| 2016-02-01 10:44:07 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15111020 |
| | ADD: 1100 S. FLAGLER DR. |
| | CONT: SUFFOLK CONSTRUCTION CO. |
| | TEL: 561-832-1616 |
| | E-MAIL: [email protected] / ED HANRATTY |
| | |
| | 2010 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | |
| | 1ST REVIEW |
| | DATE: MON. FEB. 01/2016 |
| | ACTION: DENIED |
| | |
| | NOTE: THIS REVIEW IS GOING TO BE COMPLETED AS A MIXED |
| | USE BUILDING, AND THE REQUIREMENTS FOR THE FOUNDATION |
| | PERMIT WILL BE MET AND THE ISSUANCE OF THE FOUNDATION |
| | PERMIT WILL BE FORTH COMING. PLEASE NOTE SOME COMMENTS |
| | MAY APPEAR AS WAS IN THE FOUNDATION PERMIT. |
| | 2010 FBC-B 1612.4 DESIGN & CONSTRUCTION SHALL BE IN |
| | ACCORDANCE WITH ASCE 24-05. |
| | ASCE 24-05 TABLE 6-1 MINIMUM ELEVATION OF |
| | FLOODPROOFING, RELATIVE TO THE BASE FLOOD (BFE) OR |
| | DESIGN FLOOD ELEVATION (DFE)- OUTSIDE OF HIGH RISK |
| | FLOOD HAZARD AREAS. STRUCTURE CATEGORY- II (FOOTNOTE) |
| | C. (C) DRY FLOODPROOFING OF RESIDENTIAL BUILDINGS AND |
| | RESIDENTIAL PORTIONS OF MIXED USE BUILDINGS SHALL NOT |
| | BE PERMITTED. |
| | |
| | 1) SHEET 078-A2-0P2 PARKING 2 (LOWER LEVEL) : |
| | 1A) PLEASE SEE NOTE ABOVE THE LOWER LEVEL OF THE |
| | PARKING GARAGE CANNOT BE USED FOR THE PARKING OF |
| | RESIDENTIAL VEHICLES OR STORAGE FOR THE RESIDENTS OF |
| | THE BUILDING. THE PLANS INDICATE 9 PRIVATE PARKING |
| | GARAGES AND VARIOUS AREAS THROUGHOUT THE LOWER PARKING |
| | AREA THAT INDICATE RESIDENT STORAGE. |
| | 2010 FBC-B 1612.4 DESIGN & CONSTRUCTION SHALL BE IN |
| | ACCORDANCE WITH ASCE 24-05. ASCE 24-05 TABLE 6-1. |
| | (FOOTNOTE) C. ( C ) DRY FLOODPROOFING OF RESIDENTIAL |
| | BUILDINGS AND RESIDENTIAL PORTIONS OF MIXED USE |
| | BUILDINGS SHALL NOT BE PERMITTED. |
| | |
| | 1B) ELEVATOR # 9 IS NOT IDENTIFIED ON SHEET 012-LS-P1/ |
| | P2. SHEET 176-A5.15 DOES NOT INDICATE IF THIS ELEVATOR |
| | IS A HYDRAULIC ELEVATOR? PLEASE IF THE ELEVATOR IS |
| | HYDRAULIC SHOW COMPLIANCE WITH 2010 FBC-B 3011. (1-4). |
| | IF THIS ELEVATOR IS HYDRAULIC IN WILL THE SUMP PUMP BE |
| | TIED INTO THE EMERGENCY ELECTRICAL PANEL TO KEEP DAMAGE |
| | TO THE HYDRAULIC SYSTEM AND CAB A MINIMUM. FEMA |
| | BULLETIN 4-93. |
| | |
| | 1C) ELEVATOR # 9 PLEASE IDENTIFY WHERE THE MACHINE ROOM |
| | FOR ELEVATOR # 9 IS LOCATED? PLEASE SHOW COMPLIANCE |
| | WITH 2010 FBC-B 3006.4. 1 HOUR FIRE RATING. |
| | |
| | 1D) THE OTHER ISSUE WITH ALL OF THE OTHER ELEVATORS |
| | THAT TRAVEL TO THE LOWER P2 PARKING LEVEL DEALS WITH |
| | THE FEMA TECHNICAL BULLETIN 4-93. FEMA REGULATION |
| | 60.3(A)(3) IF A PROPOSED BUILDING SITE WILL BE |
| | REASONABLY SAFE FROM FLOODING. IF A PROPOSED BUILDING |
| | SITE IS IN A FLOOD PRONE AREA, ALL NEW CONSTRUCTION AND |
| | SUBSTANTIAL IMPROVEMENTS SHALL? BE CONSTRUCTED WITH |
| | MATERIALS RESISTANT TO FLOOD DAMAGE,(III) BE |
| | CONSTRUCTED BY METHODS AND PRACTICES THAT MINIMIZE |
| | FLOOD DAMAGES, AND (IV) BE CONSTRUCTED WITH |
| | ELECTRICAL... EQUIPMENT AND OTHER SERVICES FACILITIES |
| | THAT ARE DESIGNED AND / OR LOCATED SO AS TO PREVENT |
| | WATER DAMAGE FROM ENTERING OR ACCUMULATING WITHIN THE |
| | COMPONENTS DURING CONDITIONS OF FLOODING. |
| | TO KEEP THE ELEVATOR CABS FROM HAVING SUBSTANTIAL |
| | DAMAGE FROM FLOODWATERS, IS THERE A INTERLOCKING |
| | CONTROL OR FLOAT SWITCH THAT WHEN ACTIVATED WILL KEEP |
| | THE CAB FROM DESCENDING INTO THE FLOODWATERS. |
| | THE OTHER QUESTION, IS NORMALLY WITH LOSS OF POWER THE |
| | ELEVATOR CABS DESCEND TO THE LOWEST LEVEL , WILL THE |
| | INTERLOCK AND OR FLOAT SWITCH ALLOW THE OVERRIDE? |
| | DURING TIMES OF FLOOD THIS WILL ENABLE ACCESSIBILITY TO |
| | THE LOWER PARKING GARAGE UNLESS THE OCCUPANT TRAVELS |
| | DOWN THE STAIRS. |
| | |
| | 1E) DOORS P202/ ELEV. LOBBY 1, DOOR P203/ ELEV. LOBBY |
| | 2, DOOR P205 ELEV. LOBBY 3/ DOOR P206/ ELEV. LOBBY #4, |
| | ON THE DOOR SCHEDULE SHEET 332-A8-11 DO NOT INDICATE A |
| | FIRE RATING, PLEASE SEE 2010 FBC-B 708.14.1 REQUIRING A |
| | FIRE PARTITION AS IN 709 OR ONE OF THE EXCEPTIONS. |
| | |
| | 1F) STAIR # 1 IS MISSING THE STAND PIPE IN THE |
| | STAIRWELL. 2010 FBC-B 905.3. REQUIRED INSTALLATION. |
| | ALSO NOT SHOWN ON 177-A5-21. |
| | |
| | 1G) THE BUILDING CORES CONTAINING STAIRWELLS 1 & 2 AND |
| | 3 & 4 DO NOT HAVE WALL IDENTIFICATION TAGS AS THE WALLS |
| | SURROUNDING THE PERIMETER OF THE BUILDING. SHEET |
| | 012-A0-31 THE LIFE SAFETY SHEET FOR THE PARKING GARAGES |
| | INDICATES FIRE RATED WALLS. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 1H) THE EAST WALL OF THE FPL VAULT DOES NOT INDICATE A |
| | WALL TAG. THE FLOOR ELEVATION IS INDICATED AT ELEVATION |
| | 6?-0? THIS WALL WILL STILL BE ON THIS LEVEL. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED, WALL NOT IDENTIFIED |
| | AS TO TYPE. |
| | |
| | 2) SHEET 079-A2-0P1 (PARKING LEVEL 1 UPPER LEVEL): |
| | 2A) ROOM # P123, THE FPL VAULT INDICATES AN EXTERIOR |
| | PAIR OF DOORS P123B AS THE ONLY DOORS. THE DOOR |
| | SCHEDULE INDICATES FOR THIS ROOM DOORS P123A AND P123B |
| | BOTH SETS OF DOORS ARE PAIRS OF DOORS. WHERE IS THE 2ND |
| | SET OF DOORS? 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. MISSING DOOR LOCATION. |
| | |
| | 2B) THE FPL VAULT DOORS SHOW ON THE HARDWARE SCHEDULE, |
| | HARDWARE TYPE 41. THERE ARE NO SHEETS IN THE INDEX THAT |
| | SHOW A HARDWARE SCHEDULE. PLEASE NOTE IF THE HARDWARE |
| | SCHEDULE IS IN A SPEC BOOK, WE DO NOT REVIEW SPEC |
| | BOOKS. PLEASE PROVIDE THE HARDWARE SCHEDULE. 2010 FBC-B |
| | 1008.1.10 PANIC AND FIRE EXIT HARDWARE. ELECTRICAL |
| | ROOMS WITH EQUIPMENT RATED 1,200 AMPERES OR MORE AND |
| | OVER 6 FEET (1829 MM) WIDE THAT CONTAIN OVERCURRENT |
| | DEVICES, SWITCHING DEVICES OR CONTROL DEVICES WITH EXIT |
| | OR EXIT ACCESS DOORS SHALL BE EQUIPPED WITH PANIC |
| | HARDWARE OR FIRE EXIT HARDWARE. THE DOORS SHALL SWING |
| | IN THE DIRECTION OF EGRESS TRAVEL. |
| | |
| | 2C) THE DOOR SCHEDULE SHEET 331-A8-11 DOOR # UNDER THE |
| | HEADING OF NOTES INDICATES EXTERIOR DOOR WITH FLOOD |
| | BARRIER. PLEASE PROVIDE WHAT STEPS ARE GOING TO TAKE |
| | PLACE FOR A FLOOD BARRIER FOR THIS DOOR. THIS CONDITION |
| | WILL NEED TO BE PART OF THE FLOOD EMERGENCY OPERATION |
| | PLAN, INSPECTION AND MAINTENANCE PLAN AND MINIMUM |
| | ENGINEERING CONSIDERATIONS (2) SEE FEMA?S TECHNICAL |
| | BULLETIN 3-93 NON-RESIDENTIAL FLOODPROOFING- |
| | REQUIREMENTS AND CERTIFICATION. |
| | |
| | 2D) THE MAIN ELECTRIC ROOM P124 DOES INDICATE 2 DOORS |
| | BUT ONE DOOR HAS DIFFERENT HARDWARE THAN THE FPL VAULT |
| | AND THE OTHER DOOR OF THE ELECTRICAL ROOM. HARDWARE |
| | TYPE 44 THE OTHER DOORS HAVE A HARDWARE TYPE 41. THERE |
| | IS NO HARDWARE SCHEDULE TO IDENTIFY THE TYPES OF |
| | HARDWARE. PLEASE PROVIDE CODE COMPLIANCE WITH 2010 |
| | FBC-B B 1008.1.10 PANIC AND FIRE EXIT HARDWARE. |
| | ELECTRICAL ROOMS WITH EQUIPMENT RATED 1,200 AMPERES OR |
| | MORE AND OVER 6 FEET (1829 MM) WIDE THAT CONTAIN |
| | OVERCURRENT DEVICES, SWITCHING DEVICES OR CONTROL |
| | DEVICES WITH EXIT OR EXIT ACCESS DOORS SHALL BE |
| | EQUIPPED WITH PANIC HARDWARE OR FIRE EXIT HARDWARE. THE |
| | DOORS SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL. |
| | |
| | 2E) THIS LEVEL SHOWS STACKED PARKING, PLEASE PROVIDE |
| | DETAILS FOR THIS TYPE OF LIFT. HOW THE LIFT WILL |
| | OPERATE, MANUFACTURERS SPEC, ANCHORAGE FOR LIFT, IS |
| | THERE A VALET THAT PUTS THE CARS ON THE LIFT, ETC? |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2F) THE SOUTH CORE PLAN SHOWS A WALL IDENTIFICATION TAG |
| | # 76 AS A 6 INCH CMU NON-BEARING WALL WITH A 2 HOUR |
| | FIRE RATING. PLEASE SHOW HOW A 2 HOUR FIRE RESISTANCE |
| | RATING WILL BE ACHIEVED. 2010 FBC-B TABLE 721.3.2. |
| | PLEASE PROVIDE FROM THE BLOCK MANUFACTURERS EQUIVALENT |
| | THICKNESS IN COMPLIANCE. |
| | |
| | 2G) TRASH ROOM P114 IS MISSING THE DOOR IDENTIFICATION |
| | TAG AND OPENING PROTECTIVE FIRE RATING. 2010 FBC-B |
| | TABLE 715.4. |
| | |
| | 3) SHEET 013-A)-32 & 080-A2-01 LEVEL 1 (LOBBY) : |
| | 3A) STAIR # 1 VERSUS THE FIRE EXIT CORRIDOR. THE STAIR |
| | EXIT CORRIDOR IS ACTUALLY AN EXIT PASSAGE WAY, WHICH |
| | REQUIRES THE EXIT ENCLOSURE TO BE SEPARATED FROM THE |
| | EXIT PASSAGEWAY BY A FIRE BARRIER. A FIRE DOOR ASSEMBLY |
| | COMPLYING WITH SECTION 715.4/ TABLE 715.4 (1 ? HR. |
| | PROTECTIVE) SHALL BE INSTALLED IN THE FIRE BARRIER TO |
| | PROVIDE A MEANS OF EGRESS FROM THE EXIT ENCLOSURE TO |
| | THE EXIT PASSAGE WAY. SEE 2010 FBC-B 1022.1. |
| | |
| | 3B) PLEASE SEE THE STAIR # 1 WITH THE NEW 1 ? HR. |
| | OPENING PROTECTIVE ON THE VERTICAL EXIT SEPARATING THE |
| | VERTICAL EXIT FROM THE EXIT PASSAGEWAY WILL NEED THE |
| | PLANS REVISED BECAUSE THE 2 DOORWAYS THAT SWING INTO |
| | THE EXIT PASSAGE WAY WILL CREATE A BOTTLENECK AND BLOCK |
| | ONE OF THE DOORS THAT SWING INTO THE EXIT PASSAGEWAY. |
| | 2010 FBC-B 1003.3 PROTRUDING OBJECTS. |
| | |
| | 3C) PLEASE BE AWARE OF FBC-B 1023.6. PENETRATIONS. |
| | PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT |
| | PASSAGEWAY ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| | DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT |
| | PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, |
| | ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION |
| | AND ELECTRICAL RACEWAY SERVING THE EXIT PASSAGEWAY AND |
| | TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE |
| | INCHES. |
| | |
| | 3D) STAIR # 1 IS MISSING THE REQUIRED STANDPIPE 2010 |
| | FBC-B 905.3.1. THIS STATEMENT WILL STAND FOR ALL |
| | FLOORS. |
| | |
| | 3E) PLEASE BE AWARE THAT THE DOORS ARE NOT IDENTIFIED |
| | ON THIS SHEET, NOR ARE THEY IDENTIFIED ON SHEET |
| | 166-A5-01. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 3F) PLEASE BE AWARE THAT THE WALL IDENTIFICATION TAGS |
| | ON THIS SHEET ARE MISSING AS WELL AS ON SHEET |
| | 166-A5-01. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 3G) GUEST ROOM CORRIDOR 102 SHOWS THE WALLS TO BE A |
| | MINIMUM OF A 1 HOUR FIRE RATING WITH THE EXCEPTION OF |
| | THE ELEVATOR OPENING? PLEASE PROVIDE COMPLIANCE WITH |
| | 2010 FBC-B TABLE 1018.1. |
| | |
| | 3H) THE CORRIDOR 102 FOR THE GUEST SUITES REQUIRES THE |
| | 1 HOUR RATING, THE 2010 FBC-B 1018.6 CORRIDOR |
| | CONTINUITY. FIRE-RESISTANCE-RATED CORRIDORS SHALL BE |
| | CONTINUOUS FROM THE POINT OF ENTRY TO AN EXIT, AND |
| | SHALL NOT BE INTERRUPTED BY INTERVENING ROOMS. |
| | EXCEPTION: FOYERS, LOBBIES OR RECEPTION ROOMS |
| | CONSTRUCTED AS REQUIRED FOR CORRIDORS SHALL NOT BE |
| | CONSTRUED AS INTERVENING ROOMS. |
| | PLEASE NOTE THE 1 HOUR FIRE RATING WAS NOT CONTINUED TO |
| | THE EXIT DOORWAY, LOBBY DOORS. |
| | |
| | 3I) STAIR TOWER # 4 IS MISSING THE REQUIRED FIRE DOOR |
| | BETWEEN THE VERTICAL EXIT AND THE EXIT PASSAGE WAY. |
| | 2010 FBC-B. A FIRE DOOR ASSEMBLY COMPLYING WITH SECTION |
| | 715.4/ TABLE 715.4 (1 ? HR. PROTECTIVE) SHALL BE |
| | INSTALLED IN THE FIRE BARRIER TO PROVIDE A MEANS OF |
| | EGRESS FROM THE EXIT ENCLOSURE TO THE EXIT PASSAGE WAY. |
| | SEE 2010 FBC-B 1022.1. |
| | |
| | 3J) ROOM 143 THERE IS WHAT APPEARS TO BE A 2 HOUR RATED |
| | SHAFT ENCLOSURE NEXT TO A COLUMN WITH ONE END OF THE |
| | SHAT ENCLOSURE NOT RATED. 2010 FBC-B 708.4. 2 HOUR |
| | SHAFT ENCLOSURE REQUIRED. |
| | |
| | 3K) PLEASE REVIEW THE (2) PAIR OF DOUBLE DOORS IN |
| | CORRIDOR 114 AND THE BEAUTY SALON 143. THERE IS LESS |
| | THAN 4 FEET BETWEEN DOORS. FAIR HOUSING ANSI A117-1998 |
| | SECTION. 404.2.6 DOORS IN SERIES. |
| | |
| | 3L) THE 1ST LEVEL SHEET 080-A2-01/ 013-A)-32 LIFE |
| | SAFETY AND 2ND LEVEL SHEET 081-A2-02/ 014-A0-33 LIFE |
| | SAFETY 2ND LEVEL. THESE SHEETS DEPICT A 2 STORY ATRIUM. |
| | WHAT THE LIFE SAFETY SHEETS FAIL TO PROVIDE IS THE 1 |
| | HOUR FIRE BARRIER (2010 FBC-B 404.6) CONSTRUCTED IN |
| | ACCORDANCE WITH SECTION 707. THE PLANS DO NOT SHOW A |
| | CUT SECTION WHERE ONE OF THE EXCEPTIONS WAS TAKEN. ONE |
| | HOUR FIRE RATED WALLS WOULD BE REQUIRED WITH ANY SPACE |
| | THAT COMMUNICATED WITH THE ATRIUM AND OPENING |
| | PROTECTIVE IN COMPLIANCE WITH 2010 FBC-B TABLE 715.4. |
| | SMOKE CONTROL IS NOT REQUIRED SINCE THIS IS A 2 STORY |
| | ATRIUM. |
| | |
| | 3M) ATRIUM. PLEASE SHOW HOW CODE COMPLIANCE WITH |
| | SECTION OF THE 2010 FBC-B 404.8 INTERIOR FINISHES. THE |
| | INTERIOR FINISHES OF WALLS AND CEILINGS OF THE ATRIUM |
| | SHALL NOT BE LESS THAN CLASS B WITH NO REDUCTIONS IN |
| | CLASS FOR SPRINKLER PROTECTION. |
| | |
| | 3N) BOTH ELEVATOR 7 & 9 BOTH ARE MISSING THE ELEVATOR |
| | LOBBY OR ONE OF THE EXCEPTIONS FOR ELEVATORS IN A |
| | HIGH-RISE BUILDING. 2010 FBC-B 708.14.1 AND OR |
| | EXCEPTIONS. PLEASE REVIEW BOAF (BUILDING OFFICIALS |
| | INFORMAL INTERPRETATION 3762. |
| | DATE: TUE JUN 28 2005 |
| | REPORT #: 3762 |
| | CODE: BUILDING |
| | SECTION: 412.6 |
| | QUESTION: |
| | IS IT THE INTENT OF SECTION 412.6 TO REQUIRE THE |
| | ELEVATOR LOBBIES FOR ALL ELEVATORS WITHIN A HIGH-RISE |
| | BUILDING? ARE ELEVATORS THAT DO NOT SERVE THE HIGH-RISE |
| | PORTION OF THE BUILDING EXEMPT FROM THE ELEVATOR |
| | LOBBY REQUIREMENTS? |
| | ANSWER: |
| | YES. ELEVATOR LOBBIES ARE REQUIRED FOR LOW-RISE |
| | PORTIONS OF HIGH-RISE BUILDINGS. ELEVATOR LOBBIES SERVE |
| | AS |
| | A STAGING AREA FOR EMERGENCY PERSONNEL DURING A FIRE |
| | EMERGENCY AND A COMPARATIVELY SMOKE-FREE SPACE |
| | FOR HANDLING OCCUPANTS NEEDING SPECIAL ASSISTANCE WITH |
| | EVACUATION. |
| | COMMENTARY: |
| | IT IS THE INTENT OF SECTION 412.6 TO, AMONG OTHER |
| | THINGS, (1)PREVENT MIGRATION OF HEAT AND HARMFUL |
| | PRODUCTS OF COMBUSTION THROUGH THE ELEVATOR HOISTWAY TO |
| | OTHER FLOORS IN HIGH-RISE BUILDINGS (2)PROVIDE |
| | PROTECTION FOR FIRE FIGHTER OPERATIONS IN THE EVENT THE |
| | ELEVATORS ARE USED FOR EMERGENCY RESPONSE IN A |
| | HIGH-RISE STRUCTURE (3)INHIBIT POTENTIAL EFFECTS OF THE |
| | ELEVATOR HOISTWAY ON THE PERFORMANCE OF HIGH-RISE SMOKE |
| | CONTROL SYSTEMS AND (4) ENHANCE LIFE SAFETY IN EXIT |
| | ACCESS CORRIDORS THAT REQUIRE OCCUPANTS TO TRAVERSE AN |
| | ELEVATOR LOBBY THAT SERVES AS PART OF THE EXIT ACCESS |
| | IN A HIGH-RISE BUILDING. |
| | NOTICE: |
| | THE BUILDING OFFICIALS ASSOCIATION OF FLORIDA, IN |
| | COOPERATION WITH THE FLORIDA BUILDING COMMISSION, THE |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ICC, AND |
| | INDUSTRY AND PROFESSIONAL EXPERTS OFFER THIS |
| | INTERPRETATION OF THE FLORIDA BUILDING CODE IN THE |
| | INTEREST OF CONSISTENCY IN THEIR APPLICATION STATEWIDE. |
| | THIS INTERPRETATION IS INFORMAL, NON-BINDING AND |
| | SUBJECT TO ACCEPTANCE AND APPROVAL BY THE LOCAL |
| | BUILDING OFFICIAL. |
| | |
| | 3O) THE FIRE COMMAND CENTER MEETS THE 200 SQUARE FOOT |
| | REQUIREMENT BUT PLEASE PROVIDE A DETAILED LAYOUT OF THE |
| | FIRE COMMAND CENTER TO BE APPROVED BY FIRE PRIOR TO |
| | INSTALLATION. 2010 FBC-B 911.1.4. |
| | PLEASE REVIEW FBC-B 911.1.5 FOR REQUIRED FEATURES. |
| | |
| | 3O)(1) PLEASE SHOW COMPLIANCE WITH 2010 FBC-B: 403.4.3 |
| | EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM. |
| | |
| | 3O)(2) PLEASE SHOW COMPLIANCE WITH 2010 FBC-B: 403.4.4 |
| | EMERGENCY RESPONDER RADIO COVERAGE. AN EMERGENCY |
| | VOICE/ALARM COMMUNICATION SYSTEM SHALL BE PROVIDED IN |
| | ACCORDANCE WITH SECTION 907.5.2.2. |
| | EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN |
| | ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. |
| | SECTION 907.5.2.2. |
| | |
| | 3O)(3) PLEASE SHOW COMPLIANCE WITH 2010: 403.5.3 |
| | STAIRWAY DOOR OPERATION. STAIRWAY DOORS OTHER THAN THE |
| | EXIT DISCHARGE DOORS SHALL BE PERMITTED TO BE LOCKED |
| | FROM THE STAIRWAY SIDE. STAIRWAY DOORS THAT ARE LOCKED |
| | FROM THE STAIRWAY SIDE SHALL BE CAPABLE OF BEING |
| | UNLOCKED SIMULTANEOUSLY WITHOUT UNLATCHING UPON A |
| | SIGNAL FROM THE FIRE COMMAND CENTER. |
| | |
| | 3O)(4) 403.5.3.1 STAIRWAY COMMUNICATION SYSTEM. A |
| | TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS SYSTEM |
| | CONNECTED TO AN APPROVED CONSTANTLY ATTENDED STATION |
| | SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH FLOOR IN |
| | EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY ARE |
| | LOCKED. |
| | |
| | 3O)(5) 403.5.5 LUMINOUS EGRESS PATH MARKINGS. LUMINOUS |
| | EGRESS PATH MARKINGS SHALL BE PROVIDED IN ACCORDANCE |
| | WITH 2010 FBC-B SECTION 1024. |
| | |
| | 3O)6) A CUT SECTION THROUGH THE BUILDING SHOWING WHICH |
| | STAIRWELLS SERVICE WHICH SUITES SINCE THE FLOORS WITH 3 |
| | SUITES USE STAIRWELLS 2 & 3 SO FIRE FIGHTERS WILL KNOW |
| | WHICH STAIRWELLS AND FIREMEN?S ELEVATORS TO USE FOR |
| | FIREFIGHTING AND OR EMERGENCIES. 107.2.1.3 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 3P) PLEASE PROVIDE WHERE COMPLIANCE WITH THE 2010 FBC-B |
| | SECTION 403.3.2 WATER SUPPLY TO REQUIRED FIRE PUMPS. |
| | REQUIRED FIRE PUMPS SHALL BE SUPPLIED BY CONNECTIONS TO |
| | A MINIMUM OF TWO WATER MAINS LOCATED IN DIFFERENT |
| | STREETS. SEPARATE SUPPLY PIPING SHALL BE PROVIDED |
| | BETWEEN EACH CONNECTION TO THE WATER MAIN AND THE |
| | PUMPS. EACH CONNECTION AND THE SUPPLY PIPING BETWEEN |
| | THE CONNECTION AND THE PUMPS SHALL BE SIZED TO SUPPLY |
| | THE FLOW AND PRESSURE REQUIRED FOR THE PUMPS TO |
| | OPERATE. |
| | |
| | EXCEPTION: TWO CONNECTIONS TO THE SAME MAIN SHALL BE |
| | PERMITTED PROVIDED THE MAIN IS VALVED SUCH THAT AN |
| | INTERRUPTION CAN BE ISOLATED SO THAT THE WATER SUPPLY |
| | WILL CONTINUE WITHOUT INTERRUPTION THROUGH AT LEAST ONE |
| | OF THE CONNECTIONS. TO BE APPROVED BY THE FIRE |
| | DEPARTMENT. |
| | |
| | 3R) THE LAUNDRY ROOM WILL NEED TO MEET FAIR HOUSING, AT |
| | LEAST ONE OF EACH TYPE OF APPLIANCES PROVIDED IN EACH |
| | LAUNDRY AREA, EXPECT THAT LAUNDRY ROOMS SERVING COVERED |
| | MULTIPLE-FAMILY DWELLINGS WOULD NOT BE REQUIRED TO HAVE |
| | FRONT-LOADING WASHERS IN ORDER TO MEET THE REQUIREMENTS |
| | OF 100.205?(1). (WHERE FRONT LOADING WASHERS ARE NOT |
| | PROVIDED, MANAGEMENT WILL BE EXPECTED TO PROVIDE |
| | ASSISTANCE DEVICES ON REQUEST IF NECESSARY TO PERMIT A |
| | RESIDENT TO USE A TOP LOADING WASHER. ANSI |
| | A117.1SECTION 4.32.6. ALSO IF COIN OPERATED VENDING |
| | MACHINES ARE AVAILABLE ANSI A117.1 4.25 OPERATING |
| | MECHANISMS. |
| | |
| | 3S) THE PLANS SHOW AT THE ENTRY LEVEL OF THE LOBBY A |
| | RECEPTION/ REGISTRATION DESK. PLEASE PROVIDE COMPLIANCE |
| | WITH FAIR HOUSING SPECIFICATION OF ANSI 4.31 ALSO SEE |
| | REACH RANGES. |
| | |
| | 3T) THIS COMMENT WILL STAND FOR ALL FLOORS WITH |
| | MULTIPLE R2 DWELLING UNITS ON THE SAME FLOOR OR |
| | DWELLING UNITS ABOVE OR BELOW THE OCCUPIED UNIT. PLEASE |
| | PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 3T)(1) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 3T)(2) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 3T)(3) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 3U) THE STRUCTURAL SHEETS INDICATE THE THICKNESS OF THE |
| | FLOOR SLABS FOR THE MOST PART. I COULD NOT IDENTIFY THE |
| | THICKNESS OF THE FLOOR SLABS FOR SHEETS: |
| | 0360-S2.01M |
| | 361-S2.02 GUEST SUITES LEVELS 2 & 3 |
| | S361-S2.02 LEVEL 2 |
| | S362-S2.02A POOL DECK FRAMING |
| | |
| | LEVEL DECK 1 (LOBBY) IS 12 INCH DECK |
| | ALL OTHER DECKS ARE 10 INCH WITH EXCEPTION OF LEVEL 20 |
| | WHICH IS ? OF DECK 14 INCHES DECK. |
| | |
| | |
| | 4) SHEET 014-A0-33/ 082-A2-03: 2ND LEVEL GUEST SUITES. |
| | |
| | 4A) THE PLANS INDICATE 3 FLOORS OF GUEST SUITES. THE |
| | TERM GUEST SUITES LEAD ONE TO BELIEVE THAT THE SUITES |
| | ARE FOR SHORT TERM USE. IT IS UNCLEAR IF THESE UNITS |
| | SHOULD BE REVIEWED UNDER FAIR HOUSING OR IF THEY SHOULD |
| | BE REVIEWED UNDER THE FLORIDA ACCESSIBILITY CODE OR |
| | BOTH. PLEASE SEE 2010 FBC-ACCESSIBILITY CODE |
| | DEFINITIONS: RESORT CONDOMINIUM. (SECTION 509.242, |
| | F.S.). A RESORT CONDOMINIUM IS ANY UNIT OR GROUP OF |
| | UNITS IN A CONDOMINIUM, COOPERATIVE, OR TIME-SHARE PLAN |
| | WHICH IS RENTED MORE THAN THREE TIMES A CALENDAR YEAR |
| | FOR PERIODS OF LESS THAN 30 DAYS OR ONE CALENDAR MONTH, |
| | WHICHEVER IS LESS, OR WHICH IS ADVERTISED OR HELD OUT |
| | TO THE PUBLIC AS A PLACE REGULARLY RENTED FOR PERIODS |
| | OF LESS THAN 30 DAYS OR ONE CALENDAR MONTH, WHICHEVER |
| | IS LESS (SEE ALSO, PLACES OF LODGING). |
| | |
| | 4B) THERE IS A DISCREPANCY IN PLANS IT WOULD APPEAR. |
| | SHEET 014-A0-33 LEVEL 2 GUEST SUITES IT APPEARS THE |
| | MECHANICAL UNIT HP-1IN GUEST SUITES 11 & 12 ARE LOCATED |
| | IN A ONE HOUR SHAFT WHEREAS THE UNITS 9 & 10 THE UNITS |
| | ARE NOT LOCATED IN A RATED WALL. IT APPEARS IN UNITS 11 |
| | & 12 THERE IS A VERTICAL 8X16 INCH EXHAUST DUCT NOT |
| | SHOWN IN A SHAFT, MECHANICAL SHEETS INDICATE THAT IN |
| | SOME AREA 2 HOUR FLAME BAR IS TO BE INSTALLED. PLEASE |
| | PROVIDE DETAILED INFORMATION IN RESPONSE AS TO WHAT |
| | AREAS ARE TO BE SHAFTS, HOUR RATING OF SHAFTS, WHERE |
| | THE FLAME BAR IS TO BE INSTALLED AND FIRE STOPPING |
| | ASSEMBLIES FOR THROUGH PENETRATIONS. THIS COMMENT WILL |
| | BE COMMON FOR THE 3 FLOORS OF GUEST SUITES. 2010 FBC-B |
| | 708.2.4 /716.6 HORIZONTAL ASSEMBLIES. THIS CONDITION |
| | APPEARS ON THE 3RD LEVEL OF GUEST SUITES AS WELL. |
| | |
| | 4C) SUITE # 7 & 11 IS MISSING THE SHOWER ENCLOSURE ON |
| | 014-A0-33. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 4D) SUITE # 5 & 9 IS MISSING THE SHOWER ON SHEET |
| | 014-A0-33. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 5) SHEET 014-A)-33/ 081-A2-02: 2ND LEVEL AMENITIES/ 3RD |
| | LEVEL GUEST SUITES. |
| | 5A) SHEET 081-A2-02, STAIR # 1 ON THE 3RD LEVEL OF THE |
| | GUEST ROOMS IS MISSING THE 1 ? HR. FIRE RATED DOOR. |
| | 2010 FBC-B TABLE 715.4. |
| | |
| | 5B) SHEET 014-A)-33 STAIR # 1 IS MISSING THE |
| | ILLUSTRATED DOWN PORTION OF STAIRS IN THE STAIRWELL |
| | ENCLOSURE. 107.2.1.3 ADDITIONAL INFORMATION, TYPO. |
| | |
| | 5C) SHEET 081-A2-02 IS MISSING BOTH THE WALL & DOOR |
| | IDENTIFICATION TAGS. CODE COMPLIANCE CANNOT BE |
| | DETERMINED. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 5D) SHEET 014-A)-33 IS THE 2ND LEVEL OF THE ATRIUM. |
| | THIS SHEETS DEPICTS THE 2ND FLOOR OF THE ATRIUM. WHAT |
| | THE LIFE SAFETY SHEETS FAIL TO PROVIDE IS THE 1 HOUR |
| | FIRE BARRIER (2010 FBC-B 404.6) CONSTRUCTED IN |
| | ACCORDANCE WITH SECTION 707. THE PLANS DO NOT SHOW A |
| | CUT SECTION WHERE ONE OF THE EXCEPTIONS WAS TAKEN. ONE |
| | HOUR FIRE RATED WALLS WOULD BE REQUIRED WITH ANY SPACE |
| | THAT COMMUNICATED WITH THE ATRIUM AND OPENING |
| | PROTECTIVE IN COMPLIANCE WITH 2010 FBC-B TABLE 715.4. |
| | SMOKE CONTROL IS NOT REQUIRED SINCE THIS IS A 2 STORY |
| | ATRIUM. PLEASE NOTE THE 3 LEVELS OF THE R2 GUEST ROOMS |
| | TRAVEL THROUGH A 1 HOUR FIRE RATED ACCESS CORRIDOR INTO |
| | THE ATRIUM. |
| | |
| | 5E) . PLEASE SHOW HOW CODE COMPLIANCE WITH SECTION OF |
| | THE 2010 FBC-B 404.8 INTERIOR FINISHES. THE INTERIOR |
| | FINISHES OF WALLS AND CEILINGS OF THE ATRIUM SHALL NOT |
| | BE LESS THAN CLASS B WITH NO REDUCTIONS IN CLASS FOR |
| | SPRINKLER PROTECTION. |
| | |
| | 5F) THIS SHEET INDICATES THE BRIDGE SECTION OF THE 2ND |
| | LEVEL IS INDICATED AS A MEZZANINE LOBBY. THE 2ND FLOOR |
| | AREA THAT IS OPEN AND COMMUNICATES IS OVER ? OF THE |
| | OPEN AREAS ALLOWED BY FBC-B 505.2 EXCEPTION # 2 FOR |
| | TYPE I TYPE II BUILDINGS. THIS IS A TRUE 2 STORY |
| | ATRIUM, FBC-B 404.6 ENCLOSURES OF ATRIUMS. |
| | |
| | 5G) SHEET 014-A0-33 POOL DECK STAIR # 6 & 7 SHOW THE |
| | USE OF AN AREA OF RESCUE ASSISTANCE. THE 2010 FBC-B |
| | 1007.1 ACCESSIBLE MEANS OF EGRESS. ACCESSIBLE MEANS OF |
| | EGRESS SHALL BE PROVIDED IN ACCORDANCE WITH THE |
| | APPLICABLE SECTIONS OF THE FLORIDA BUILDING CODE, |
| | ACCESSIBILITY. |
| | 2010 FBC-ACCESSIBILITY CODE. ACCESSIBLE MEANS OF EGRESS |
| | . 207.1 GENERAL. MEANS OF EGRESS SHALL COMPLY WITH |
| | SECTION 1003.2.13 OF THE INTERNATIONAL BUILDING CODE |
| | (2000 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF |
| | THE INTERNATIONAL BUILDING CODE (2003 EDITION) |
| | (INCORPORATED BY REFERENCE, SEE "REFERENCED STANDARDS" |
| | IN CHAPTER 1). |
| | PLEASE SHOW FULL COMPLIANCE FOR THE AREA OF REFUGE |
| | ASSISTANCE, 2003 IBC-B REQUIREMENTS 1007.6.(1-7) & |
| | 1007.8(1-3). |
| | |
| | 5H) DEPENDING ON THE CLASSIFICATION AND OR OF THE |
| | DINING ROOM, BEAUTY PARLOR AND GUEST ROOMS THERE MAYBE |
| | ELEMENTS OF THIS BUILDING THAT MAY FALL UNDER THE 2010 |
| | FBC-ACCESSIBILITY CODE. THE POOL DECK AND ACCESS TO THE |
| | POOL WOULD THEN NEED TO MEET THE REQUIREMENTS OF 1009. |
| | SWIMMING POOLS AND SPAS AS WELL AS WHERE PROVIDED, POOL |
| | LIFTS SLOPED ENTRIES, TRANSFER WALLS, TRANSFER SYSTEMS, |
| | AND POOL STAIRS SHALL COMPLY WITH 1009. IF THE END |
| | RESULT OF THE RESEARCH IS COMPLETED AND ONLY FAIR |
| | HOUSING IS TO BE APPLIED THEN ONLY ACCESS TO THE POOL |
| | DECK WILL BE A FACTOR. |
| | |
| | 5I) PLEASE NOTE THE POOL DECK DOES SHOW STEPS BUT THERE |
| | ARE NO RAMPS DESIGNATED ON THE PLANS FOR AN ACCESSIBLE |
| | ROUTE TO THE LOWER POOL DECK AREA. FAIR HOSING ANSI |
| | A117.1 4.3 (C) CONNECTING ACCESSIBLE BUILDING OR |
| | FACILITY ENTRANCES WITH ACCESSIBLE SPACES AND ELEMENTS |
| | WITHIN THE BUILDING OR FACILITY, INCLUDING ADAPTABLE |
| | DWELLING UNITS. |
| | |
| | 5J) PLEASE PROVIDE FAIR HOUSING COMPLIANCE FOR THE |
| | STEAM ROOMS AND SAUNAS. FAIR HOUSING COMMON USE SPACES |
| | AND FACILITIES. WHEN ANSI DOES NOT CONTAIN |
| | SPECIFICATIONS FOR SPECIFIC FACILITIES OR FEATURE IN |
| | QUESTION RELATED HUMAN FACTORS AND PERFORMANCE |
| | SPECIFICATIONS MUST BE USED TO ACHIEVE ACCESSIBILITY. |
| | SUCH SPECIFICATIONS INCLUDE, BUT ARE NOT LIMITED TO, |
| | 4.2 SPACE ALLOWANCES AND REACH RANGES, 4.3 ACCESSIBLE |
| | ROUTE, 4.4 PROTRUDING OBJECTS, 4.5 GROUND & FLOOR |
| | SURFACES, AND 4.25 OPERATING MECHANISMS. |
| | |
| | 5K) SHEET 014-A0-33 THE LOWER POOL DECK IT APPEARS |
| | THERE IS ONLY ONE RAMP (NOT MARKED, NOR ELEVATION |
| | CHANGES GIVEN) BETWEEN THE POOL DECK AND POOL THERE ARE |
| | 116 OCCUPANTS AND WHAT APPEARS TO BE ONLY ONE |
| | ACCESSIBLE MEANS OF EGRESS. PLEASE SHOW COMPLIANCE |
| | WITH: 2010 FBC-BUILDING CODE 1007.1 ACCESSIBLE MEANS OF |
| | EGRESS. ACCESSIBLE MEANS OF EGRESS SHALL BE PROVIDED IN |
| | ACCORDANCE WITH THE APPLICABLE SECTIONS OF THE FLORIDA |
| | BUILDING CODE, ACCESSIBILITY. |
| | 2010 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF |
| | EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | |
| | 6) SHEETS 015-A0-34 LEVELS 5-10. 11-17 (TIER 1) LEVELS |
| | 18-19 TIER 2. / 083-A2-05 LEVEL 5/ 084-A2-06 LEVELS |
| | 6-9, 11 TIER 1; |
| | 6A) THIS COMMENT IS A COMMON COMMENT FOR ALL DWELLING |
| | UNITS TIER 1 LEVELS 5-9 &11. THE LIFE SAFETY PLAN SHOWS |
| | (2) REQUIRED COMMON PATHS OF TRAVEL BECAUSE THEY ARE |
| | OVER THE 125 FEET REQUIRED BY 2010 FBC-B 1014.3 |
| | EXCEPTION # 4. |
| | |
| | 6A) (1)THE PLANS SHOW THE 1ST COMMON PATH OF TRAVEL |
| | EXITING THROUGH THE FRONT ENTRY DOORS THROUGH AN |
| | ELEVATOR LOBBY, THE LIFE SAFETY PLANS WILL NEED TO |
| | INDICATE IF THE ELEVATOR HOIST WAYS ARE PRESSURIZED TO |
| | ALLOW EXITING THROUGH THE ELEVATOR LOBBY. 2010 FBC-B |
| | 708.14.1 ELEVATOR LOBBIES. |
| | |
| | 6A)(2) THE 2ND ISSUE IS THE COMMON PATH OF TRAVEL |
| | THROUGH THE LAUNDRY/ STORAGE/ UTILITY ROOM. PLEASE SEE |
| | THE 2010 FBC-B SECTION 1014.2.1(4) 4. EGRESS SHALL NOT |
| | PASS THROUGH KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES |
| | USED FOR SIMILAR PURPOSES. NOTE THE EXCEPTION IS ONLY |
| | FOR A KITCHEN AREA SERVING ADJOINING ROOMS CONSTITUTING |
| | PART OF THE SAME DWELLING UNIT OR SLEEPING UNIT. |
| | |
| | 6B) COMMON COMMENT FOR ALL FLOORS. EXITING CAPACITY |
| | ANALYSIS FOR ALL TIERS SHOW A 36 INCH DOORWAY AND THE |
| | EXIT CAPACITY AT 180 OCCUPANTS. THIS WOULD MEAN YOU |
| | HAVE OFFSET HINGES ON THE EXIT DOORS SO THERE IS A FULL |
| | 36 INCHES CLEAR WIDTH FROM THE FACE OF THE DOOR WHEN |
| | OPEN AT 90 DEGREES TO THE OPPOSING LATCH SIDE OF THE |
| | DOOR AND NOT INCLUDING THE DOOR STOP. SEE 2010 FBC-B |
| | 1008.1.1. CLEAR OPENINGS OF DOORWAYS WITH SWINGING |
| | DOORS SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR |
| | AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. THE ACTUAL |
| | ALLOWABLE MAXIMUM OCCUPANT LOAD IS CLOSER TO 167. |
| | |
| | 7) SHEET 016-A0-35 LEVELS 20 & 21 / 090-A2-20 LEVEL 20 |
| | REFERS TO SHEET 089- A2.18 FOR UNITS A & B. SHEET |
| | 090-A2-20 FOR UNIT C. SAME COMMENTS AND ISSUES AS |
| | COMMENTS 6A AND 6B. |
| | |
| | 8) SHEET 017-A0-36 LIFE SAFETY PLANS FOR LEVEL 22 & 23/ |
| | 092-A2-22 & 093-A2-23. SAME COMMENTS AND ISSUES AS |
| | COMMENTS 6A AND 6B. |
| | |
| | 9) SHEET 017-A0-36 LIFE SAFETY PLANS FOR LEVEL 22 & 23/ |
| | SHEET 093-A2-23. ON NEITHER THE LIFE SAFETY PLAN NOR |
| | THE ARCHITECTURAL SHEET ARE THE WALLS FILED IN TO SEE |
| | IF THE TRAVEL DISTANCES SHOWN ARE CORRECT. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. 2010 FBC-B 1014.3 |
| | EXCEPTION # 4. |
| | |
| | 10) SHEET 018-A0-37 LEVELS 24 &25/ SHEET 094-A2-24 |
| | LEVEL 24 & 095-A2-25. |
| | 10A) UNIT PH-24N & PH25N HAS THE SAME ISSUES AS COMMENT |
| | 6A)(1) ELEVATOR LOBBY & 6A)(2) EGRESS THROUGH STORAGE/ |
| | UTILITY CLOSET / LAUNDRY ROOM. |
| | |
| | 10B) UNIT PH-24S &PH-25S ONLY NEEDS THE VERIFICATION OF |
| | 2010 FBC-B 708.14.1 ELEVATOR LOBBY?S AND OR EXCEPTION. |
| | |
| | 11) SHEET 019-A)-38 LEVEL 26 MECHANICAL FLOOR - ROOF / |
| | 096-A2-26 ARCH. MECHANICAL FLOOR |
| | PLAN. A122-A2-76ALEVEL 26 NORTH, 411-M2-26 & 374.S2-26 |
| | STRUCTURAL MECHANICAL ROOF FRAMING PLAN. |
| | |
| | 11A) SHEET 122-A2-76A NONE OF THE ARCHITECTURAL NOR |
| | STRUCTURAL SHEETS, PROVIDE A ROOM & WALL IDENTIFICATION |
| | TAG FOR THE WALL IN THE UPPER RIGHT CORNER OF THE |
| | BUILDING, THE SAME WALL IS ALSO COMMON TO STAIR TOWER |
| | #2 AND FIREMAN?S VESTIBULE 2601. ADDITIONAL INFORMATION |
| | IS REQUIRED BOTH THE FIREMAN?S VESTIBULE (1HR.) AND THE |
| | STAIR SHAFT(2 HR.) ARE FIRE RATED PROTECTED. 3007.4.2 & |
| | 708.4. |
| | |
| | 11B) THIS SAME ROOM IN THE UPPER RIGHT HAND CORNER OF |
| | THE MECHANICAL PENTHOUSE SHOWS MECHANICAL EQUIPMENT |
| | SHEET 411-M2-26 MECHANICAL LEVEL 26. NONE OF THE PLANS |
| | SHOW ACCESS TO THE EQUIPMENT IN THIS ROOM. USE OF ROOM |
| | NOR IS THE ROOM IDENTIFIED ON NEITHER PLANS NOR ACCESS. |
| | 2010 FBC-B 302.1 STRUCTURES OR PORTIONS OF STRUCTURES |
| | SHALL BE CLASSIFIED WITH RESPECT TO OCCUPANCY IN ONE OR |
| | MORE OF THE GROUPS LISTED BELOW. A ROOM OR SPACE THAT |
| | IS INTENDED TO BE OCCUPIED AT DIFFERENT TIMES FOR |
| | DIFFERENT PURPOSES SHALL COMPLY WITH ALL OF THE |
| | REQUIREMENTS THAT ARE APPLICABLE TO EACH OF THE |
| | PURPOSES FOR WHICH THE ROOM OR SPACE WILL BE OCCUPIED. |
| | |
| | 11C) THIS SAME ROOM SHOWS THE WALLS OF THIS ROOM |
| | CONTINUING INTO THE EXTERIOR WALL TO THE CENTERLINE OF |
| | THE SHEER WALL CONSTRUCTION? 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. TYPO. |
| | |
| | 11D) ROOM 2607 IS IDENTIFIED AS AN ELEVATOR STORAGE? IS |
| | THE USE AN ELEVATOR MACHINE ROOM? 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 11E) THE ROOM IN THE UPPER LEFT HAND CORNER OF THE |
| | SHEET IS NOT IDENTIFIED, THE USE NOR IS THE DOOR. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 11F) THE STAIRWELL 1 & 2 BOTH INDICATE HANDRAILS ON |
| | BOTH SIDES OF THE STAIRS, THE PLANS ARE NOT CLEAR AS IF |
| | THERE IS A KNEEWALL OR A GUARDRAIL AT THE LANDING |
| | ADJACENT TO THE STAIRS. FBC-B 1013.1. |
| | |
| | 11G) DOORS ARE MISSING FROM THE DOOR SCHEDULE ON |
| | 331-A8-11 DOORS 2602 & 2604A. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 11H)SHEET 122-A2-76A LEVEL 26 PLEASE NOTE ROOFTOP AND |
| | FLOOR ELEVATION TAGS ARE NOT PROVIDED. |
| | EXTERIOR OF THE BUILDING GRID LINES ARE GIVEN TO THE |
| | HIGH POINTS AND ROOF DRAINS AS TO THE HIGH AND LOW |
| | POINTS AGAIN ELEVATION TAGS WERE NOT PROVIDED. WILL THE |
| | ROOF DECK BE SLOPED OR WILL ROOFTOP INSULATION MAKE UP |
| | THE DIFFERENCE IN HEIGHT, WHAT TYPE OF ROOF TOP |
| | INSULATION WILL BE USED? 107.2.1.3 ADDITIONAL |
| | INFORMATION REQUIRED, PLANS LACKING DETAILS OR SECTIONS |
| | THROUGH TO LOCATE DOCUMENTS WITH THIS INFORMATION. |
| | |
| | 11I) SHEET 171-A5-06 PLEASE NOTE NONE OF THE WALLS NOR |
| | DOORS ARE PROVIDED WITH IDENTIFICATION TAGS, PLANS ARE |
| | INCOMPLETE, 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 11J) SHEET 171-A5-06 AND 096-A2-26 THERE IS A |
| | DISCREPANCY IN THE PLANS, SHEET 096-A2-26 HAS AN |
| | ADDITIONAL DOOR INTO THE ELEVATOR CONTROL ROOM 3, 4 &6. |
| | |
| | 11K) SHEET 171-A5-06, 096-A2-26 & 374-S2-26 NONE OF |
| | THESE SHEETS DEPICT A SECTION THROUGH CORRIDOR 2604 AS |
| | TO IF THIS IS WITHIN THE BUILDING OR ON THE EXTERIOR OF |
| | THE BUILDING. AS OF WHAT MATERIALS IT WILL BE |
| | CONSTRUCTED FROM. THE STRUCTURAL DRAWING 3374-S2-26 |
| | SHOWS A VERTICAL TUBE, THE SIZE, MATERIAL, SPACING NOR |
| | ATTACHMENT DETAILS ARE NOT PROVIDED. INCOMPLETE |
| | PLANS.107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 11M) SHEET 096-A2-26 SHOWS WHAT APPEARS TO BE A |
| | MECHANICAL EQUIPMENT SCREEN. THE STRUCTURAL SHEETS DO |
| | NOT PROVIDE DETAILS OF THIS SYSTEM. PLEASE PROVIDE CODE |
| | COMPLIANCE WITH 2010 FBC-B SECTIONS; |
| | |
| | 1509.6 MECHANICAL EQUIPMENT SCREENS. MECHANICAL |
| | EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF THE MATERIALS |
| | SPECIFIED FOR THE EXTERIOR WALLS IN ACCORDANCE WITH THE |
| | TYPE OF CONSTRUCTION OF THE BUILDING. WHERE THE FIRE |
| | SEPARATION DISTANCE IS GREATER THAN 5 FEET (1524 MM), |
| | MECHANICAL EQUIPMENT SCREENS SHALL NOT BE REQUIRED TO |
| | COMPLY WITH THE FIRE-RESISTANCE RATING REQUIREMENTS. |
| | WIND DESIGN CRITERIA NOT GIVEN. |
| | |
| | 1509.6.1 HEIGHT LIMITATIONS. MECHANICAL EQUIPMENT |
| | SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN HEIGHT |
| | ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST POINT |
| | ON THE MECHANICAL EQUIPMENT SCREEN. |
| | |
| | 11N) SHEET 096-A2-26 THE MECHANICAL EQUIPMENT SCREEN |
| | APPEARS TO HAVE BRACING LEGS, MATERIAL NOT KNOWN, SIZE |
| | OF MATERIAL NOT KNOWN, SPACING NOT GIVEN NOR THE |
| | ATTACHMENT TO NEITHER THE EQUIPMENT SCREEN NOR THE WALL |
| | OR FLOOR ASSEMBLY. PLANS NOT COMPLETE. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 11O) SHEET 096-A2-26 THE MECHANICAL EQUIPMENT SCREEN |
| | BRACING SYSTEM AS DRAWN HAS LEGS THAT GO INTO THE |
| | CORRIDOR 2604 BLOCKING ACCESS, BLOCKING ENTRY TO A |
| | EXTERIOR MECHANICAL ROOM 2603 AND ALSO TO ROOM 2606. |
| | PLEASE CORRECT THESE AREAS. |
| | |
| | 12) SHEET 431-M4-01 MECHANICAL DETAILS, DETAIL 20 |
| | COOLING TOWER VIBRATION ISOLATOR DETAIL TO BE REVIEWED |
| | BY THE STRUCTURAL ENGINEER OF RECORD, AND WITH THEIR |
| | SHOP DRAWING STAMP OF APPROVAL. PLEASE NOTE THE |
| | STRUCTURAL BASE OR SUPPORT WILL NEED TO BE DESIGNED BY |
| | THE STRUCTURAL ENGINEER OR HIS DELEGATE WITH THE |
| | STRUCTURAL ENGINEER?S APPROVAL BEFORE SUBMITTAL TO THE |
| | BUILDING DEPARTMENT FOR REVIEW. |
| | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. |
| | |
| | |
| | 13) SHEET 431-M4-01 MECHANICAL DETAILS EQUIPMENT |
| | SUPPORT CURB DETAIL & THYBAR VIBRATION CURB III DETAIL |
| | FOR OAU-1 & 2. PLEASE PROVIDE THE PRODUCT APPROVALS FOR |
| | CURB DETAILS. TO BE REVIEWED BY THE STRUCTURAL ENGINEER |
| | OF RECORD, AND WITH THEIR SHOP DRAWING STAMP OF |
| | APPROVAL. PLEASE NOTE THE STRUCTURAL ANCHOR TO THE BASE |
| | OR SUPPORT AS WELL AS THE UNIT TO THE CURB FOR MOMENT |
| | OF OVERTURNING, WILL NEED TO BE DESIGNED BY THE |
| | STRUCTURAL ENGINEER OR HIS DELEGATE WITH THE STRUCTURAL |
| | ENGINEER?S APPROVAL BEFORE SUBMITTAL TO THE BUILDING |
| | DEPARTMENT FOR REVIEW. |
| | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 14) SHEET 131-A3-21. |
| | 14A) THROUGH THE CUT SECTION OF THE BUILDING THERE ARE |
| | VARIOUS FLOORS (EXAMPLE ELEV. # 1 LEVELS 23-20, 15-12, |
| | 10 IN THE UPPER PORTION OF THE ELEVATOR LOBBY A RED |
| | OBJECT THAT EITHER IS HANGING FORM THE CEILING OR CLOSE |
| | TO THE CEILING. THIS DEPICTED THROUGHOUT THE SHEET IN |
| | VARIOUS ELEVATOR LOBBY LOBBIES? 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 14B) ELEVATORS 2/4 DO NOT CONTINUE THROUGH TO THE ROOF. |
| | PLEASE PROVIDE WHERE COMPLIANCE WITH SECTIONS OF THE |
| | 2010 FBC-B CAN BE FOUND: |
| | |
| | 14B)(1) 3004.1 VENTS REQUIRED. HOISTWAYS OF ELEVATORS |
| | AND DUMBWAITERS PENETRATING MORE THAN THREE STORIES |
| | SHALL BE PROVIDED WITH A MEANS FOR VENTING SMOKE AND |
| | HOT GASES TO THE OUTER AIR IN CASE OF FIRE. FOR R1 AND |
| | R2 OCCUPANCIES VENTING IS REQUIRED. |
| | |
| | 14B)(2) 3004.2 LOCATION OF VENTS. VENTS SHALL BE |
| | LOCATED AT THE TOP THE HOISTWAY AND SHALL OPEN EITHER |
| | DIRECTLY TO THE OUTER AIR OR THROUGH NONCOMBUSTIBLE |
| | DUCTS TO THE OUTER AIR. NONCOMBUSTIBLE DUCTS SHALL BE |
| | PERMITTED TO PASS THROUGH THE ELEVATOR MACHINE ROOM, |
| | PROVIDED THAT PORTIONS OF THE DUCTS LOCATED OUTSIDE THE |
| | HOISTWAY OR MACHINE ROOM ARE ENCLOSED BY CONSTRUCTION |
| | HAVING NOT LESS THAN THE FIRE-RESISTANCE RATING |
| | REQUIRED FOR THE HOISTWAY. HOLES IN THE MACHINE ROOM |
| | FLOORS FOR THE PASSAGE OF ROPES, CABLES OR OTHER MOVING |
| | ELEVATOR EQUIPMENT SHALL BE LIMITED AS NOT TO PROVIDE |
| | GREATER THAN 2 INCHES (51 MM) OF CLEARANCE ON ALL |
| | SIDES. |
| | |
| | 14)(3) 3004.3 AREA OF VENTS. EXCEPT AS PROVIDED FOR IN |
| | SECTION 3004.3.1, THE AREA OF THE VENTS SHALL NOT BE |
| | LESS THAN 31/2 PERCENT OF THE AREA OF THE HOISTWAY NOR |
| | LESS THAN 3 SQUARE FEET (0.28 M2) FOR EACH ELEVATOR |
| | CAR, AND NOT LESS THAN 31/2 PERCENT NOR LESS THAN 0.5 |
| | SQUARE FEET (0.047 M2) FOR EACH DUMBWAITER CAR IN THE |
| | HOISTWAY, WHICHEVER IS GREATER. OF THE TOTAL REQUIRED |
| | VENT AREA, NOT LESS THAN ONE-THIRD SHALL BE PERMANENTLY |
| | OPEN. CLOSED PORTIONS OF THE REQUIRED VENT AREA SHALL |
| | CONSIST OF OPENINGS GLAZED WITH ANNEALED GLASS NOT |
| | GREATER THAN 1/8 INCH (3.2 MM) IN THICKNESS. |
| | |
| | |
| | 15) SHEET 137-A3-31 DETAILS 1 & 2 & SHEET A0.23 |
| | EXTERIOR SYSTEMS. |
| | |
| | 15A) BOTH INDICATE THE USE OF METAL WALL PANELS, THERE |
| | ARE NO CUT SECTIONS INDICATING MORE INFORMATION ON THE |
| | PANELS. COMPONENTS AND CLADDING FBC-B, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. PLEASE SEE THE 2010 FBC-B |
| | SECTION 1407.3 ARCHITECTURAL TRIM AND EMBELLISHMENTS. |
| | MCM USED AS ARCHITECTURAL TRIM OR EMBELLISHMENTS SHALL |
| | COMPLY WITH SECTIONS 1407.7 THROUGH 1407.14. |
| | 1407.4 STRUCTURAL DESIGN. MCM SYSTEMS SHALL BE DESIGNED |
| | AND CONSTRUCTED TO RESIST WIND LOADS AS REQUIRED BY |
| | CHAPTER 16 FOR COMPONENTS AND CLADDING. |
| | |
| | 1407.5 APPROVAL. RESULTS OF APPROVED TESTS OR AN |
| | ENGINEERING ANALYSIS SHALL BE SUBMITTED TO THE BUILDING |
| | OFFICIAL TO VERIFY COMPLIANCE WITH THE REQUIREMENTS OF |
| | CHAPTER 16 FOR WIND LOADS. 1407.6 WEATHER RESISTANCE. |
| | |
| | 15B) GLASS EXTERIOR HAND/ GUARD RAIL SYSTEMS. PLEASE |
| | PROVIDE COMPLIANCE WITH FBC-B 1607.7.1 & SECTION 2407. |
| | WILL THE BALCONY DEMISING GLASS WALL SECTIONS HAVE |
| | PATTERNS IN THE GLASS OR SANDBLASTED GLASS IN THE |
| | FRAMES? IF SO COMPLIANCE WITH 2404.3 |
| | . 2404.3.3 VERTICAL PATTERNED GLASS. PATTERNED GLASS |
| | SLOPED 15 DEGREES (0.26 RAD) OR LESS FROM VERTICAL IN |
| | WINDOWS, CURTAIN AND WINDOW WALLS, DOORS AND OTHER |
| | EXTERIOR APPLICATIONS SHALL BE DESIGNED TO RESIST THE |
| | WIND LOADS IN SECTION 1609 FOR COMPONENTS AND CLADDING |
| | ACCORDING TO THE FOLLOWING EQUATION: |
| | FGW < 1.0 FGE (EQUATION 24-9) |
| | 2404.3.5 VERTICAL SANDBLASTED GLASS. |
| | SANDBLASTED GLASS SLOPED 15 DEGREES (0.26 RAD) OR LESS |
| | FROM VERTICAL IN WINDOWS, CURTAIN AND WINDOW WALLS, |
| | DOORS, AND OTHER EXTERIOR APPLICATIONS SHALL BE |
| | DESIGNED TO RESIST THE WIND LOADS IN SECTION 1609 FOR |
| | COMPONENTS AND CLADDING ACCORDING TO THE FOLLOWING |
| | EQUATION: |
| | FG< 0.5 FGE (EQUATION 24-12) |
| | |
| | 15C) 137-A3-31 DETAILS 1 & 2 & SHEET A0.23 EXTERIOR |
| | SYSTEMS & 144-A4-01. DETAILS 10 & 11. BOTH THESE |
| | DETAILS SHOW A 1 INCH AIR GAP BETWEEN THE EDGE OF THE |
| | SLAB AND THE METAL SLAB EDGE COVER PLATE. |
| | |
| | |
| | 16) SHEETS 138-A3-32, 108-A2-68A & DETAIL # 2/ |
| | 278-A6-85C BALCONY DEMISING GLASS WALL. THIS WILL MEAN |
| | THE GLASS HAND RAIL SYSTEM IS FULLY SUPPORTED BY THE |
| | VERTICAL FRAMING ELEMENT. THERE IS NO CLEAR DETAIL IN |
| | EITHER THE ARCHITECTURAL SHEETS NOR THE STRUCTURAL |
| | SHEETS AS TO THE ANCHORAGE OF SYSTEM NOR THE SPACING OF |
| | THE HANDRAIL. THERE IS NO COMMENT THESE DETAILS ARE TO |
| | BE SUPPLIED FROM A DELEGATE ENGINEER EITHER. WITH FBC-B |
| | 1607.7.1 & SECTION 2407. |
| | |
| | THE FLOOR PLAN 108-A2-68A DOES SHOW THE USE OF BALCONY |
| | DEMISING GLASS WALL AND DETAIL 2/0278-A6.85C AS WELL AS |
| | THE ELEVATION SHEET 137-A3-31. THE DETAIL 2 ON SHEET |
| | 278-A6-85C APPEAR TO BE FOR INSULATED SPANDREL PANEL |
| | BUT NOT FOR THE GLASSED DEMISING WALL. PLEASE SHOW HOW |
| | CODE COMPLIANCE WILL BE ACHIEVED FOR SECTION 439.2 |
| | SEPARATION WALLS. WALLS SEPARATING DWELLING UNITS IN |
| | THE SAME BUILDING, WALLS SEPARATING SLEEPING UNITS IN |
| | THE SAME BUILDING AND WALLS SEPARATING DWELLING OR |
| | SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO |
| | THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS FIRE |
| | PARTITIONS IN ACCORDANCE WITH SECTION 709. UL U# 419 IS |
| | NOT A GLASS DEMISING WALL. |
| | |
| | 17) SHEET 157-A4-14 DETAIL 11 SHOWS THE INSTALLATION OF |
| | A TERRA COTTA RAIN SCREEN. REFERENCES DETAIL 11/ |
| | 157-A4-14 PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B |
| | SECTIONS: |
| | |
| | 17A) 1403.2 WEATHER PROTECTION. |
| | |
| | 17B) 1403.3 STRUCTURAL. EXTERIOR WALLS, AND THE |
| | ASSOCIATED OPENINGS, SHALL BE DESIGNED AND CONSTRUCTED |
| | TO RESIST SAFELY THE SUPERIMPOSED LOADS REQUIRED BY |
| | CHAPTER 16. |
| | |
| | 17C) 1405.9 TERRA COTTA. ANCHORED TERRA COTTA OR |
| | CERAMIC UNITS NOT LESS THAN 15/8 INCHES (41 MM) THICK |
| | SHALL BE ANCHORED DIRECTLY TO MASONRY, CONCRETE OR STUD |
| | CONSTRUCTION. TIED TERRA COTTA OR CERAMIC VENEER UNITS |
| | SHALL BE NOT LESS THAN 15/8 INCHES (41 MM) THICK WITH |
| | PROJECTING DOVETAIL WEBS ON THE BACK SURFACE SPACED |
| | APPROXIMATELY 8 INCHES (203 MM) O.C. THE FACING SHALL |
| | BE TIED TO THE BACKING WALL WITH CORROSION-RESISTANT |
| | METAL ANCHORS OF NOT LESS THAN NO. 8 GAGE WIRE |
| | INSTALLED AT THE TOP OF EACH PIECE IN HORIZONTAL BED |
| | JOINTS NOT LESS THAN 12 INCHES (305 MM) NOR MORE THAN |
| | 18 INCHES (457 MM) O.C.; THESE ANCHORS SHALL BE SECURED |
| | TO 1/4-INCH (6.4 MM) CORROSION-RESISTANT PENCIL RODS |
| | THAT PASS THROUGH THE VERTICAL ALIGNED LOOP ANCHORS IN |
| | THE BACKING WALL. THE VENEER TIES SHALL HAVE SUFFICIENT |
| | STRENGTH TO SUPPORT THE FULL WEIGHT OF THE VENEER IN |
| | TENSION. THE FACING SHALL BE SET WITH NOT LESS THAN A |
| | 2-INCH (51 MM) SPACE FROM THE BACKING WALL AND THE |
| | SPACE SHALL BE FILLED SOLIDLY WITH PORTLAND CEMENT |
| | GROUT AND PEA GRAVEL. IMMEDIATELY PRIOR TO SETTING, THE |
| | BACKING WALL AND THE FACING SHALL BE DRENCHED WITH |
| | CLEAN WATER AND SHALL BE DISTINCTLY DAMP WHEN THE GROUT |
| | IS POURED. |
| | |
| | 18) SHEETS 160-A4.15 PODIUM METAL FIN, 161-A4.16 PODIUM |
| | METAL FIN, THE DETAIL # 2 ON SHEET 160 INDICATES A HSS |
| | TUBE POST, REFER TO STRUCTURAL SHEETS. THE STRUCTURAL |
| | SHEETS DO NOT PROVIDE DETAILS OF THIS STRUCTURAL TUBE. |
| | 197.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 19) SHEET 162-A4-31 ROOF DETAILS: |
| | 19A) BETWEEN THE DIFFERENT DETAILS THEY SHOW A |
| | DIFFERENCE BETWEEN SPRAY FOAM INSULATION ON THE ROOF |
| | DECK DETAIL 14 TO THE USE OF TAPERED INSULATION BOARD. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | ENGINEERED DRAWINGS FOR THE TAPERED ROOF INSULATION |
| | WILL BE REQUIRED, AND TO BE REVIEWED BY THE ENGINEER OF |
| | RECORD BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT. FL |
| | 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD |
| | THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF |
| | RECORD FOR REVIEW. |
| | |
| | 19B) DETAILS 3 & 4 BOTH SHOW A TILE DECK ABOVE THE |
| | ROOFING SYSTEM. THE ROOFING SYSTEM WELL NEED TO PROVIDE |
| | PRODUCT APPROVALS FOR WIND AS WELL AS ENGINEERING FOR |
| | THE TILE DECK INSTALLATION THEY WILL MEET THE WIND |
| | LOADS FOR THE LOCATION ON THE BUILDING.2010 FBC-B |
| | COMPONENTS AND CLADDING. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |
| | 20) SHEETS 164-A4-41 AND 165-A4-41A CANOPY SYSTEMS |
| | SHEETS ARE CONCEPTUAL DRAWINGS AT BEST, THERE ARE NO |
| | PLANS IN THE STRUCTURAL DOCUMENTS PROVIDES STRUCTURAL |
| | ELEMENTS OR LOADS TO BE RESISTED. THESE LOADS WILL NEED |
| | TO BE KNOWN FOR THE ECCENTRIC LOADING ONTO THE FRAMING |
| | MEMBERS. ONCE THE LOADS ARE KNOWN THEN THE STRUCTURAL |
| | DRAWINGS WILL BE ABLE TO REACT TO THE ECCENTRIC LOADS |
| | BEING PLACED ON THE VARIOUS COLUMNS AND BEAMS. IF THE |
| | CANOPY IS TO BE DESIGNED BY A DELEGATE ENGINEER THEN |
| | COMPLIANCE WITH FL 61G-15-30.006 WILL NEED TO BE MET. |
| | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 21) THIS REVIEW NO PRODUCT APPROVALS WERE SUBMITTED. |
| | THE DESIGNER OF RECORD OR THE CONTRACTOR CAN ELECT TO |
| | SUBMIT THE PRODUCT APPROVALS FOR THE EXTERIOR CLADDING |
| | AS A DEFERRED SUBMITTAL PER: |
| | 2010 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.4.2 DEFERRED SUBMITTALS. FOR THE |
| | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 21A) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. ROOF HATCHES. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, INTAKE AND |
| | EXHAUST FANS ? |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | |
| | 21B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY |
| | DCA RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING |
| | BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 22) THE PLANS WERE SUBMITTED EARLY FOR REVIEW BEFORE |
| | THE FOUNDATION PERMIT WOULD BE ISSUED. THE SUBMITTED |
| | BUILDING PLANS WERE NOT 100% DRAWINGS AND WILL NEED TO |
| | BE RESUBMITTED BEFORE A THROUGH REVIEW CAN BE |
| | COMPLETED. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |