Plan Review Notes For Permit 15111020
Permit Number 15111020
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-01-14 12:00:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. SHEET 008-A0-25 - THERE IS AN INCORRECT REFERENCE TO
 THE FIRE CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 2. SHEET 027-C3-01 - THE LOCATION OF THE FIRE HYDRANTS
 AND FDC'S IS LIMITED AND NOT CONDUCIVE TO FIRE GROUND
 OPERATIONS.AND NOT APPROVED.
  
 THE FIRE LANE AROUND THE ENTIRE BUILDING IS NOT
 REQUIRED AND CAN BE ELIMINATED.
  
 RELOCATION OF THE FIRE HYDRANT AND FDC ON THE NORTH
 SIDE TO THE LANDSCAPE ISLAND AREA IN THE FRONT ON THE
 MAIN ENTRANCE ACCESS. ON SHEET 071-L9-10 THE AREA
 MARKED WITH TREES FD9 AND 4FD IS STRONGLY ENCOURAGED.
 3FT TO THE SIDE AND REAR IS REQUIRED AND, IF DESIRED,
 THE EQUIPMENT CAN BE COLORED TO MATCH THE LANDSCAPE.
  
 RELOCATION OF THE SOUTHEAST FIRE HYDRANT AND FDC TO THE
 AREA OF THE BACK FLOW PREVENTORS BEFORE THE GATE IS
 STRONGLY ENCOURAGED.
  
 CLOSE COORDINATION WITH THE PREVNETION BUREAU WOULD BE
 EXTRMELY BENEFICIAL.
  
 3. SHEET 603-FP2-OP1 & OP2 - PROVIDE NOTE INDICATING
 THAT FIRE SPRINKLER COVERAGE COMPLIES WITH THE
 REQUIRMENTS AND DESIGN OF STACKED PARKING WHERE
 APPLICABLE.
  
 4. SHEET 603-FP2-OP1 - NO SPRINKLER PROTECTION SHOWN IN
 CENTER CORE AREAS. COMPLETE FIRE SPRINKLER SYSTEM IS
 REQUIRED BE NFPA 1, 101, AND 13.
  
 5. SHEET 605 FP2-01 - NO SPRINKLER PROTECTION SHOWN IN
 EMEGENCY RM.
  
 6. SHEET 605 FP2-01 - NO FIRE PROTECTION SHOWN IN FPL
 VAULT RM.
  
 7. SHEET 605 FP2-01 - NO SPRINKLER PROTECTION SHOWN IN
 EXIT CORRIDOR 114 ALONG LAUNDRY RM.
  
 8. SHEET 605 FP2-01 - NO SPRINKLER PROTECTION IN TRASH
 CHUTE ( NOT SHOWN FOR THE ENTIRE BLDG)
  
 9. SHEET 606 FP2-02 - A FCVA COULD NOT BE LOCATED OR IS
 NOT INDICATED.
  
 (PROVIDE A NOTE FOR EACH FCVA ON EACH FLOOR ON WHAT IT
 SHUTS DOWN.)
  
 10. SHEET 606 FP2-24 - A FCVA COULD NOT BE LOCATED OR
 IS NOT INDICATED ON THE 18TH & 19TH LEVEL.
  
 11. SHEET 608 FP2-05 - A FCVA COULD NOT BE LOCATED OR
 IS NOT INDICATED.
  
 12. SHEET 612 FP2-20 - A FCVA COULD NOT BE LOCATED AND
 INDICATED ITS ON THE 18TH & 19TH LEVEL.
  
 13. SHEET 613 FP2-21 - A FCVA COULD NOT BE LOCATED AND
 INDICATED ITS ON THE 18TH & 19TH LEVEL.
  
 14. SHEET 614 FP2-22 - A FCVA COULD NOT BE LOCATED AND
 INDICATED ITS ON THE 18TH & 19TH LEVEL.
  
 15. SHEET 615 FP2-23 - A FCVA COULD NOT BE LOCATED AND
 INDICATED ITS ON THE 18TH & 19TH LEVEL.
  
 16. SHEET 617-FP2-25 - A FCVA COULD NOT BE LOCATED AND
 INDICATED ITS ON THE 18TH & 19TH LEVEL.
  
 17. SHEET 621-FP4-03 - A REGULATING HOSE VALVE IS NOT
 INDICATED. ( EACH FLLOR SHALL HAVE A NOTE INDICATING
 THE PSI AND LOCATION OF A RHV PER NFPA 14)
  
 18. SHEET 180-A5-26 - NO DETAIL IS PROVIDED FOR
 INDICATED HANDRAILS, ALL HANDRAILS SHALL COMPLY WITH
 NFPA 101. CHAPTER 7, 7.2.2.4.4.1. MIN. 34"
  
 19. SHEET 181-A5-27 - NO DETAIL IS PROVIDED FOR
 INDICATED HANDRAILS, ALL HANDRAILS SHALL COMPLY WITH
 NFPA 101. CHAPTER 7, 7.2.2.4.4.1. MIN. 34".
  
 20. SHEET 182-A5-28 - NO DETAIL IS PROVIDED FOR
 INDICATED HANDRAILS, ALL HANDRAILS SHALL COMPLY WITH
 NFPA 101. CHAPTER 7, 7.2.2.4.4.1. MIN. 34".
  
 21. SHEET 184-A5-51 - SECTIONS 1 & 2 HANDRAILS SHALL
 COMPLY WITH NFPA 101. CHAPTER 7, 7.2.2.4.4.1. MIN. 34".
  
 22. GENRAL STAIRWAY SHEETS - STAIRWAY TREAD MARKING AND
 HANDRAIL MARKINGS SHALL COMPLY WITH NFPA 101, CHAPTER
 7, 7.2.2.5.4.3, THROUGH 7.2.2.5.5.3
  
 23. SHEET 187-A5-21 - PROVIDE STAIWAY IDENTIFICATION
 SIGNAGE IS NOT INDICATED. STAIRWAY INDENTIFICATION
 SHALL COMPLY WITH NFPA 101, CHAPTER 7, 7.2.2.5.4.
  
 24. MECHANICAL SHEETS 396 - 430 - IT IS NOT CLEARLY
 INDICATED WHAT AREAS WILL BE SMOKE CONTROL, SMOKE EVAC,
 STAIRWELL PRESSURIZATION OR ELEVATOR SHAFT
 PERSSURIZATION.
  
 25. ELECTRICAL SHEETS 448 - 469 = IT IS NOT CLEARLY
 INDICATED THE LOCATION OF EXIT LIGHTING ON ANY LEVEL.
  
 26. GENERAL SHEETS - IT IS NOT CLEARLY INDICATED THE
 INITIAL OR BACK-UP POWER OF THE FIRE PUMP.
  
 27. GENERAL SHEETS - IT IS NOT CLEARLY INDICATED, IF
 ANY, THE EMERGENCY POWER TO THE EMERGENCY GENERATOR.
  
 28. THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1,
 CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN
 THE FOLLOWING FEATURES:
  
 1. SHALL BE A MINIMUM OF 200 FT SQUARED WITH A MINIMUM
 DIMENSION OF 10 FT.
 2. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 3. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
 4. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION
 OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS
 5. A WORK TABLE.
 6. IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN
 FOR THE BUILDING.
 7. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 8. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF
 THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL
 9. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION
 SYSTEMS.
 10. CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY
 11. SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY
 PANELS
 12. EMERGENCY AND STANDBY POWER STATUS INDICATORS
 13. FIRE PUMP STATUS INDICATORS
 14. GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES.
 15. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE
 16. CONTROLS REQUIRED FOR SMOKE CONTROL
 17. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1.
 18. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED
  
 29. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 35. THE BUREAU SHALL REVIEW ALL RE-SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL