT IDENTIFIED ON SHEET 012-LS-P1/ P2.
 SHEET 176-A5.15 DOES NOT INDICATE IF THIS ELEVATOR IS A
 HYDRAULIC ELEVATOR? PLEASE IF THE ELEVATOR IS HYDRAULIC
 SHOW COMPLIANCE WITH 2010 FBC-B 3011. (1-4). IF THIS
 ELEVATOR IS HYDRAULIC IN WILL THE SUMP PUMP BE TIED
 INTO THE EMERGENCY ELECTRICAL PANEL TO KEEP DAMAGE TO
 THE HYDRAULIC SYSTEM AND CAB A MINIMUM. FEMA BULLETIN
 4-93.
  
 1C) 2ND REQUEST. THE RESPONSE LETTER INDICATES THE
 ELEVATOR IS A TRACTION ELEVATOR, WHICH IS MACHINE
 ROOMLESS ELEVATOR AS IDENTIFIED. THERE IS NO REFERENCE
 TO THE ELEVATOR BEING A TRACTION ELEVATOR OR A REVISION
 NUMBER AND BEING CLOUDED, BUBBLED OR A DELTA.
 ELEVATOR # 9 PLEASE IDENTIFY WHERE THE MACHINE ROOM FOR
 ELEVATOR # 9 IS LOCATED? PLEASE SHOW COMPLIANCE WITH
 2010 FBC-B 3006.4. 1 HOUR FIRE RATING.
  
 1D) 2ND REQUEST. THE RESPONSE INDICATES THE ELEVATOR TO
 BE A OTIS GEN 2 AND INCLUDES FLOAT SWITCH AND SOFTWARE,
 IT WOULD APPEAR THERE WOULD BE PRODUCT LITERATURE
 SUBMITTED, RESEARCHED THE EQUIPMENT SPEC SHEETS 33
 SHEETS NOT INCLUDED IN THIS FILE.
 THE OTHER ISSUE WITH ALL OF THE OTHER ELEVATORS THAT
 TRAVEL TO THE LOWER P2 PARKING LEVEL DEALS WITH THE
 FEMA TECHNICAL BULLETIN 4-93. FEMA REGULATION
 60.3(A)(3) IF A PROPOSED BUILDING SITE WILL BE
 REASONABLY SAFE FROM FLOODING. IF A PROPOSED BUILDING
 SITE IS IN A FLOOD PRONE AREA, ALL NEW CONSTRUCTION AND
 SUBSTANTIAL IMPROVEMENTS SHALL? BE CONSTRUCTED WITH
 MATERIALS RESISTANT TO FLOOD DAMAGE,(III) BE
 CONSTRUCTED BY METHODS AND PRACTICES THAT MINIMIZE
 FLOOD DAMAGES, AND (IV) BE CONSTRUCTED WITH
 ELECTRICAL... EQUIPMENT AND OTHER SERVICES FACILITIES
 THAT ARE DESIGNED AND / OR LOCATED SO AS TO PREVENT
 WATER DAMAGE FROM ENTERING OR ACCUMULATING WITHIN THE
 COMPONENTS DURING CONDITIONS OF FLOODING.
 TO KEEP THE ELEVATOR CABS FROM HAVING SUBSTANTIAL
 DAMAGE FROM FLOODWATERS, IS THERE A INTERLOCKING
 CONTROL OR FLOAT SWITCH THAT WHEN ACTIVATED WILL KEEP
 THE CAB FROM DESCENDING INTO THE FLOODWATERS.
 THE OTHER QUESTION, IS NORMALLY WITH LOSS OF POWER THE
 ELEVATOR CABS DESCEND TO THE LOWEST LEVEL , WILL THE
 INTERLOCK AND OR FLOAT SWITCH ALLOW THE OVERRIDE?
 DURING TIMES OF FLOOD THIS WILL ENABLE ACCESSIBILITY TO
 THE LOWER PARKING GARAGE UNLESS THE OCCUPANT TRAVELS
 DOWN THE STAIRS.
  
 1E) COMPLIED. SMOKE DOORS. DOORS P202/ ELEV. LOBBY 1,
 DOOR P203/ ELEV. LOBBY 2, DOOR P205 ELEV. LOBBY 3/ DOOR
 P206/ ELEV. LOBBY #4. ,
  
 1F) COMPLIED. FBC-B 905.3. STANDPIPES IN STAIRWELLS.
  
 1G)SEMI-COMPLIED, SHEET 166-A5-01 IDENTIFIES VARIOUS
 WALLS WITH TAGS:
  
 1G)(1) WALL IDENTIFICATION TAGGED WALLS 70, 71, 73, 74
 & 75 ALL SHOW AN ANGLE IRON BRACING SYSTEM ATTACHED TO
 THE UNDERSIDE OF THE NEXT CONCRETE SLAB AND A NOTE
 INDICATING A CONTINUOUS FIRE RESISTIVE JOINT SYSTEM.
 UL LISTING U905 & U906 ARE THE LISTING FOR THE WALL
 ONLY. PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 714.2
 AN RATED ASSEMBLY FOR THE DISSIMILAR MATERIALS AT THE
 JOINT WALL /SLAB JOINT (FIRE ?RESISTANT JOINT SYSTEM).
  
 1ST ROUND COMMENT. THE BUILDING CORES CONTAINING
 STAIRWELLS 1 & 2 AND 3 & 4 DO NOT HAVE WALL
 IDENTIFICATION TAGS AS THE WALLS SURROUNDING THE
 PERIMETER OF THE BUILDING. SHEET 012-A0-31 THE LIFE
 SAFETY SHEET FOR THE PARKING GARAGES INDICATES FIRE
 RATED WALLS. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1H) SEMI-COMPLIED. THE RESPONSE INDICATES THE VOID
 SPACE BETWEEN THE INTERSTITIAL FLOOR OF THE FPL VAULT
 WILL BE FILLED WITH STRUCTURAL GEOFOAM. PLEASE PROVIDE
 TESTING IN COMPLIANCE WITH 2603.3 SURFACE BURNING
 CHARACTERISTICS. ASTM E84 OR UL 723.
  
 1ST ROUND OF COMMENTS. THE EAST WALL OF THE FPL VAULT
 DOES NOT INDICATE A WALL TAG. THE FLOOR ELEVATION IS
 INDICATED AT ELEVATION 6?-0? THIS WALL WILL STILL BE ON
 THIS LEVEL. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED, WALL NOT IDENTIFIED AS TO TYPE.
  
 NEW COMMENTS:
 1I) COMMON COMMENT TO ALL FLOORS THE DOOR SCHEDULES
 FOUND ON SHEETS 331_A8.11 & 332_A8.12 LABEL ALL FIRE
 RATED DOORS AS B OR C LABEL. PLEASE RATE THEM IN
 MINUTES AND HOURS AS FBC-B TABLE 715.5.
  
 2) SHEET 079-A2-0P1 (PARKING LEVEL 1 UPPER LEVEL):
  
 2A-D) COMPLIED
  
  
  
  
 2E) SEMI-COMPLIED. PLEASE BE AWARE THIS IS A EUROPEAN
 SYSTEM THAT PROBABLY DOES NOT HAVE AN UL LISTING, NOR
 WILL THE 50 HZ 3-PHASE HOOK UP TO THE US STANDARD 60 HZ
 ELECTRICAL SYSTEM.
 ELECTRICAL NOTE # 6 INDICATES THE NEED OF A CORNER PIT
 IN THE FLOOR. ADDITIONAL INFORMATION REQUIRED WHEREAS
 THE PIT LOCATION AND THE SIZE OF THE PIT. 107.2.1.3.
 1ST REVIEW COMMENT. THIS LEVEL SHOWS STACKED PARKING,
 PLEASE PROVIDE DETAILS FOR THIS TYPE OF LIFT. HOW THE
 LIFT WILL OPERATE, MANUFACTURERS SPEC, ANCHORAGE FOR
 LIFT, IS THERE A VALET THAT PUTS THE CARS ON THE LIFT,
 ETC. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 2F-G) COMPLIED
  
 3) SHEET 013-A)-32 & 080-A2-01 LEVEL 1 (LOBBY):
  
 3A-D) COMPLIED.
  
 3E) SEMI-COMPLIED. ON THE LOBBY LEVEL THE DOORS TO THE
 GUEST SUITES LABELED GS01 ARE NOT FOUND IN THE DOOR
 SCHEDULE PAGE 331_A8-11.
  
 1ST ROUND COMMENT. PLEASE BE AWARE THAT THE DOORS ARE
 NOT IDENTIFIED ON THIS SHEET, NOR ARE THEY IDENTIFIED
 ON SHEET 166-A5-01. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3F)SEMI-COMPLIED. SHEET 098_A2-51A GUEST SUITE 1 COMMON
 WALL BATHROOM TO ATRIUM IS LABELED A WALL TYPE 3A. THIS
 WALL IS A 1 HOUR WALL AND HAS A STC RATING OF 47.
 PLEASE SEE FBC-B 1207.2 AIR-BORNE SOUND MINIMUM STC OF
 50, ASTM E90.
 1ST ROUND COMMENTS. PLEASE BE AWARE THAT THE WALL
 IDENTIFICATION TAGS ON THIS SHEET ARE MISSING AS WELL
 AS ON SHEET 166-A5-01. 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 3G)2ND REQUEST. PLEASE NOTE IS FOR ALL FLOORS WITH
 ELEVATOR DOOR OPENINGS. THE PLANS DO NOT INDICATE A
 FIRE RATED DOOR ON THE ELEVATOR SHAFT. FBC-B 3002.1.1
 OPENING PROTECTIVES OPENINGS IN HOISTWAY ENCLOSURES
 SHALL BE PROTECTED AS REQUIRED IN CHAPTER 7. OPENING
 PROTECTIVES TABLE 715.5.EXCEPTION THE FLOOR LEVEL
 DESIGNATED FOR RECALL SHALL REMAIN OPEN DURING PHASE I
 EMERGENCY RECALL OPERATION. WHAT FLOOR LEVEL WILL BE
 THE LEVEL DESIGNATED FOR RECALL?
 1ST ROUND OF COMMENTS. GUEST ROOM CORRIDOR 102 SHOWS
 THE WALLS TO BE A MINIMUM OF A 1 HOUR FIRE RATING WITH
 THE EXCEPTION OF THE ELEVATOR OPENING? PLEASE PROVIDE
 COMPLIANCE WITH 2010 FBC-B TABLE 1018.1.
  
 3H-K) COMPLIED..
  
 3L) 2ND REQUEST. THE 1ST LEVEL SHEET 080-A2-01/
 013-A)-32 LIFE SAFETY AND 2ND LEVEL SHEET 081-A2-02/
 014-A0-33 LIFE SAFETY 2ND LEVEL. THESE SHEETS DEPICT A
 2 STORY ATRIUM. I?M NOT SPEAKING OF THE STAIRWAY TO
 BELOW. THE LOBBY FLOOR SHEET 080_A2.01 AND THE SHEET
 081_A2.02 LEVEL 2 OF AMENITIES CONSTITUTES AN ATRIUM,
 WHERE THE AIR COMMUNICATES BETWEEN 2 STORIES. THESE
 WALLS IN COMMON SHOULD BE FIRE RATED FBC-B 404.6 WITH
 OPENING PROTECTIVES IN ACCORDANCE WITH TABLE 715.5.
  
 1ST ROUND OF COMMENTS. THE 1ST LEVEL SHEET 080-A2-01/
 013-A)-32 LIFE SAFETY AND 2ND LEVEL SHEET 081-A2-02/
 014-A0-33 LIFE SAFETY 2ND LEVEL. THESE SHEETS DEPICT A
 2 STORY ATRIUM. WHAT THE LIFE SAFETY SHEETS FAIL TO
 PROVIDE IS THE 1 HOUR FIRE BARRIER (2010 FBC-B 404.6)
 CONSTRUCTED IN ACCORDANCE WITH SECTION 707. THE PLANS
 DO NOT SHOW A CUT SECTION WHERE ONE OF THE EXCEPTIONS
 WAS TAKEN. ONE HOUR FIRE RATED WALLS WOULD BE REQUIRED
 WITH ANY SPACE THAT COMMUNICATED WITH THE ATRIUM AND
 OPENING PROTECTIVE IN COMPLIANCE WITH 2010 FBC-B TABLE
 715.4. SMOKE CONTROL IS NOT REQUIRED SINCE THIS IS A 2
 STORY ATRIUM.
  
 3M-O) COMPLIED. 2010 FBC-B 404.8 INTERIOR FINISHES.
  
 3O)(6) SEMI-COMPLIED. SHEET 184A-A5-52, THE DESIGNER OF
 RECORD HAS PROVIDED THE CHART SHOWING THE EXIT STAIR &
 RESIDENTIAL UNIT DISTRIBUTION TABLE. THE QUESTION STILL
 IS HOW WILL THE FIRE FIGHTERS KNOW THIS CHART EXIST,
 WILL A COPY OF THIS CHART BE POSTED IN THE FIRE COMMAND
 ROOM OR IN AN OVERALL FIRE MANUAL?
  
 1ST ROUND OF COMMENTS. A CUT SECTION THROUGH THE
 BUILDING SHOWING WHICH STAIRWELLS SERVICE WHICH SUITES
 SINCE THE FLOORS WITH 3 SUITES USE STAIRWELLS 2 & 3 SO
 FIRE FIGHTERS WILL KNOW WHICH STAIRWELLS AND FIREMENS
 ELEVATORS TO USE FOR FIREFIGHTING AND OR EMERGENCIES.
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 3P-R) COMPLIED. 2010 FBC-B SECTION 403.3.2 WATER SUPPLY
 TO REQUIRED FIRE PUMPS
  
 3S) BUILDING PROVISO: THE PLANS SHOW AT THE ENTRY LEVEL
 OF THE LOBBY A RECEPTION/ REGISTRATION DESK. PLEASE
 PROVIDE COMPLIANCE WITH FAIR HOUSING SPECIFICATION OF
 ANSI 4.31 ALSO SEE REACH RANGES.
  
 3T) 2ND REQUEST. THIS COMMENT WILL STAND FOR ALL FLOORS
 WITH MULTIPLE R2 DWELLING UNITS ON THE SAME FLOOR OR
 DWELLING UNITS ABOVE OR BELOW THE OCCUPIED UNIT. PLEASE
 NOTE ALL 3 TEST ARE REQUIRED FOR ANY FLOOR
 UNDERLAYMENT. IF THERE IS TO BE TILE AND OR MARBLE THE
 UNDERLAYMENT HAS TO BEEN TESTED ALL 3 TEST, THIS HOLDS
 TRUE FOR WOOD VENEERS AS WELL. PLEASE KEEP THE 3 TEST
 CRITERIA TOGETHER, IF THEY ARE POSTED ON THE SAME PLANS
 SHEET, WE CAN THEN LET THE ACTUAL TEST APPROVALS TO BE
 A DEFERRED SUBMITTAL AFTER THE ISSUANCE OF THE PERMIT.
 WE NEED THE CONTRACTOR OR SUB-CONTRACTORS OR VENDORS TO
 SEE THERE ARE 3 DIFFERENT CRITERIA IN THE SELECTING
 FLOOR UNDER-LAYMENTS. THANK YOU FOR YOUR HELP IN THIS
 MATTER.
  
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 3T)(1) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3T)(2) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3T)(3) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3U) COMPLIED.
  
  
 4) SHEET 014-A0-33/ 082-A2-03: 2ND LEVEL GUEST SUITES.
  
 4A) COMPLIED. GUEST SUITES ARE PURCHASED BY THE CURRENT
 OWNERS TO BE USED AS A ALTERNATE SLEEPING ROOM.
 4B)2ND REQUEST. THE SHAFT WALLS HAVE NOW BEEN
 IDENTIFIED AS WALL IDENTIFICATION TAGS, 1 & 52. PLEASE
 NOTE THESE WALLS ARE COMMON WITHIN THE TENANT SPACE AND
 ONLY HAVE A STC RATING OF 47 NOT THE REQUIRED 50.
 FBC-B 2010 SECTION 1207.2 AIR-BORNE SOUND.
  
 1ST ROUND OF COMMENTS. THERE IS A DISCREPANCY IN PLANS
 IT WOULD APPEAR. SHEET 014-A0-33 LEVEL 2 GUEST SUITES
 IT APPEARS THE MECHANICAL UNIT HP-1IN GUEST SUITES 11 &
 12 ARE LOCATED IN A ONE HOUR SHAFT WHEREAS THE UNITS 9
 & 10 THE UNITS ARE NOT LOCATED IN A RATED WALL. IT
 APPEARS IN UNITS 11 & 12 THERE IS A VERTICAL 8X16 INCH
 EXHAUST DUCT NOT SHOWN IN A SHAFT, MECHANICAL SHEETS
 INDICATE THAT IN SOME AREA 2 HOUR FLAME BAR IS TO BE
 INSTALLED. PLEASE PROVIDE DETAILED INFORMATION IN
 RESPONSE AS TO WHAT AREAS ARE TO BE SHAFTS, HOUR RATING
 OF SHAFTS, WHERE THE FLAME BAR IS TO BE INSTALLED AND
 FIRE STOPPING ASSEMBLIES FOR THROUGH PENETRATIONS. THIS
 COMMENT WILL BE COMMON FOR THE 3 FLOORS OF GUEST
 SUITES. 2010 FBC-B 708.2.4 /716.6 HORIZONTAL
 ASSEMBLIES. THIS CONDITION APPEARS ON THE 3RD LEVEL OF
 GUEST SUITES AS WELL.
  
 4C-D) COMPLIED
 .
  
 5) SHEET 014-A)-33/ 098-A2-51A2: 2ND LEVEL AMENITIES/
 103-A2.53A THE 3RD LEVEL GUEST SUITES.
  
 5A-B) COMPLIED.
  
 5C)2ND REQUEST. SHEET 098_A2-51A2 &/ 103-A2.53A THE 3RD
 LEVEL GUEST SUITES IS MISSING BOTH THE WALL & DOOR
 IDENTIFICATION TAGS. CODE COMPLIANCE CANNOT BE
 DETERMINED. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 5D) 2ND REQUEST. SHEET 014-A)-33 IS THE 2ND LEVEL OF
 THE ATRIUM. THIS SHEETS DEPICTS THE 2ND FLOOR OF THE
 ATRIUM. WHAT THE LIFE SAFETY SHEETS FAIL TO PROVIDE IS
 THE 1 HOUR FIRE BARRIER (2010 FBC-B 404.6) CONSTRUCTED
 IN ACCORDANCE WITH SECTION 707. THE PLANS DO NOT SHOW A
 CUT SECTION WHERE ONE OF THE EXCEPTIONS WAS TAKEN. ONE
 HOUR FIRE RATED WALLS WOULD BE REQUIRED WITH ANY SPACE
 THAT COMMUNICATED WITH THE ATRIUM AND OPENING
 PROTECTIVE IN COMPLIANCE WITH 2010 FBC-B TABLE 715.4.
 SMOKE CONTROL IS NOT REQUIRED SINCE THIS IS A 2 STORY
 ATRIUM. PLEASE NOTE THE 3 LEVELS OF THE R2 GUEST ROOMS
 TRAVEL THROUGH A 1 HOUR FIRE RATED ACCESS CORRIDOR INTO
 THE ATRIUM.
  
 5E) COMPLIED
  
 5F) 2ND REQUEST. THIS SHEET INDICATES THE BRIDGE
 SECTION OF THE 2ND LEVEL IS INDICATED AS A MEZZANINE
 LOBBY. THE 2ND FLOOR AREA THAT IS OPEN AND COMMUNICATES
 IS OVER THE 1/3RD OF THE OPEN AREAS ALLOWED BY FBC-B
 505.2 EXCEPTION # 2 FOR TYPE I TYPE II BUILDINGS. THIS
 IS A TRUE 2 STORY ATRIUM, FBC-B 404.6 ENCLOSURES OF
 ATRIUMS.
  
 5G)2ND REQUEST. SHEET 014-A0-33 POOL DECK STAIR # 6 & 7
 SHOW THE USE OF AN AREA OF RESCUE ASSISTANCE.
 THE RESPONSE INDICATES TWO-WAY COMMUNICATION SYSTEM HAS
 BEEN PROVIDED, SEE SHEET A0.33.
 PLEASE SHOW COMPLIANCE WITH ALL ASPECTS OF THE 2003 IBC
 1007.6.
  
 AREA OF REFUGE. 2003 IBC-B 1007.6 .3 TWO-WAY
 COMMUNICATION. AREAS OF REFUGE SHALL BE PROVIDED WITH
 TWO-WAY COMMUNICATION SYSTEM BETWEEN THE AREA OF REFUGE
 AND A CONTROL POINT. IF THE CENTRAL CONTROL POINT IS
 NOT CONSTANTLY ATTENDED, THE AREA OF REFUGE SHALL ALSO
 HAVE CONTROLLED ACCESS TO A PUBLIC TELEPHONE SYSTEM.
 LOCATION OF THE CENTRAL CONTROL POINT SHALL BE APPROVED
 BY THE FIRE DEPARTMENT. TWO-WAY COMMUNICATION SYSTEM
 SHALL INCLUDE BOTH AUDIBLE AND VISIBLE SIGNALS.
  
 1007.6.4 INSTRUCTIONS. IN AREAS OF REFUGE THAT HAVE A
 TWO-WAY EMERGENCY COMMUNICATIONS SYSTEM, INSTRUCTIONS
 ON THE USE OF THE AREA UNDER EMERGENCY CONDITIONS SHALL
 BE POSTED ADJOINING THE COMMUNICATIONS SYSTEM. THE
 INSTRUCTIONS SHALL INCLUDE ALL OF THE FOLLOWING;
 1) DIRECTIONS TO FIND OTHER MEANS OF EGRESS.
 2) PERSONS ABLE TO USE THE EXIT STAIRWAY DO SO AS SOON
 AS POSSIBLE, UNLESS THEY ARE ASSISTING OTHERS.
 3) INFORMATION ON THE PLANNED AVAILABILITY OF
 ASSISTANCE IN THE USE OF STAIRS OR SUPERVISED OPERATION
 OF ELEVATORS AND HOW TO SUMMON SUCH ASSISTANCE. 4)
 DIRECTIONS FOR THE USE OF THE EMERGENCY COMMUNICATIONS
 SYSTEM.
  
 1007.6.5 IDENTIFICATION. EACH DOOR PROVIDING ACCESS TO
 AN AREA OF REFUGE FROM AN ADJACENT FLOOR AREA SHALL BE
 IDENTIFIED BY A SIGN COMPLYING WITH ICC A117., STATING
 AREA OF REFUGE, AND INCLUDING THE INTERNATIONAL SYMBOL
 OF ACCESSIBILITY. WHERE EXIT SIGN ILLUMINATION IS
 REQUIRED BY SECTION 1011.2, THE AREA OF REFUGE SIGN
 SHALL BE ILLUMINATED. ADDITIONALLY, TACTILE SIGNAGE
 COMPLYING WITH ICC A117.1 SHALL BE LOCATED AT EACH DOOR
 TO AN AREA OF REFUGE.
  
 1007.7. SIGNAGE. AT EXITS AND ELEVATORS SERVING A
 REQUIRED ACCESSIBLE SPACE BUT NOT PROVIDING AN APPROVED
 ACCESSIBLE MEANS OF EGRESS, SIGNAGE SHALL BE INSTALLED
 INDICATING THE LOCATION OF ACCESSIBLE MEANS OF EGRESS
  
 1ST ROUND COMMENT. SHEET 014-A0-33 POOL DECK STAIR # 6
 & 7 SHOW THE USE OF AN AREA OF RESCUE
 ASSISTANCE. THE 2010 FBC-B 1007.1 ACCESSIBLE MEANS OF
 EGRESS. ACCESSIBLE MEANS OF EGRESS SHALL BE PROVIDED IN
 ACCORDANCE WITH THE APPLICABLE SECTIONS OF THE FLORIDA
 BUILDING CODE, ACCESSIBILITY.
 2010 FBC-ACCESSIBILITY CODE. ACCESSIBLE MEANS OF EGRESS
 . 207.1 GENERAL. MEANS OF EGRESS SHALL COMPLY WITH
 SECTION 1003.2.13 OF THE INTERNATIONAL BUILDING CODE
 (2000 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF
 THE INTERNATIONAL BUILDING CODE (2003 EDITION)
 (INCORPORATED BY REFERENCE, SEE "REFERENCED STANDARDS"
 IN CHAPTER 1).
 PLEASE SHOW FULL COMPLIANCE FOR THE AREA OF REFUGE
 ASSISTANCE, 2003 IBC-B REQUIREMENTS 1007.6.(1-7) &
 1007.8(1-3).
  
  
 START REVIEWS MON. 8/29/16
  
  
 5H) COMPLIED. FAIR HOUSING. THE DINING ROOM, BEAUTY
 PARLOR AND GUEST ROOMS ARE UNDER FAIR HOUSING ACT. FAIR
 HOUSING IS TO BE APPLIED THEN ONLY ACCESS TO THE POOL
 DECK WILL BE REQUIRED.
  
 5I) COMPLIED. FAIR HOUSING. AN ACCESSIBLE ROUTE TO THE
 LOWER POOL DECK AREA. FAIR HOSING ANSI A117.1 4.3 (C)
 CONNECTING ACCESSIBLE BUILDING OR FACILITY ENTRANCES
 WITH ACCESSIBLE SPACES AND ELEMENTS WITHIN THE BUILDING
 OR FACILITY, INCLUDING ADAPTABLE DWELLING UNITS.
  
 5J) COMPLIED. FAIR HOUSING COMPLIANCE FOR THE STEAM
 ROOMS AND SAUNAS. FAIR HOUSING COMMON USE SPACES AND
 FACILITIES. WHEN ANSI DOES NOT CONTAIN SPECIFICATIONS
 FOR SPECIFIC FACILITIES OR FEATURE IN QUESTION RELATED
 HUMAN FACTORS AND PERFORMANCE SPECIFICATIONS MUST BE
 USED TO ACHIEVE ACCESSIBILITY. SUCH SPECIFICATIONS
 INCLUDE, BUT ARE NOT LIMITED TO, 4.2 SPACE ALLOWANCES
 AND REACH RANGES, 4.3 ACCESSIBLE ROUTE, 4.4 PROTRUDING
 OBJECTS, 4.5 GROUND & FLOOR SURFACES, AND 4.25
 OPERATING MECHANISMS.
  
 5K) 2ND REQUEST, SEMI-COMPLIED, THE RESPONSE INDICATES
 HOW COMPLIANCE CAN BE OBTAINED. COMPLIANCE WITH COMMENT
 5G MUST BE MET FOR COMMENT TO BE COMPLIED WITH.
 1ST ROUND COMMENT. SHEET 014-A0-33 THE LOWER POOL DECK
 IT APPEARS THERE IS ONLY ONE RAMP (NOT MARKED, NOR
 ELEVATION CHANGES GIVEN) BETWEEN THE POOL DECK AND POOL
 THERE ARE 116 OCCUPANTS AND WHAT APPEARS TO BE ONLY ONE
 ACCESSIBLE MEANS OF EGRESS. PLEASE SHOW COMPLIANCE
 WITH: 2010 FBC-BUILDING CODE 1007.1 ACCESSIBLE MEANS OF
 EGRESS. ACCESSIBLE MEANS OF EGRESS SHALL BE PROVIDED IN
 ACCORDANCE WITH THE APPLICABLE SECTIONS OF THE FLORIDA
 BUILDING CODE, ACCESSIBILITY.
 2010 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
  
  
 6) SHEETS 015-A0-34 LEVELS 5-10. 11-17 (TIER 1) LEVELS
 18-19 TIER 2. / 083-A2-05 LEVEL 5/ 084-A2-06 LEVELS
 6-9, 11 TIER 1;
 6A) 2ND REQUEST. THIS COMMENT IS A COMMON COMMENT FOR
 ALL DWELLING UNITS TIER 1 LEVELS 5-9 &11. THE LIFE
 SAFETY PLAN SHOWS (2) REQUIRED MEANS OF EGRESS PER UNIT
 OVER 3 STORIES, COMMON PATH OF TRAVEL EXCEEDED WITH ONE
 MEANS OF EGRESS, BECAUSE THEY ARE OVER THE 125 FEET
 REQUIRED BY 2010 FBC-B 1014.3 EXCEPTION # 4.
  
 6A)(1) COMPLIED. THE PLANS SHOW THE 1ST COMMON PATH OF
 TRAVEL EXITING THROUGH THE FRONT ENTRY DOORS THROUGH AN
 ELEVATOR LOBBY, THE LIFE SAFETY PLANS WILL NEED TO
 INDICATE IF THE ELEVATOR HOIST WAYS ARE PRESSURIZED TO
 ALLOW EXITING THROUGH THE ELEVATOR LOBBY. 2010 FBC-B
 708.14.1 ELEVATOR LOBBIES.
  
 6A)(2) 2ND REQUEST. THE RESPONSE INDICATES A ISSUE WITH
 LOCKABLE DOORS ONLY NOT THE CODE SECTION OF NO EGRESS
 THROUGH STORAGE ROOMS, CLOSETS OR SPACES USED FOR
 SIMILAR PURPOSES.
  
 1ST ROUND COMMENTS. THE 2ND ISSUE IS THE COMMON PATH OF
 TRAVEL THROUGH THE LAUNDRY/ STORAGE/ UTILITY ROOM.
 PLEASE SEE THE 2010 FBC-B SECTION 1014.2.1(4) 4. EGRESS
 SHALL NOT PASS THROUGH KITCHENS, STORAGE ROOMS, CLOSETS
 OR SPACES USED FOR SIMILAR PURPOSES. NOTE THE EXCEPTION
 IS ONLY FOR A KITCHEN AREA SERVING ADJOINING ROOMS
 CONSTITUTING PART OF THE SAME DWELLING UNIT OR SLEEPING
 UNIT.
  
 6B) COMPLIED. COMMON COMMENT FOR ALL FLOORS. EXITING
 CAPACITY ANALYSIS FOR ALL TIERS SHOW A 36 INCH DOORWAY
 AND THE EXIT CAPACITY AT 180 OCCUPANTS. THIS WOULD MEAN
 YOU HAVE OFFSET HINGES ON THE EXIT DOORS SO THERE IS A
 FULL 36 INCHES CLEAR WIDTH FROM THE FACE OF THE DOOR
 WHEN OPEN AT 90 DEGREES TO THE OPPOSING LATCH SIDE OF
 THE DOOR AND NOT INCLUDING THE DOOR STOP. SEE 2010
 FBC-B 1008.1.1. CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
 THE ACTUAL ALLOWABLE MAXIMUM OCCUPANT LOAD IS CLOSER TO
 167.
  
 7) 2ND REQUEST. SHEET 016-A0-35 LEVELS 20 & 21 /
 090-A2-20 LEVEL 20 REFERS TO SHEET 089- A2.18 FOR UNITS
 A & B. SHEET 090-A2-20 FOR UNIT C. SAME COMMENTS AND
 ISSUES AS COMMENTS 6A AND 6B.
  
 8)2ND REQUEST. SHEET 017-A0-36 LIFE SAFETY PLANS FOR
 LEVEL 22 & 23/ 092-A2-22 & 093-A2-23. SAME COMMENTS AND
 ISSUES AS COMMENTS 6A AND 6B.
  
 9) PROVISO: SHEET 017-A0-36 LIFE SAFETY PLANS FOR LEVEL
 23/ SHEET 093-A2-23. AT OWN RISK!!!!!
 THE COMMON PATH OF TRAVEL THROUGH THE LAUNDRY/ STORAGE/
 UTILITY ROOM. PLEASE SEE THE 2010 FBC-B SECTION
 1014.2.1(4) 4. EGRESS SHALL NOT PASS THROUGH KITCHENS,
 STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR
 PURPOSES. NOTE THE EXCEPTION IS ONLY FOR A KITCHEN AREA
 SERVING ADJOINING ROOMS CONSTITUTING PART OF THE SAME
 DWELLING UNIT OR SLEEPING UNIT.
  
 10) SHEET 018-A0-37 LEVELS 24 &25/ SHEET 094-A2-24
 LEVEL 24 & 095-A2-25.
  
 10A)2ND REQUEST. UNIT PH-24N & PH25N HAS THE SAME
 ISSUES AS COMMENT 6A)(1) ELEVATOR LOBBY & 6A)(2) EGRESS
 THROUGH STORAGE/ UTILITY CLOSET / LAUNDRY ROOM. THE
 2010 FBC-B SECTION 1014.2.1(4) 4. EGRESS SHALL NOT PASS
 THROUGH KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED
 FOR SIMILAR PURPOSES.
  
 10B) COMPLIED 2010 FBC-B 708.14.1 ELEVATOR SHAFTS ARE
 PRESSURIZED.
  
 11) SHEET 019-A)-38 LEVEL 26 MECHANICAL FLOOR - ROOF /
 096-A2-26 ARCH. MECHANICAL FLOOR
 PLAN. A122-A2-76ALEVEL 26 NORTH, 411-M2-26 & 374.S2-26
 STRUCTURAL MECHANICAL ROOF FRAMING PLAN.
  
  
  
 11A) NEW COMMENT.. SHEET 122-A2-76A ONE WALL THAT
 ENCLOSES STAIR # 2 IS IDENTIFIED WITH A WALL TAG # 78
 THIS WALL DESIGNATION IS NOT FOUND ON SHEET 330-A8-02.
 1ST ROUND OF COMMENTS. SHEET 122-A2-76A NONE OF THE
 ARCHITECTURAL NOR STRUCTURAL SHEETS, PROVIDE A ROOM &
 WALL IDENTIFICATION TAG FOR THE WALL IN THE UPPER RIGHT
 CORNER OF THE BUILDING, THE SAME WALL IS ALSO COMMON TO
 STAIR TOWER #2 AND FIREMANS VESTIBULE 2601. ADDITIONAL
 INFORMATION IS REQUIRED BOTH THE FIREMANS VESTIBULE
 (1HR.) AND THE STAIR SHAFT(2 HR.) ARE FIRE RATED
 PROTECTED. 3007.4.2 & 708.4.
  
 11B-G) COMPLIED.
  
 11H)COMPLIED. SHEET 122-A2-76A LEVEL 26 PLEASE NOTE
 ROOFTOP AND FLOOR ELEVATION TAGS ARE PROVIDED.
  
 11I) 2ND REQUEST. SEMI-COMPLIED. RESPONSE INDICATES SEE
 SHEETS A2,56A AND A2.76B. SHEET A2-76B SHOWS THE DOORS
 WITH IDENTIFICATION TAGS BUR NOT THE WALLS. SHEET
 A2.56A IS THE FLOOR LEVELS 5-9, 11-17? DO YOU MEAN
 A2-26 NEITHER THE WALLS NOR DOORS ARE IDENTIFIED?
 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
 1ST ROUND OF COMMENTS. SHEET 171-A5-06 PLEASE NOTE NONE
 OF THE WALLS NOR DOORS ARE PROVIDED WITH IDENTIFICATION
 TAGS, PLANS ARE INCOMPLETE, 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 11J) COMPLIED. SHEET 171-A5-06 AND 096-A2-26 ELEVATOR
 CONTROL ROOM 3, 4 &6.
  
 11K-N) COMPLIED.
  
 11O) 2ND REQUEST. THE SHEET 123_A2-76B DOES HAVE A NOTE
 WHERE THE VERTICAL BRACING OCCURS IN THE EXTERIOR
 CORRIDOR 2604 OUTLINE OF SCREEN WALL & STEEL BRACING
 ABOVE. THE STRUCTURAL SHEETS 374_S2-26 DOES NOT
 INDICATE SUCH DETAILS. A DIFFERENT VERSION IS FOUND ON
 SHEET 375_S2-27 WHERE THE VERTICAL LEG AND BRACING
 STILL APPEAR TO BE IN THE CORRIDOR.
 1ST ROUND COMMENT. SHEET 096-A2-26 THE MECHANICAL
 EQUIPMENT SCREEN BRACING SYSTEM AS DRAWN HAS LEGS THAT
 GO INTO THE CORRIDOR 2604 BLOCKING ACCESS, BLOCKING
 ENTRY TO A EXTERIOR MECHANICAL ROOM 2603 AND ALSO TO
 ROOM 2606. PLEASE CORRECT THESE AREAS.
  
 12) SEMI- COMPLIED. SHEET 431-M4-01 MECHANICAL DETAILS,
 DETAIL 20 COOLING TOWER VIBRATION ISOLATOR.
 RESPONSE INDICATES SEE SHEET 395_A-S5-31 SEE DETAIL # 4
 FOR CONCRETE PIER FOR A/C ROOF TOP EQUIPMENT. PLEASE
 PROVIDE REQUIRED CLEARANCES BELOW RAISED ROOF MOUNTED
 MECHANICAL UNITS, SEE TABLE 1509.7
 FBC-B. TAKE THE MEASUREMENTS FROM THE LOWEST HORIZONTAL
 FRAMING MEMBER.
  
 1ST ROUND OF COMMENTS. SHEET 431-M4-01 MECHANICAL
 DETAILS, DETAIL 20 COOLING TOWER VIBRATION ISOLATOR
 DETAIL TO BE REVIEWED BY THE STRUCTURAL ENGINEER OF
 RECORD, AND WITH THEIR SHOP DRAWING STAMP OF APPROVAL.
 PLEASE NOTE THE STRUCTURAL BASE OR SUPPORT WILL NEED TO
 BE DESIGNED BY THE STRUCTURAL ENGINEER OR HIS DELEGATE
 WITH THE STRUCTURAL ENGINEERS APPROVAL BEFORE SUBMITTAL
 TO THE BUILDING DEPARTMENT FOR REVIEW.
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
  
 13) BUILDING PROVISO: DEFERRED SUBMITTALS: SHEET
 431-M4-01 MECHANICAL DETAILS EQUIPMENT SUPPORT CURB
 DETAIL & THYBAR VIBRATION CURB III DETAIL FOR OAU-1 &
 2. PLEASE PROVIDE THE PRODUCT APPROVALS FOR CURB
 DETAILS. TO BE REVIEWED BY THE STRUCTURAL ENGINEER OF
 RECORD, AND WITH THEIR SHOP DRAWING STAMP OF APPROVAL.
 PLEASE NOTE THE STRUCTURAL ANCHOR TO THE BASE OR
 SUPPORT AS WELL AS THE UNIT TO THE CURB FOR MOMENT OF
 OVERTURNING, WILL NEED TO BE DESIGNED BY THE STRUCTURAL
 ENGINEER OR HIS DELEGATE WITH THE STRUCTURAL ENGINEERS
 APPROVAL BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT
 FOR REVIEW.
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 14) SHEET 131-A3-21.
 14A) COMPLIED.
  
 14B) ELEVATORS 2/4 DO NOT CONTINUE THROUGH TO THE ROOF.
 PLEASE PROVIDE WHERE COMPLIANCE WITH SECTIONS OF THE
 2010 FBC-B CAN BE FOUND:
  
 14B)(1) 2ND REQUEST IDENTIFY THE SHAFT THAT GOES TO THE
 ROOF TOP. 3004.1 VENTS REQUIRED. HOISTWAYS OF ELEVATORS
 PENETRATING MORE THAN THREE STORIES SHALL BE PROVIDED
 WITH A MEANS FOR VENTING SMOKE AND HOT GASES TO THE
 OUTER AIR IN CASE OF FIRE. FOR R1 AND R2 OCCUPANCIES
 VENTING IS REQUIRED.
  
 14B)(2) 2ND REQUEST IDENTIFY THE SHAFT AND ROOF TOP
 VENT, SIZE OF THE AREA VENTING. 3004.2 LOCATION OF
 VENTS. VENTS SHALL BE LOCATED AT THE TOP THE HOISTWAY
 AND SHALL OPEN EITHER DIRECTLY TO THE OUTER AIR OR
 THROUGH NONCOMBUSTIBLE DUCTS TO THE OUTER AIR.
 NONCOMBUSTIBLE DUCTS SHALL BE PERMITTED TO PASS THROUGH
 THE ELEVATOR MACHINE ROOM, PROVIDED THAT PORTIONS OF
 THE DUCTS LOCATED OUTSIDE THE HOISTWAY OR MACHINE ROOM
 ARE ENCLOSED BY CONSTRUCTION HAVING NOT LESS THAN THE
 FIRE-RESISTANCE RATING REQUIRED FOR THE HOISTWAY. HOLES
 IN THE MACHINE ROOM FLOORS FOR THE PASSAGE OF ROPES,
 CABLES OR OTHER MOVING ELEVATOR EQUIPMENT SHALL BE
 LIMITED AS NOT TO PROVIDE GREATER THAN 2 INCHES (51 MM)
 OF CLEARANCE ON ALL SIDES.
  
 14)(3) 2ND REQUEST. 3004.3 AREA OF VENTS. EXCEPT AS
 PROVIDED FOR IN SECTION 3004.3.1, THE AREA OF THE VENTS
 SHALL NOT BE LESS THAN 31/2 PERCENT OF THE AREA OF THE
 HOISTWAY NOR LESS THAN 3 SQUARE FEET (0.28 M2) FOR EACH
 ELEVATOR CAR, AND NOT LESS THAN 31/2 PERCENT NOR LESS
 THAN 0.5 SQUARE FEET (0.047 M2) FOR EACH DUMBWAITER CAR
 IN THE HOISTWAY, WHICHEVER IS GREATER. OF THE TOTAL
 REQUIRED VENT AREA, NOT LESS THAN ONE-THIRD SHALL BE
 PERMANENTLY OPEN. CLOSED PORTIONS OF THE REQUIRED VENT
 AREA SHALL CONSIST OF OPENINGS GLAZED WITH ANNEALED
 GLASS NOT GREATER THAN 1/8 INCH (3.2 MM) IN THICKNESS.
  
  
 15) SHEET 137-A3-31 DETAILS 1 & 2 & SHEET A0.23
 EXTERIOR SYSTEMS.
  
 15A)2ND REQUEST. THE SHEET 137-A3-31 SHOWS VARIOUS
 AREAS WHERE METAL PANELS ARE GOING TO BE INSTALLED ON
 THE EXTERIOR OF THE BUILDING. TO DATE NO PLANS HAVE
 BEEN SUBMITTED FOR COMPLIANCE. THE RESPONSE STATES
 THESE PANELS ARE METAL PLATE PANELS AND POSSIBLY THE
 USE OF MCM PANELS. THE SYSTEM IS GOING TO HAVE TO BE
 BETTER DEFINED AS TO USAGE WEATHER ABILITY, MATERIALS
 AND ANCHORAGE FOR THE COMPONENT PORTION OF THE
 BUILDING.
 AT THE 26TH LEVEL THERE ARE METAL SKINNED ARCHES
 ARCHITECTURAL ELEMENTS AS WELL AS LEVEL 1 FIN , THAT
 NEED STRUCTURAL DETAILS THE PAGES REFERENCED S5.31 ARE
 FOR THE A/C CHILLER SCREEN AND FOR PILLARS FOR THE A/C
 CHILLER. IS THIS AN ELEMENT THAT YOU WOULD LIKE TO A
 DEFERRED SUBMITTAL.
  
 BOTH INDICATE THE USE OF METAL WALL PANELS, THERE ARE
 NO CUT SECTIONS INDICATING MORE INFORMATION ON THE
 PANELS. COMPONENTS AND CLADDING FBC-B, 1609.6.4.4.1
 COMPONENTS & CLADDING. PLEASE SEE THE 2010 FBC-B
 SECTION 1407.3 ARCHITECTURAL TRIM AND EMBELLISHMENTS.
 MCM USED AS ARCHITECTURAL TRIM OR EMBELLISHMENTS SHALL
 COMPLY WITH SECTIONS 1407.7 THROUGH 1407.14.
 1407.4 STRUCTURAL DESIGN. MCM SYSTEMS SHALL BE DESIGNED
 AND CONSTRUCTED TO RESIST WIND LOADS AS REQUIRED BY
 CHAPTER 16 FOR COMPONENTS AND CLADDING.
  
 1407.5 APPROVAL. RESULTS OF APPROVED TESTS OR AN
 ENGINEERING ANALYSIS SHALL BE SUBMITTED TO THE BUILDING
 OFFICIAL TO VERIFY COMPLIANCE WITH THE REQUIREMENTS OF
 CHAPTER 16 FOR WIND LOADS. 1407.6 WEATHER RESISTANCE.
  
 15B) COMPLIED. BALCONY DIVIDER GLASS TO HAVE A ARTIC
 SNOW PVB INNER CORE, FBC-B 2407
  
 15C) COMPLIED.
  
 16)2ND REQUEST. SHEETS 108-A2-68A & DETAIL # 2/
 278-A6-85C BALCONY DEMISING GLASS WALL. THE FLOOR PLAN
 108-A2-68A DOES SHOW THE USE OF BALCONY DEMISING GLASS
 WALL AS WELL AS THE ELEVATION SHEET 137-A3-31. THE
 DETAIL 2 ON SHEET 278-A6-85C APPEAR TO BE FOR INSULATED
 SPANDREL PANEL BUT NOT FOR THE GLASSED DEMISING WALL IT
 WOULD APPEAR THIS IS THE WRONG DETAIL.
  
 17) SHEET 157-A4-14 DETAIL 11 SHOWS THE INSTALLATION OF
 A TERRA COTTA RAIN SCREEN. REFERENCES DETAIL 11/
 157-A4-14 PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B
 SECTIONS:
  
 17A) 2ND REQUEST, PLEASE PROVIDE PRODUCT TESTING.
 1403.2 WEATHER PROTECTION.
  
 17B) 2ND REQUEST. RESPONSE INDICATES REFER TO
 STRUCTURAL LOADS REPORT. THE PLANS DO NOT PROVIDE
 ANCHORAGE, TYPE OF ANCHOR, AT WHAT SPACING AN NO
 PRODUCT DATA HAS BEEN SUBMITTED FOR THIS SYSTEM. 1403.3
 STRUCTURAL. EXTERIOR WALLS, AND THE ASSOCIATED
 OPENINGS, SHALL BE DESIGNED AND CONSTRUCTED TO RESIST
 SAFELY THE SUPERIMPOSED LOADS REQUIRED BY CHAPTER 16.
  
 17C) 2ND REQUEST. THE PLANS DO NOT PROVIDE ANCHORAGE,
 TYPE OF ANCHOR, AT WHAT SPACING AN NO PRODUCT DATA HAS
 BEEN SUBMITTED FOR THIS SYSTEM.
  
 1405.9 TERRA COTTA. ANCHORED TERRA COTTA OR CERAMIC
 UNITS NOT LESS THAN 15/8 INCHES (41 MM) THICK SHALL BE
 ANCHORED DIRECTLY TO MASONRY, CONCRETE OR STUD
 CONSTRUCTION. TIED TERRA COTTA OR CERAMIC VENEER UNITS
 SHALL BE NOT LESS THAN 15/8 INCHES (41 MM) THICK WITH
 PROJECTING DOVETAIL WEBS ON THE BACK SURFACE SPACED
 APPROXIMATELY 8 INCHES (203 MM) O.C. THE FACING SHALL
 BE TIED TO THE BACKING WALL WITH CORROSION-RESISTANT
 METAL ANCHORS OF NOT LESS THAN NO. 8 GAGE WIRE
 INSTALLED AT THE TOP OF EACH PIECE IN HORIZONTAL BED
 JOINTS NOT LESS THAN 12 INCHES (305 MM) NOR MORE THAN
 18 INCHES (457 MM) O.C.; THESE ANCHORS SHALL BE SECURED
 TO 1/4-INCH (6.4 MM) CORROSION-RESISTANT PENCIL RODS
 THAT PASS THROUGH THE VERTICAL ALIGNED LOOP ANCHORS IN
 THE BACKING WALL. THE VENEER TIES SHALL HAVE SUFFICIENT
 STRENGTH TO SUPPORT THE FULL WEIGHT OF THE VENEER IN
 TENSION. THE FACING SHALL BE SET WITH NOT LESS THAN A
 2-INCH (51 MM) SPACE FROM THE BACKING WALL AND THE
 SPACE SHALL BE FILLED SOLIDLY WITH PORTLAND CEMENT
 GROUT AND PEA GRAVEL. IMMEDIATELY PRIOR TO SETTING, THE
 BACKING WALL AND THE FACING SHALL BE DRENCHED WITH
 CLEAN WATER AND SHALL BE DISTINCTLY DAMP WHEN THE GROUT
 IS POURED.
  
 18) 2ND REQUEST. SHEET 395-S5-33 HAS A CONCEPTUAL
 DRAWING INDICATING THE TYPE OF TUBE STEEL HSS20X12X
 ?(LSH) THERE ARE NO DIMENSION FOR ANY OF THE ELEMENTS,
 ANGLE BETWEEN FRAMING MEMBERS, WELDS, TYPE OF
 ATTACHMENT TO DECKS BOTH TOP AND BOTTOM. 197.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 1ST REVIEW. SHEETS 160-A4.15 PODIUM METAL FIN,
 161-A4.16 PODIUM METAL FIN, THE DETAIL # 2 ON SHEET 160
 INDICATES A HSS TUBE POST, REFER TO STRUCTURAL SHEETS.
 THE STRUCTURAL SHEETS DO NOT PROVIDE DETAILS OF THIS
 STRUCTURAL TUBE. SHEET 395-S5-33 HAS A CONCEPTUAL
 DRAWING INDICATING THE TYPE OF TUBE STEEL HSS20X12X
 ?(LSH) THERE ARE NO DIMENSION FOR ANY OF THE ELEMENTS,
 ANGLE BETWEEN FRAMING MEMBERS, WELDS, TYPE OF
 ATTACHMENT TO DECKS BOTH TOP AND BOTTOM. 197.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 19) SHEET 162-A4-31 ROOF DETAILS:
 19A) DETAILS 1 & 2 SHOW THE USE OF POLYISOCYANURATE
 BOARD. WITH SINGLE PLY RECOVERY BOARD AND SINGLE PLY
 PVC ROOFING MEMBRANE ROOFING. PLEASE PROVIDE THE
 PRODUCT APPROVALS FOR EACH OF THE MEMBERS. FOR ALL
 ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 19B) DEFERRED SUBMITTALS. DETAILS 3 & 4 BOTH SHOW A
 TILE DECK ABOVE THE ROOFING SYSTEM. THE ROOFING SYSTEM
 WELL NEED TO PROVIDE PRODUCT APPROVALS FOR WIND AS WELL
 AS ENGINEERING FOR THE TILE DECK INSTALLATION THEY WILL
 MEET THE WIND LOADS FOR THE LOCATION ON THE
 BUILDING.2010 FBC-B COMPONENTS AND CLADDING.
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 20) BUILDING PROVISO: SHEETS 164-A4-41 AND 165-A4-41A
 S2.02 PROVIDE A BASIC DESIGN FOR THE CANOPY SYSTEMS.
 ADDITIONAL ENGINEERING SHEETS (SHOP DRAWINGS) TO BE
 SUBMITTED AS A DEFERRED SUBMITTAL. PLEASE ALSO PROVIDE
 HOW CODE COMPLIANCE WITH 2010 FBC-B 2405.2 ALLOWABLE
 GLAZING MATERIALS AND LIMITATIONS WILL BE COMPLIED
 WITH. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 21) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. ROOF HATCHES.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, INTAKE AND
 EXHAUST FANS ?
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 22) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  