| 2016-01-14 12:00:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1. SHEET 008-A0-25 - THERE IS AN INCORRECT REFERENCE TO |
| | THE FIRE CODE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | |
| | 2. SHEET 027-C3-01 - THE LOCATION OF THE FIRE HYDRANTS |
| | AND FDC'S IS LIMITED AND NOT CONDUCIVE TO FIRE GROUND |
| | OPERATIONS.AND NOT APPROVED. |
| | |
| | THE FIRE LANE AROUND THE ENTIRE BUILDING IS NOT |
| | REQUIRED AND CAN BE ELIMINATED. |
| | |
| | RELOCATION OF THE FIRE HYDRANT AND FDC ON THE NORTH |
| | SIDE TO THE LANDSCAPE ISLAND AREA IN THE FRONT ON THE |
| | MAIN ENTRANCE ACCESS. ON SHEET 071-L9-10 THE AREA |
| | MARKED WITH TREES FD9 AND 4FD IS STRONGLY ENCOURAGED. |
| | 3FT TO THE SIDE AND REAR IS REQUIRED AND, IF DESIRED, |
| | THE EQUIPMENT CAN BE COLORED TO MATCH THE LANDSCAPE. |
| | |
| | RELOCATION OF THE SOUTHEAST FIRE HYDRANT AND FDC TO THE |
| | AREA OF THE BACK FLOW PREVENTORS BEFORE THE GATE IS |
| | STRONGLY ENCOURAGED. |
| | |
| | CLOSE COORDINATION WITH THE PREVNETION BUREAU WOULD BE |
| | EXTRMELY BENEFICIAL. |
| | |
| | 3. SHEET 603-FP2-OP1 & OP2 - PROVIDE NOTE INDICATING |
| | THAT FIRE SPRINKLER COVERAGE COMPLIES WITH THE |
| | REQUIRMENTS AND DESIGN OF STACKED PARKING WHERE |
| | APPLICABLE. |
| | |
| | 4. SHEET 603-FP2-OP1 - NO SPRINKLER PROTECTION SHOWN IN |
| | CENTER CORE AREAS. COMPLETE FIRE SPRINKLER SYSTEM IS |
| | REQUIRED BE NFPA 1, 101, AND 13. |
| | |
| | 5. SHEET 605 FP2-01 - NO SPRINKLER PROTECTION SHOWN IN |
| | EMEGENCY RM. |
| | |
| | 6. SHEET 605 FP2-01 - NO FIRE PROTECTION SHOWN IN FPL |
| | VAULT RM. |
| | |
| | 7. SHEET 605 FP2-01 - NO SPRINKLER PROTECTION SHOWN IN |
| | EXIT CORRIDOR 114 ALONG LAUNDRY RM. |
| | |
| | 8. SHEET 605 FP2-01 - NO SPRINKLER PROTECTION IN TRASH |
| | CHUTE ( NOT SHOWN FOR THE ENTIRE BLDG) |
| | |
| | 9. SHEET 606 FP2-02 - A FCVA COULD NOT BE LOCATED OR IS |
| | NOT INDICATED. |
| | |
| | (PROVIDE A NOTE FOR EACH FCVA ON EACH FLOOR ON WHAT IT |
| | SHUTS DOWN.) |
| | |
| | 10. SHEET 606 FP2-24 - A FCVA COULD NOT BE LOCATED OR |
| | IS NOT INDICATED ON THE 18TH & 19TH LEVEL. |
| | |
| | 11. SHEET 608 FP2-05 - A FCVA COULD NOT BE LOCATED OR |
| | IS NOT INDICATED. |
| | |
| | 12. SHEET 612 FP2-20 - A FCVA COULD NOT BE LOCATED AND |
| | INDICATED ITS ON THE 18TH & 19TH LEVEL. |
| | |
| | 13. SHEET 613 FP2-21 - A FCVA COULD NOT BE LOCATED AND |
| | INDICATED ITS ON THE 18TH & 19TH LEVEL. |
| | |
| | 14. SHEET 614 FP2-22 - A FCVA COULD NOT BE LOCATED AND |
| | INDICATED ITS ON THE 18TH & 19TH LEVEL. |
| | |
| | 15. SHEET 615 FP2-23 - A FCVA COULD NOT BE LOCATED AND |
| | INDICATED ITS ON THE 18TH & 19TH LEVEL. |
| | |
| | 16. SHEET 617-FP2-25 - A FCVA COULD NOT BE LOCATED AND |
| | INDICATED ITS ON THE 18TH & 19TH LEVEL. |
| | |
| | 17. SHEET 621-FP4-03 - A REGULATING HOSE VALVE IS NOT |
| | INDICATED. ( EACH FLLOR SHALL HAVE A NOTE INDICATING |
| | THE PSI AND LOCATION OF A RHV PER NFPA 14) |
| | |
| | 18. SHEET 180-A5-26 - NO DETAIL IS PROVIDED FOR |
| | INDICATED HANDRAILS, ALL HANDRAILS SHALL COMPLY WITH |
| | NFPA 101. CHAPTER 7, 7.2.2.4.4.1. MIN. 34" |
| | |
| | 19. SHEET 181-A5-27 - NO DETAIL IS PROVIDED FOR |
| | INDICATED HANDRAILS, ALL HANDRAILS SHALL COMPLY WITH |
| | NFPA 101. CHAPTER 7, 7.2.2.4.4.1. MIN. 34". |
| | |
| | 20. SHEET 182-A5-28 - NO DETAIL IS PROVIDED FOR |
| | INDICATED HANDRAILS, ALL HANDRAILS SHALL COMPLY WITH |
| | NFPA 101. CHAPTER 7, 7.2.2.4.4.1. MIN. 34". |
| | |
| | 21. SHEET 184-A5-51 - SECTIONS 1 & 2 HANDRAILS SHALL |
| | COMPLY WITH NFPA 101. CHAPTER 7, 7.2.2.4.4.1. MIN. 34". |
| | |
| | 22. GENRAL STAIRWAY SHEETS - STAIRWAY TREAD MARKING AND |
| | HANDRAIL MARKINGS SHALL COMPLY WITH NFPA 101, CHAPTER |
| | 7, 7.2.2.5.4.3, THROUGH 7.2.2.5.5.3 |
| | |
| | 23. SHEET 187-A5-21 - PROVIDE STAIWAY IDENTIFICATION |
| | SIGNAGE IS NOT INDICATED. STAIRWAY INDENTIFICATION |
| | SHALL COMPLY WITH NFPA 101, CHAPTER 7, 7.2.2.5.4. |
| | |
| | 24. MECHANICAL SHEETS 396 - 430 - IT IS NOT CLEARLY |
| | INDICATED WHAT AREAS WILL BE SMOKE CONTROL, SMOKE EVAC, |
| | STAIRWELL PRESSURIZATION OR ELEVATOR SHAFT |
| | PERSSURIZATION. |
| | |
| | 25. ELECTRICAL SHEETS 448 - 469 = IT IS NOT CLEARLY |
| | INDICATED THE LOCATION OF EXIT LIGHTING ON ANY LEVEL. |
| | |
| | 26. GENERAL SHEETS - IT IS NOT CLEARLY INDICATED THE |
| | INITIAL OR BACK-UP POWER OF THE FIRE PUMP. |
| | |
| | 27. GENERAL SHEETS - IT IS NOT CLEARLY INDICATED, IF |
| | ANY, THE EMERGENCY POWER TO THE EMERGENCY GENERATOR. |
| | |
| | 28. THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1, |
| | CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN |
| | THE FOLLOWING FEATURES: |
| | |
| | 1. SHALL BE A MINIMUM OF 200 FT SQUARED WITH A MINIMUM |
| | DIMENSION OF 10 FT. |
| | 2. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM. |
| | 3. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE PUBLIC TELEPHONE SYSTEM |
| | 4. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| | FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF |
| | EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING |
| | EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION |
| | OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE |
| | BARRIERS AND SMOKE PARTITIONS |
| | 5. A WORK TABLE. |
| | 6. IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN |
| | FOR THE BUILDING. |
| | 7. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM |
| | CONTROL UNIT. |
| | 8. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF |
| | THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL |
| | 9. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION |
| | SYSTEMS. |
| | 10. CONTROLS FOR UNLOCKING STAIRWAY DOORS |
| | SIMULTANEOUSLY |
| | 11. SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY |
| | PANELS |
| | 12. EMERGENCY AND STANDBY POWER STATUS INDICATORS |
| | 13. FIRE PUMP STATUS INDICATORS |
| | 14. GENERATOR SUPERVISION DEVICES AND MANUAL START AND |
| | TRANSFER FEATURES. |
| | 15. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| | BY OTHER SECTIONS OF THIS CODE |
| | 16. CONTROLS REQUIRED FOR SMOKE CONTROL |
| | 17. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| | A17.1. |
| | 18. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR |
| | SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS |
| | PROVIDED |
| | |
| | 29. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT |
| | DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. |
| | |
| | 35. THE BUREAU SHALL REVIEW ALL RE-SUBMITTED BUILDING |
| | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH |
| | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | |
| | |
| | |
| | |
| | |
| | |