| 2015-12-16 18:01:26 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1. ELECTRICAL SPECIFICATIONS SECTION ON SHEET E0.1 |
| | MISQUOTED FBC-E SECTIONS: FBC-EC405.7.3 VOLTAGE DROP. |
| | FEEDERS & CUSTOMER OWNED SERVICE CONDUCTORS SHALL BE |
| | SIZED FOR A MAXIMUM OF 2% VOLTAGE DROP. BRANCH CIRCUITS |
| | SHALL BE SIZED FOR A MAXIMUM OF 3% VOLTAGE DROP. |
| | 2. TRENCHING FOR FPL CONDUCTORS BETWEEN EXISTING POLE |
| | AND THE PROPOSED FPL TRANSFORMER, IF UNDER THE SCOPE OF |
| | THIS PERMIT, AS WELL AS ALL OTHER UNDERGROUND WIRING |
| | SHALL REMAIN OPEN FOR INSPECTION UNLESS PRIOR |
| | ARRANGEMENTS ARE MADE WITH ELECTRICAL INSPECTOR, OR RUN |
| | VIA DIRECT BORING. SHEET E2.1 |
| | 3. FBC 1006.1 MEANS OF EGRESS ILLUMINATION REQUIRED. |
| | THE MEANS OF EGRESS, INCLUDING THE EXIT DISCHARGE, |
| | SHALL BE ILLUMINATED AT ALL TIMES THE BUILDING SPACE |
| | SERVED BY THE MEANS OF EGRESS ARE OCCUPIED. SHEET E2.1 |
| | 4. THE SERVICE RACK SHALL BE GUARDED AGAINST PHYSICAL |
| | DAMAGE AS INDICATED IN NEC 110.27(B). SHEET E2.1 |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |