| Date |
Text |
| 2016-02-01 14:58:47 | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. A6-70F DETAIL 3 IS CALLING OUT BATH 2 FOR SPEC |
| | B FHA, DETAIL 2 IS CALLING OUT BATH 2 AS STANDARD ,IT |
| | APPEARS TO BE A TYPO PLEASE CLARIFY. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 2. SHOLL WHICH BATHROOM IS DESIGNATED FOR FHA UNIT |
| | 21A-21B. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 3.SHT. A2-75A REFERS TO A2-60A THEY DO NOT MATCH PLEASE |
| | CLARIFY. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 4.SHOW HEIGHT OF SINK IN ADMINISTRATION OFFICE TO |
| | COMPLY WITH FBC ACC. SEC. 606.3 |
| | 5. SHOW ACCESSIBILITY LEVEL FOR AMENITY BATH ROOMS ON |
| | LEVEL 1-3. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 6. SHT. P5-01 AND P5-01 THE LINES FOR FLOOR LEVELS AND |
| | WATER PIPES LOOK THE SAME. PROVIDE CLEAR ISOMETRIC |
| | WATER RISER DIAGRAM. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 7. PROVIDE AN EXPANDED ISOMETRIC HOT AND COLD WATER |
| | RISER DIAGRAM FOR UNITS AND AMENITYS AND GUEST SUITES. |
| | PER WPB AMEND. TO FBC SEC. 107.2. |
| | 8.LABEL WATER RISERS TO COINCIDE WITH UNIT DESIGNATION. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 9. WATER HAMMER ARRESTOR REQUIRED FOR TRASH SHUTE FLUSH |
| | RING TO COMPLY WITH FBC PL.SEC. 604.9 |
| | 10. PROVIDE ISOMETRIC FOR COOLING TOWER FILL PIPING. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 11. SHT. P5-01 SHOWS 6IN. CW RISER RUNNING UP FROM |
| | PUMPS TO BLADDER TANKS WHERE DOES IT CONNETC WITH THE |
| | REST OF THE WATER RISER PLEASE CLARIFY. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 12. PROVIDE HOT WATER ISOMETRIC.RISER DIAGRAM. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 13. SIZE ALL SECTIONS OF PIPE ON HOT AND COLD ISOMETRIC |
| | RISER DIAGRAM. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 14.INDICATE DIRECTION OF FLOW MORE CLEARLY ON HOT WATER |
| | RECIRCULATION SYSTEM. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 15. PLEASE PROVIDE ISOMETRIC RISER DIAGRAM FOR SANITARY |
| | SHT.P5-03 |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 16.SHT. P5-13 SHOWS S-13A NOT SHOWN ON P5-05 PLEASE |
| | CLARIFY. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 17.AAV. ARE NOT ALLOWED BELOW FOURTH BRANCH INTERVAL |
| | DOWN FROM THE TOP OF THE STACK. SHALL COMPLY WITH. FBC |
| | PL. SEC.918.3.1 |
| | |
| | 18. PLEASE LABEL ALL STACKS TO MATCH |
| | .PER WPB AMEND. TO FBC SEC. 107.2. |
| | 19. PROVIDE EXPANDED ISOMETRIC DRAWINGS FOR ALL |
| | DWELLING UNITS AND AMENITY'S ONES PROVIDED ARE TO |
| | COMPACK. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 20. INDICATE BATHROOM # ON SANITARY ISOMETRIC DETAILS. |
| | PER WPB AMEND. TO FBC SEC. 107.2. |
| | 21.SHT P5.06 DOES NOT MATCH PLEASE CLARIFY. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 22.SHT P5-03 SHOW ALL STACKS MISSING |
| | S3/S6-8/S11/S14-16/S18-19/S21-15/S28-30. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 23. FIXTURE DRAINS FOR WASHING MACHINE SHALL BE 3IN. |
| | PER FBC PL.SEC.406.2 |
| | 24.SHT. P5-20 SHOW TRAP PRIMERS ON ALL FLOOR DRAINS AND |
| | HUB DRAINS. |
| | SHALL COMPLY WITH FBC PL.SEC. 1002.4 |
| | 25.PROVIDE FLOOR PLAN WITH PLUMBING FOR MECHANICAL ROOM |
| | AND ISOMETRIC. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 26.ALL VENTS THROUGH ROOF SHALL BE A MINIMUM OF 10FT |
| | AWAY FROM ANY AIR INTAKE. |
| | SHALL COMPLY WITH FBC PL. SEC.903.5 |
| | 27. P5-04 PROVIDE ISOMETRIC RISER DIAGRAM SHALL ALL |
| | RWL. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 28. MISSING RD1-2 ON RISER DIAGRAM SHT. P5-21 ,BETWEEN |
| | LINES Q+S/11+12 ON SHT.P2-26. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 29. SHT. P5-04 SHOW ALL RWL WITH SIZE AND SQ FT |
| | DRAINED. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 30.SHT. P5-23 DETAIL #2 LOCATION CLARIFY |
| | LOCATION,CLARIFY NOTE *IN RWL FOR OVERFLOW. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 31. SHT.P2-01 DD-2 BETWEEN LINES 1-2 AND A-D IS MISSING |
| | ON RISER DIAGRAM ON SHT. P5-24 ALSO MISSING PD BETWEEN |
| | LINES 1-2 A-D. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 32.SHT. P5-24 DETAIL #1 LABEL LOCATION. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 33. LABEL WITH LOCATION ALL DD+PD+AD ON RISER DIAGRAM |
| | AND PLUMBING FLOOR PLAN. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 34.SHT. C3-01 SHOWS EXISTING SEWER TO BE USED AS DRAIN |
| | FOR FOUNTAIN. WATER FROM FOUNTAIN POOLS AND WATER |
| | FEATURES SHALL NOT DRAIN INTO SANITARY PER. WPB ORD. |
| | SEC. 90-126.(5) |
| | 35. PROVIDE CALCULATIONS FOR STORM SUMP PUMP AND OIL |
| | SAND SEPARATORS. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 36. SHT. P5-24 SHORT TRENCH DRAINS MISSING SQ FT CALC . |
| | PLEASE PROVIDE. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 37. ALL OVER FLOW DRAINS MUST BE SIZED SAME AS MAIN |
| | DRAINS SHALL COMPLY WITH FBC PL. SEC. 1108.3 |
| | 38. PLEASE REMOVE ALL UNUSED DETAIL FROM PLUMBING |
| | DETAIL SHEETS. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 39. PROVIDE MANUFACTURE SECS FOR OIL SAND SEPARATOR. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 40. SHT. P4-06 DETAIL #3 IS THIS THE OIL SAND SEPARATOR |
| | YOU ARE USING PLEASE CLARIFY. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 41.PROVIDE MANUFACTURE SPEC SHEETS FOR ALL PUMPS |
| | ,THERMOSTATIC MIXING VALVES, TANKS, WATER HEATERS ECT. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 42. CLEAN OUTS REQUIRED AT THE BASE OF ALL STACKS SHOW |
| | COMPLIANCE WITH. FBC PL SEC. 708.3.4 |
| | 43. SHT.P5-20 + P2-26 IT APPEARS THAT YOU ARE DRAINING |
| | THE CONDENSATE OR COOLING WATER INTO THE SANITARY |
| | SYSTEM . CONDENSATE AND COOLING TOWER WATER MUST DRAIN |
| | INTO STORM AND BE INCLUDED IN SIZING CALCULATIONS. |
| | PER. WPB ORD. SEC. 90-126(5) |
| | 44. PROVIDE COMPLETE CONDENSATE RISER DIAGRAM WITH |
| | SIZING CALCULATIONS. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 45.SHOW CONNECTION OF IRRIGATION SYSTEM ON WATER RISER |
| | DIAGRAM. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 46. SEPARATE PERMITS REQUIRED FOR BACKFLOW PREVENTER'S |
| | AT METERS. FOR IRRIGATION, DOMESTIC, AND COOLING TOWERS |
| | POOL FILL,FIRE |
| | 47.SHT.M4-02 NOTE ON GENERATOR DETAIL STATES THAT FUEL |
| | PIPPING IS TO BE DONE BY ELECTRICAL CONTRACTOR. THAT IS |
| | NOT IN THERE SCOPE OF REG ALLOWED BY THE STATE PLEASE |
| | CLARIFY. |
| | 48. SHT. M4-04 DETAIL FOR AIR SEPARATOR, EXPANSION TANK |
| | SHOWS CONNECTION TO WATER SUPPLY PLEASE CLARIFY WHAT |
| | THIS SYSTEM IS FOR. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 49. PROVIDE MANUFACTURE SPEC SHEETS FOR GENERATOR. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 50. PLEASE PROVIDE MSDS SHEETS FOR DIESEL FUEL. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 51.PROVIDE PROVIDE DETAILED PIPING RISER DIAGRAM FOR |
| | DIESEL FUEL PIPING. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 52. WHERE DOES THE SUMP DRAINS ON FUEL PUMPS DISCHARGE |
| | TO. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | DO TO THE DEFICIENCY'S AND SOME SHEETS BEING UNCLEAR A |
| | COMPLETE AND COMPREHENSIVE REVIEW OF THE PLUMBING |
| | SYSTEMS CAN NOT BE COMPLETED AT THIS TIME. THIS MAY |
| | GENERATE MORE COMMENTS UPON SECOND REVIEW. |
| | |
| | POOL COMMENTS: |
| | |
| | 1. POOL ,HOT SPA POOL , HIS AND HER JACUZZIS AND ALL |
| | WATER FEATURES REQUIRE SEPARATE PERMIT FROM MAIN |
| | BUILDING.\ |
| | 2. SHALL OBTAIN OPERATING PERMIT FROM PALM BEACH COUNTY |
| | HEALTH DEPARTMENT. |
| | PER FBC SEC. 454 |
| | NOTE: OTHER ADMINISTRATIVE AND PROGRAMMATIC PROVISIONS |
| | APPLY. SEE DEPARTMENT OF HEALTH (DOH) RULE 64E-9, |
| | FLORIDA ADMINISTRATIVE CODE AND CHAPTER 514, FLORIDA |
| | STATUTES. THE REGULATION AND ENFORCEMENT OF THE INITIAL |
| | AND ANNUAL OPERATION PERMIT FOR PUBLIC POOLS ARE |
| | PREEMPTED TO THE DOH. THE CONSTRUCTION PERMIT HOLDER IS |
| | RESPONSIBLE FOR OBTAINING AN OPERATION PERMIT ISSUED BY |
| | DOH, AS A PUBLIC SWIMMING POOL SHALL NOT BE PUT INTO |
| | OPERATION WITHOUT AN INSPECTION AND OPERATION PERMIT |
| | ISSUED FROM THE DOH. DOH MAY GRANT VARIANCES FROM THE |
| | PROVISIONS OF THE FLORIDA BUILDING CODE SPECIFICALLY |
| | PERTAINING TO PUBLIC SWIMMING POOLS AND BATHING PLACES |
| | AS AUTHORIZED BY SECTION 514.0115, FLORIDA STATUTES. |
| | BUILDING OFFICIALS SHALL RECOGNIZE AND ENFORCE VARIANCE |
| | ORDERS ISSUED BY THE DEPARTMENT OF HEALTH PURSUANT TO |
| | SECTION 514.0115(5), FLORIDA STATUTES INCLUDING ANY |
| | CONDITIONS ATTACHED TO THE GRANTING OF THE VARIANCE. |
| | 3. SHT.W0-0.01 GENERAL NOTES SEC H ADA COMPLIANCE #1 |
| | SWIMMING POOL SHALL COMPLY WITH FBC ACC. 2014. |
| | 4. PROVIDE INSTALL GUIDE AND SPEC SHEETS FOR |
| | ACCESSIBILITY LIFT. |
| | NOTE: OTHER ADMINISTRATIVE AND PROGRAMMATIC PROVISIONS |
| | APPLY. SEE DEPARTMENT OF HEALTH (DOH) RULE 64E-9, |
| | FLORIDA ADMINISTRATIVE CODE AND CHAPTER 514, FLORIDA |
| | STATUTES. THE REGULATION AND ENFORCEMENT OF THE INITIAL |
| | AND ANNUAL OPERATION PERMIT FOR PUBLIC POOLS ARE |
| | PREEMPTED TO THE DOH. THE CONSTRUCTION PERMIT HOLDER IS |
| | RESPONSIBLE FOR OBTAINING AN OPERATION PERMIT ISSUED BY |
| | DOH, AS A PUBLIC SWIMMING POOL SHALL NOT BE PUT INTO |
| | OPERATION WITHOUT AN INSPECTION AND OPERATION PERMIT |
| | ISSUED FROM THE DOH. DOH MAY GRANT VARIANCES FROM THE |
| | PROVISIONS OF THE FLORIDA BUILDING CODE SPECIFICALLY |
| | PERTAINING TO PUBLIC SWIMMING POOLS AND BATHING PLACES |
| | AS AUTHORIZED BY SECTION 514.0115, FLORIDA STATUTES. |
| | BUILDING OFFICIALS SHALL RECOGNIZE AND ENFORCE VARIANCE |
| | ORDERS ISSUED BY THE DEPARTMENT OF HEALTH PURSUANT TO |
| | SECTION 514.0115(5), FLORIDA STATUTES INCLUDING ANY |
| | CONDITIONS ATTACHED TO THE GRANTING OF THE VARIANCE. |
| | 5. SHOW ACCESSIBILITY TO HOT SPA. SHALL COMPLY WITH FBC |
| | ACC. SEC. 1009.4 |
| | 6. SHT.W0-1.12 MENS SPA JACUZZI SHOWS A TOILET IN THE |
| | JACUZZI THE TOILET IS MISSING IN THE BATHROOM NEXT TO |
| | IT PLEASE CORRECT. |
| | PERWPB AMEND. TO FBC SEC.107.2.1 |
| | 7. SHT. W1-1.02 SHOW DIMENSIONS ON ALL FLOOR INLETS MAX |
| | SPACING BETWEEN 20 FT MAX DISTANCE FROM ADJACENT WALL |
| | 10FT TO COMPLY WITH FBC SEC.454.1.6.5.9.2 |
| | 8. PROVIDE DIMENSIONS AND VOLUME OF ALL COLLECTOR TANKS |
| | SHALL COMPLY WITH FBC SEC.454.1.6.5.10.5 |
| | 9. PROVIDE MATCH LINES ON ALL DRAWING TO SHOW |
| | CONTINUATION OF PIPING. PER WPBAMEND. TO FBC |
| | SEC.107.2.1 |
| | 10. PROVIDE MANUFACTURE SPECS FOR PUMPS AND OTHER |
| | EQUIPMENT .MAIN DRAIN AND SKIMMERS. PER WPBAMEND. TO |
| | FBC SEC.107.2.1 |
| | 11. DETAILS AND PLAN VIEWS FOR WATER FEATURES ARE |
| | UNCLEAR PLEASE PROVIDE COMPLETE PIPING DIAGRAMS AND |
| | DIMENSIONAL DEPTH OF ALL WATER FEATURES. PER WPBAMEND. |
| | TO FBC SEC.107.2.1 |
| | 12. SHT. W2-4.01 REFERS TO DETAIL 8 FOR BOTH DETAILS IN |
| | SEC B ONE SHOULD REFER TO DETAIL 7. PLEASE CLARIFY. PER |
| | WPBAMEND. TO FBC SEC.107.2.1 |
| | 13. SHOW ALL BACKFLOW DEVICES REQUIRED ON ALL FILL BOXS |
| | AND AUTO FILLS. TO COMPLY WITH FBC PL. SEC.608.1 |
| | 14. ONE URINAL IS REQUIRED IN MEN?S POOL BATHROOM. PER |
| | FBC PL TABLE 403.6 AND SEC 403.6 |
| | 15. EACH POOL BATHROOM SHALL BE EQUIPPED WITH BABY |
| | CHANGING TABLE .PER FBC PL. SEC. 403.6 |
| | 16. PROVIDE MANUFACTURE SPECS ON ALL POOL EQUIPMENT AND |
| | CHEMICAL TANKS. PER WPB AMEND. TO FBC 107.2. |
| | 17. ON ALL POOL, HOT SPA, JACUZZI, SPLASH PAD AND WATER |
| | FEATURES. PLEASE SHOW CONTINUATION OF PIPING LABEL AND |
| | LIST PAGE FOR CONTINUATION. PER WPB AMEND. TO FBC SEC. |
| | 107.2.1 |
| | 18. SHOW COMPLIANCE FOR OZONE EQUIPMENT ROOM |
| | VENTILATION MUST COMPLY WITH FBC SEC. 545.1.6.5.16.4.5 |
| | 19. SHOW COMPLIANCE WITH FBC SEC.545.1.6.5.16.4.6 FOR |
| | SELF-CONTAINED BREATHING APPARATUS. |
| | 20. CONCENTRATION OR OZONE IN THE RETURN LINE TO THE |
| | SPLASH PAD SHALL NOT EXCEED 0.1MG/2 PER FBC SEC. |
| | 454.1.6.5.16.4.3 |
| | 21. SHT. W4-1.03 EQUIPMENT TAG # DT-301 SHALL BE |
| | INSTALLED IN VERTICAL POSITION PER MANUFACTURE |
| | INSTALLATION GUIDE. |
| | 22. ALL CARTRIDGE FILTERS SHALL COMPLY WITH FBC |
| | .1.6.5.5.1 FOR FILTRATION RATE CAPACITIES. |
| | 23. ALL BACKFLOW PREVENTERS SHALL BE LEAD FREE AND |
| | LISTED ON THE UNIVERSITY OF SOUTHERN CALIFORNIA LIST OF |
| | APPROVED DEVICES. PER FBC PL SEC. 605.2 AND 605.2.1 |
| | 24. PROVIDE MSDS SHEETS FOR ALL CHEMICALS USED. PER WPB |
| | AMEND. TO FBC 107.2. |
| | 25. SHT. W4-3.01 CHECK THE FLOW ARROWS @ EQUIPMENT TAG |
| | CL-401 THE SCHEMATIC SHOWS THE FLOW IN OPPOSITE |
| | DIRECTION@ CL-401 SHALL COMPLY WITH FBC 454.1.6.5.16 |
| | 26. SHT. W4-3.01 A FIXED THERMOSTAT SHALL BE MOUNTED ON |
| | IN POOL RECIRCULATION LINE DOWNSTREAM FROM THE POOL |
| | HEATER OUTLET. THERMOSTAT MOUNTED ON POOL HEATER |
| | OUTLETS DOES NOT MEET THIS REQUIREMENT. PER FBC SEC. |
| | 454.1.6.5.14 CHECK ALL SYSTEMS FOR COMPLIANCE. |
| | 27. SHT. W4-3.02 FLOW ARROWS FROM CL-501 ARE REVERSED |
| | SHALL COMPLY WITH FBC 454.1.6.5.16 |
| | 28. OZONE GENERATING EQUIPMENT ELECTRICAL COMPONENTS |
| | AND WIRING SHALL COMPLY WITH THE REQUIREMENTS OF |
| | CHAPTER 27 OF THIS CODE AND THE MANUFACTURER SHALL |
| | PROVIDE A CERTIFICATE OF CONFORMANCE. THE PROCESS |
| | EQUIPMENT SHALL BE PROVIDED WITH AN EFFECTIVE MEANS TO |
| | ALERT THE USER WHEN A COMPONENT OF THIS EQUIPMENT IS |
| | NOT OPERATING PER FBC 454.1.6.5.16.4.1 |
| | 29. PROVIDE SPECS FOR CHANNEL DRAINS FOR SPA AND MAIN |
| | DRAINS FOR POOL. PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 30. PROVIDE SPECS FOR STEAM GENERATOR AND SHOW WHAT IT |
| | IS GOING TO BE USED FOR. PER WPB AMEND. TO FBC SEC. |
| | 107.2.1 |
| | 31. LABEL ALL EQUIPMENT AND CONTROLLERS ON ISOMETRIC |
| | VIEWS. PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 32. SHOW THE DEPTH OF ALL WATER FEATURES ON SECTION |
| | DRAWING PER WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | |
| | DO TO THE DEFICIENCY'S AND SOME SHEETS BEING UNCLEAR A |
| | COMPLETE AND COMPREHENSIVE REVIEW OF THE PLUMBING |
| | SYSTEMS CAN NOT BE COMPLETED AT THIS TIME. THIS MAY |
| | GENERATE MORE COMMENTS UPON SECOND REVIEW. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |