| 2016-02-10 06:37:21 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2010 |
| | NFPA 70- 2008 NEC |
| | COMMENTS: |
| | |
| | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| | PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL SITE |
| | LIGHTING AND ASSOCIATED EQUIPMENT, GENERATOR, ALL LOW |
| | VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE |
| | ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, SIGNAGE, |
| | WIRELESS SYSTEMS, ELEVATORS, CAR CHARGING STATIONS, |
| | ETC. A NOTE WILL SUFFICE. |
| | 2. SHEET E1.01- PLEASE ADD A GENERAL NOTE TO SHEET TO |
| | INDICATE THE REQUIREMENTS OF NEC 300.5D3 AND TABLE |
| | 300.5 FOR MINIMUM COVER REQUIREMENTS FOR CONDUITS AND |
| | THE PLACEMENT OF A WARNING RIBBON FOR THE SERVICE |
| | LATERAL CONDUCTORS SHOWN FOR THIS PROJECT. A NOTE WILL |
| | SUFFICE |
| | 3. SHEET E1.01- ADD A NOTE TO MAINTAIN ALL ELECTRICAL |
| | EQUIPMENT ABOVE THE BASELINE FLOOD ELEVATION PER STATE |
| | AND CITY REGULATORY AGENCIES. |
| | 4. SHEET E2.0P1- SHOW ON FLOOR PLAN THE ELEVATOR PIT |
| | CIRCUIT DESIGNATIONS FOR PIT LIGHTING, RECEPTACLES AND |
| | PUMP EQUIPMENT AS NOTED IN NEC 620.24 A,B AND C |
| | 5. SHEET E2.0P1- REFLECT ON FLOOR PLAN, PER FBC 107, |
| | MINIMUM CRITERIA FOR PLAN REVIEW, ALL PANEL AND CIRCUIT |
| | DESIGNATIONS FOR LIGHTING FIXTURES, RECEPTACLES AND |
| | MECHANICAL DISCONNECT WITH CIRCUIT NUMBERS ASSIGNED TO |
| | EQUIPMENT SHOWN. ALSO ID THE CIRCULATING FANS SHOWN. |
| | 6. SHEET E2-0P2- REFLECT ON FLOOR PLAN, PER FBC 107, |
| | MINIMUM CRITERIA FOR PLAN REVIEW, ALL PANEL AND CIRCUIT |
| | DESIGNATIONS FOR LIGHTING FIXTURES, RECEPTACLES AND |
| | MECHANICAL DISCONNECT WITH CIRCUIT NUMBERS ASSIGNED TO |
| | EQUIPMENT SHOWN. ALSO ID THE CIRCULATING FANS AND |
| | ROLLING DOORS |
| | 7. SHEET E2-01- IDENTIFY ALL AREAS ON FLOOR PLAN. GFCI |
| | PROTECTION REQUIRED WITHIN 6FT OF EVERY SINK PER NEC |
| | 210.8B5, SEE LAUNDRY ROOM ADJACENT AREA. MINIMUM |
| | CRITERIA FOR PLAN REVIEW, ALL PANEL AND CIRCUIT |
| | DESIGNATIONS FOR LIGHTING FIXTURES, RECEPTACLES AND |
| | MECHANICAL DISCONNECT WITH CIRCUIT NUMBERS ASSIGNED TO |
| | EQUIPMENT SHOWN. |
| | 8. SHEET E2-01L- SEE NOTE ABOVE REGARDING |
| | IDENTIFICATION OF ALL ELECTRICAL OUTLETS, LUMINAIRES |
| | ETC. FBC 107. ENTIRE SHEET TO BE ADDRESSED FOR A |
| | COMPLETE REVIEW. |
| | 9. SHEET E2-02- SAME AS ABOVE COMMENT #8. ALSO GFCI |
| | PROTECTION IS REQUIRED FOR THE SPA AND RESTROOMS AREAS |
| | SHOWN. |
| | 10. SHEET E2-05 THROUGH E2-17, E2.18 THROUGH E2.26L- |
| | SAME AS ABOVE COMMENT #8. FURTHER COMMENTS TO FOLLOW |
| | UPON RE-REVIEW. |
| | 11. SHEET 2.26L- PER NEC 700.20 SWITCH REQUIREMENTS- |
| | 3WAY SWITCHES SHALL NOT BE USED AS SHOWN ON EMERGENCY |
| | LIGHTING CIRCUITS. PLEASE CLARIFY DESIGN INTENT. |
| | 12. SHEET 2-27- PROVIDE A NOTE TO INDICATE LIGHTNING |
| | PROTECTION AND EQUIPMENT TO BE SUBMITTED UNDER SEPARATE |
| | PERMIT. ALSO PROVIDE THE OBSTRUCTION LIGHT/AIRCRAFT |
| | WARNING LIGHTS. |
| | 13. SHEET 2-51A THROUGH 2-53A- SAME AS ABOVE COMMENT #8 |
| | 14. SHEET 2-54A- SEE KITCHEN AREAS NEXT TO CIRCUIT #7, |
| | ADDRESS COUNTERTOP AREAS SPACING TO COMPLY WITH NEC |
| | 210.52C1 |
| | 15. SHEET 2-54B- SEE KITCHEN AREAS NEXT TO CIRCUIT #7, |
| | ADDRESS COUNTERTOP AREAS SPACING TO COMPLY WITH NEC |
| | 210.52C1 |
| | 16. SHEET 2-55A- SEE KITCHEN AREAS NEXT TO CIRCUIT #7, |
| | ADDRESS COUNTERTOP AREAS SPACING TO COMPLY WITH NEC |
| | 210.52C1 |
| | 17. SHEET 2-55B- SEE KITCHEN AREAS NEXT TO CIRCUIT #7, |
| | ADDRESS COUNTERTOP AREAS SPACING TO COMPLY WITH NEC |
| | 210.52C1 |
| | 18. SHEET 2-56A- SEE KITCHEN AREAS NEXT TO CIRCUIT #7, |
| | ADDRESS COUNTERTOP AREAS SPACING TO COMPLY WITH NEC |
| | 210.52C1 |
| | 19. SHEET 2-56B- SEE KITCHEN AREAS NEXT TO CIRCUIT #7, |
| | ADDRESS COUNTERTOP AREAS SPACING TO COMPLY WITH NEC |
| | 210.52C1 |
| | 20. SHEET 2-58B- SEE KITCHEN AREAS NEXT TO CIRCUIT #3, |
| | ADDRESS COUNTERTOP AREAS SPACING TO COMPLY WITH NEC |
| | 210.52C1 |
| | 21. SHEET 2-59A- SEE KITCHEN AREAS NEXT TO CIRCUIT #7, |
| | ADDRESS COUNTERTOP AREAS SPACING TO COMPLY WITH NEC |
| | 210.52C1 |
| | 22. RISER DIAGRAM AND PANEL SCHEDULES SHEET 5-01 |
| | THROUGH E6-12- PLEASE PROVIDE AVAILABLE FAULT CURRENT |
| | AVAILABLE AT THE FPL SERVICE. ATTACH TO DOCUMENTS |
| | LETTER FROM FLORIDA POWER & LIGHT INDICATING AIC. SHOW |
| | AIC CALCULATION BASED ON INFORMATION PROVIDED BY |
| | UTILITY FOR APPROVAL. NEC 110.24 FBC 107 |
| | 23. SHOW THE SIZE OF THE TAP BOX ON RISER DIAGRAM. FBC |
| | 107 |
| | 24. MAINS THAT ARE OVER 1000AMP 277/480VOLTS TO BE GFCI |
| | PROTECTED. NEC 240.13 |
| | 25. PROVIDE VOLTAGE DROP CALCULATIONS NOT ONLY FOR |
| | FEEDERS BUT ALSO THE BRANCH CIRCUIT FBC EC 505.7 |
| | 26. PANEL HR NOT ON PANEL SCHEDULE TO VERIFY LOADS AS |
| | SHOWN ON RISER DIAGRAM, PLEASE CLARIFY. FBC 107 |
| | 27. THE SUBMETTERING STANDBY POWER TO RESIDENTIAL UNITS |
| | ARE TOO VAGUE AS FAR AS MEETING THE REQUIREMENTS OF NEC |
| | 702.5A, B2. CLARIFY INTENT. |
| | 28. WILL NEED TO CORRELATE PANEL DESIGNATIONS SHOWN |
| | FEEDING FROM OTHER PANEL BOARDS; FOR EXAMPLE PANEL HS3 |
| | FROM HS2, NO OVERCURRENT PROTECTION SHOWN ON PANEL |
| | SCHEDULE. THIS IS JUST ONE EXAMPLE AS THIS CONDITION |
| | REPEATS ITSELF THROUGHOUT DESIGN. PLEASE REVISE A SHOW |
| | ALL CORRECTLY. FBC 107 |
| | 29. THERE ARE MULTIPLE PANEL LOAD SCHEDULES THAT |
| | REFLECT DIFFERENT AMPERAGES THAT THOSE SHOWN ON RISER |
| | DIAGRAM. EXAMPLE ; SEE PANEL EM |
| | 30. DESIGNATION OF PANEL BOARDS IS NOT ACCURATE. GEAR |
| | LABELED M1 IS ALSO LABELED MDP1. M2 IS LABELED MDP2. |
| | MAINTAIN CONSISTENCY TO PROVIDE AN ACCURATE REVIEW OF |
| | CONDUCTOR?S SIZES ETC. FBC 107 |
| | 31. ONE-LINE DIAGRAM TO REFLECT CONDUCTOR SIZES |
| | THROUGHOUT. |
| | 32. REVISIT LOAD CALCULATIONS FOR ACCURACY. SEE PANEL |
| | GDP WHICH IS SHOWN WITH NO CALCULATED LOADS YET RISER |
| | SHOWS LOADS OBVIOUSLY BEING DRAWN FROM THIS PANEL |
| | BOARD. NEED TO REVIEW MULTIPLE PANELS WITH SAME |
| | CONDITION. SELECTED CONDUCTORS ARE ALSO UNDERSIZED PER |
| | NEC 310.16 FOR 250AL. AS SHOWN. TOO MANY ITEMS TO LIST. |
| | NEC 220, FBC 107. |
| | 33. CORRECT AMPERAGE FOR GDP PANEL BOARD SHOWN AT |
| | 3000AMP ON RISER DIAGRAM BUT 800 AMPS MAIN BUS. PLEASE |
| | CLARIFY. |
| | 34. ATS #3 NOT SHOWN ON GDP PANEL BOARD SCHEDULE. SEE |
| | RISER DIAGRAM. SAME SCENARIO REPEATS ITSELF THROUGHOUT |
| | DESIGN. NEED TO ADDRESS. |
| | 35. NOTE THAT CONNECTED CALCULATED LOADS AND TOTAL |
| | DEMANDS ARE INACCURATE. ADDRESS PANEL BOARDS |
| | CALCULATION, FOR EXAMPLE SEE PANEL P, LNR, AND HNR, |
| | ETC. MULTIPLE PANEL BOARDS. NEC 220 FBC 107. |
| | 36. MAIN ELECTRICAL ROOMS MUST COMPLY WITH NEC |
| | 110.26C2, THERE SHALL BE ONE ENTRANCE AT EACH END OF |
| | THE WORKING SPACE. SHOW TWO MEANS OF EGRESS. ALSO NEC |
| | 110.26C3 REQUIRES PERSONNEL DOORS TO BE EQUIPPED WITH |
| | PANIC HARDWARE AND OPEN IN THE DIRECTION OF EGRESS. A |
| | NOTE WILL SUFFICE. |
| | 37. PROVIDE INFORMATION ON DRAWINGS AND DATA SHEETS FOR |
| | LIGHTING CONTROL PANEL, NOT ADDRESSED FOR REVIEW. |
| | 38. ALL ELECTRICAL ROOMS THAT CONTAIN TRANSFORMER MUST |
| | BE ID TO INDICATE IF TRANSFORMERS ARE BEING HUNG OR |
| | NOT,TO VERIFY CLEARANCE REQUIREMENTS PER NEC 110.26. |
| | SEE ROOM LEVEL 11, 18 AND 25. |
| | 39. CLARIFY AS NO ELEVATOR MACHINE ROOMS ARE SHOWN TO |
| | COMPLY WITH NEC 620.23 A,B AND C. |
| | 40. SHOW ELECTRICAL REQUIREMENTS FOR THE GENERATOR FUEL |
| | TANK. |
| | 41. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL |
| | FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS |
| | REGARDING THIS PROJECT. |
| | |
| | |
| | VALENTINO PEREZ |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |