2016-02-10 06:37:21INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2010
 NFPA 70- 2008 NEC
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL SITE
 LIGHTING AND ASSOCIATED EQUIPMENT, GENERATOR, ALL LOW
 VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, SIGNAGE,
 WIRELESS SYSTEMS, ELEVATORS, CAR CHARGING STATIONS,
 ETC. A NOTE WILL SUFFICE.
 2. SHEET E1.01- PLEASE ADD A GENERAL NOTE TO SHEET TO
 INDICATE THE REQUIREMENTS OF NEC 300.5D3 AND TABLE
 300.5 FOR MINIMUM COVER REQUIREMENTS FOR CONDUITS AND
 THE PLACEMENT OF A WARNING RIBBON FOR THE SERVICE
 LATERAL CONDUCTORS SHOWN FOR THIS PROJECT. A NOTE WILL
 SUFFICE
 3. SHEET E1.01- ADD A NOTE TO MAINTAIN ALL ELECTRICAL
 EQUIPMENT ABOVE THE BASELINE FLOOD ELEVATION PER STATE
 AND CITY REGULATORY AGENCIES.
 4. SHEET E2.0P1- SHOW ON FLOOR PLAN THE ELEVATOR PIT
 CIRCUIT DESIGNATIONS FOR PIT LIGHTING, RECEPTACLES AND
 PUMP EQUIPMENT AS NOTED IN NEC 620.24 A,B AND C
 5. SHEET E2.0P1- REFLECT ON FLOOR PLAN, PER FBC 107,
 MINIMUM CRITERIA FOR PLAN REVIEW, ALL PANEL AND CIRCUIT
 DESIGNATIONS FOR LIGHTING FIXTURES, RECEPTACLES AND
 MECHANICAL DISCONNECT WITH CIRCUIT NUMBERS ASSIGNED TO
 EQUIPMENT SHOWN. ALSO ID THE CIRCULATING FANS SHOWN.
 6. SHEET E2-0P2- REFLECT ON FLOOR PLAN, PER FBC 107,
 MINIMUM CRITERIA FOR PLAN REVIEW, ALL PANEL AND CIRCUIT
 DESIGNATIONS FOR LIGHTING FIXTURES, RECEPTACLES AND
 MECHANICAL DISCONNECT WITH CIRCUIT NUMBERS ASSIGNED TO
 EQUIPMENT SHOWN. ALSO ID THE CIRCULATING FANS AND
 ROLLING DOORS
 7. SHEET E2-01- IDENTIFY ALL AREAS ON FLOOR PLAN. GFCI
 PROTECTION REQUIRED WITHIN 6FT OF EVERY SINK PER NEC
 210.8B5, SEE LAUNDRY ROOM ADJACENT AREA. MINIMUM
 CRITERIA FOR PLAN REVIEW, ALL PANEL AND CIRCUIT
 DESIGNATIONS FOR LIGHTING FIXTURES, RECEPTACLES AND
 MECHANICAL DISCONNECT WITH CIRCUIT NUMBERS ASSIGNED TO
 EQUIPMENT SHOWN.
 8. SHEET E2-01L- SEE NOTE ABOVE REGARDING
 IDENTIFICATION OF ALL ELECTRICAL OUTLETS, LUMINAIRES
 ETC. FBC 107. ENTIRE SHEET TO BE ADDRESSED FOR A
 COMPLETE REVIEW.
 9. SHEET E2-02- SAME AS ABOVE COMMENT #8. ALSO GFCI
 PROTECTION IS REQUIRED FOR THE SPA AND RESTROOMS AREAS
 SHOWN.
 10. SHEET E2-05 THROUGH E2-17, E2.18 THROUGH E2.26L-
 SAME AS ABOVE COMMENT #8. FURTHER COMMENTS TO FOLLOW
 UPON RE-REVIEW.
 11. SHEET 2.26L- PER NEC 700.20 SWITCH REQUIREMENTS-
 3WAY SWITCHES SHALL NOT BE USED AS SHOWN ON EMERGENCY
 LIGHTING CIRCUITS. PLEASE CLARIFY DESIGN INTENT.
 12. SHEET 2-27- PROVIDE A NOTE TO INDICATE LIGHTNING
 PROTECTION AND EQUIPMENT TO BE SUBMITTED UNDER SEPARATE
 PERMIT. ALSO PROVIDE THE OBSTRUCTION LIGHT/AIRCRAFT
 WARNING LIGHTS.
 13. SHEET 2-51A THROUGH 2-53A- SAME AS ABOVE COMMENT #8
 14. SHEET 2-54A- SEE KITCHEN AREAS NEXT TO CIRCUIT #7,
 ADDRESS COUNTERTOP AREAS SPACING TO COMPLY WITH NEC
 210.52C1
 15. SHEET 2-54B- SEE KITCHEN AREAS NEXT TO CIRCUIT #7,
 ADDRESS COUNTERTOP AREAS SPACING TO COMPLY WITH NEC
 210.52C1
 16. SHEET 2-55A- SEE KITCHEN AREAS NEXT TO CIRCUIT #7,
 ADDRESS COUNTERTOP AREAS SPACING TO COMPLY WITH NEC
 210.52C1
 17. SHEET 2-55B- SEE KITCHEN AREAS NEXT TO CIRCUIT #7,
 ADDRESS COUNTERTOP AREAS SPACING TO COMPLY WITH NEC
 210.52C1
 18. SHEET 2-56A- SEE KITCHEN AREAS NEXT TO CIRCUIT #7,
 ADDRESS COUNTERTOP AREAS SPACING TO COMPLY WITH NEC
 210.52C1
 19. SHEET 2-56B- SEE KITCHEN AREAS NEXT TO CIRCUIT #7,
 ADDRESS COUNTERTOP AREAS SPACING TO COMPLY WITH NEC
 210.52C1
 20. SHEET 2-58B- SEE KITCHEN AREAS NEXT TO CIRCUIT #3,
 ADDRESS COUNTERTOP AREAS SPACING TO COMPLY WITH NEC
 210.52C1
 21. SHEET 2-59A- SEE KITCHEN AREAS NEXT TO CIRCUIT #7,
 ADDRESS COUNTERTOP AREAS SPACING TO COMPLY WITH NEC
 210.52C1
 22. RISER DIAGRAM AND PANEL SCHEDULES SHEET 5-01
 THROUGH E6-12- PLEASE PROVIDE AVAILABLE FAULT CURRENT
 AVAILABLE AT THE FPL SERVICE. ATTACH TO DOCUMENTS
 LETTER FROM FLORIDA POWER & LIGHT INDICATING AIC. SHOW
 AIC CALCULATION BASED ON INFORMATION PROVIDED BY
 UTILITY FOR APPROVAL. NEC 110.24 FBC 107
 23. SHOW THE SIZE OF THE TAP BOX ON RISER DIAGRAM. FBC
 107
 24. MAINS THAT ARE OVER 1000AMP 277/480VOLTS TO BE GFCI
 PROTECTED. NEC 240.13
 25. PROVIDE VOLTAGE DROP CALCULATIONS NOT ONLY FOR
 FEEDERS BUT ALSO THE BRANCH CIRCUIT FBC EC 505.7
 26. PANEL HR NOT ON PANEL SCHEDULE TO VERIFY LOADS AS
 SHOWN ON RISER DIAGRAM, PLEASE CLARIFY. FBC 107
 27. THE SUBMETTERING STANDBY POWER TO RESIDENTIAL UNITS
 ARE TOO VAGUE AS FAR AS MEETING THE REQUIREMENTS OF NEC
 702.5A, B2. CLARIFY INTENT.
 28. WILL NEED TO CORRELATE PANEL DESIGNATIONS SHOWN
 FEEDING FROM OTHER PANEL BOARDS; FOR EXAMPLE PANEL HS3
 FROM HS2, NO OVERCURRENT PROTECTION SHOWN ON PANEL
 SCHEDULE. THIS IS JUST ONE EXAMPLE AS THIS CONDITION
 REPEATS ITSELF THROUGHOUT DESIGN. PLEASE REVISE A SHOW
 ALL CORRECTLY. FBC 107
 29. THERE ARE MULTIPLE PANEL LOAD SCHEDULES THAT
 REFLECT DIFFERENT AMPERAGES THAT THOSE SHOWN ON RISER
 DIAGRAM. EXAMPLE ; SEE PANEL EM
 30. DESIGNATION OF PANEL BOARDS IS NOT ACCURATE. GEAR
 LABELED M1 IS ALSO LABELED MDP1. M2 IS LABELED MDP2.
 MAINTAIN CONSISTENCY TO PROVIDE AN ACCURATE REVIEW OF
 CONDUCTOR?S SIZES ETC. FBC 107
 31. ONE-LINE DIAGRAM TO REFLECT CONDUCTOR SIZES
 THROUGHOUT.
 32. REVISIT LOAD CALCULATIONS FOR ACCURACY. SEE PANEL
 GDP WHICH IS SHOWN WITH NO CALCULATED LOADS YET RISER
 SHOWS LOADS OBVIOUSLY BEING DRAWN FROM THIS PANEL
 BOARD. NEED TO REVIEW MULTIPLE PANELS WITH SAME
 CONDITION. SELECTED CONDUCTORS ARE ALSO UNDERSIZED PER
 NEC 310.16 FOR 250AL. AS SHOWN. TOO MANY ITEMS TO LIST.
 NEC 220, FBC 107.
 33. CORRECT AMPERAGE FOR GDP PANEL BOARD SHOWN AT
 3000AMP ON RISER DIAGRAM BUT 800 AMPS MAIN BUS. PLEASE
 CLARIFY.
 34. ATS #3 NOT SHOWN ON GDP PANEL BOARD SCHEDULE. SEE
 RISER DIAGRAM. SAME SCENARIO REPEATS ITSELF THROUGHOUT
 DESIGN. NEED TO ADDRESS.
 35. NOTE THAT CONNECTED CALCULATED LOADS AND TOTAL
 DEMANDS ARE INACCURATE. ADDRESS PANEL BOARDS
 CALCULATION, FOR EXAMPLE SEE PANEL P, LNR, AND HNR,
 ETC. MULTIPLE PANEL BOARDS. NEC 220 FBC 107.
 36. MAIN ELECTRICAL ROOMS MUST COMPLY WITH NEC
 110.26C2, THERE SHALL BE ONE ENTRANCE AT EACH END OF
 THE WORKING SPACE. SHOW TWO MEANS OF EGRESS. ALSO NEC
 110.26C3 REQUIRES PERSONNEL DOORS TO BE EQUIPPED WITH
 PANIC HARDWARE AND OPEN IN THE DIRECTION OF EGRESS. A
 NOTE WILL SUFFICE.
 37. PROVIDE INFORMATION ON DRAWINGS AND DATA SHEETS FOR
 LIGHTING CONTROL PANEL, NOT ADDRESSED FOR REVIEW.
 38. ALL ELECTRICAL ROOMS THAT CONTAIN TRANSFORMER MUST
 BE ID TO INDICATE IF TRANSFORMERS ARE BEING HUNG OR
 NOT,TO VERIFY CLEARANCE REQUIREMENTS PER NEC 110.26.
 SEE ROOM LEVEL 11, 18 AND 25.
 39. CLARIFY AS NO ELEVATOR MACHINE ROOMS ARE SHOWN TO
 COMPLY WITH NEC 620.23 A,B AND C.
 40. SHOW ELECTRICAL REQUIREMENTS FOR THE GENERATOR FUEL
 TANK.
 41. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  