Plan Review Notes
Plan Review Notes For Permit 15111010
Permit Number 15111010
Review Stop B
Sequence Number 1
Notes
Date Text
2015-11-25 12:33:08BUILDING PLAN REVIEW
 W. P. B. REVISION: 15101010
 W. P. B. PERMIT: 15050530 UNDER THE 2010 FBC
 ADD: 500 BELVEDERE RD.
 CONT: SOURCE REFRIGERATION
 TEL: (904)612-3627
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV. 25/2015
 ACTION: DENIED
  
 1) STRUCTURAL CALCULATIONS BY CHARLES MOSS FOR HILL
 PHOENIX, JOB PUBLIX 500 BELVEDERE RD. STORE # 1491 ROOF
 TOP MECHANICAL CENTER 9'-6" X 58'-0" X 8'-11". ONLY THE
 FIRST PAGE OF THE DOCUMENT IS SIGNED AND SEALED, NO
 INDEX SHEET LISTING HOW MANY PAGES ARE COVERED BY THE
 COVERSHEET. FLORIDA ADMINISTRATIVE STATUTE
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE
 COVERED UNDER THE COVER SHEET OR INDEX SHEET.
  
 2) THERE IS NO DOCUMENT OF THE MECHANICAL CENTER TO THE
 ROOF TOP CURB. IN THE SUBMITTAL PACKAGE FOR THE 831
 VILLAGE BLVD THERE WAS? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED
  
 3) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (C) PANEL WALLS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES NO REPORTS
 SUBMITTED.
  
 4) NO INFORMATION AS TO THE PREMIER SEVERE WINDSTORM
 RATED FLOOR & FRAME WAS SUBMITTED NOR THE NEED TO
 INSTALL A NEW DOOR THAT MEETS THE WIND PRESSURES AS WAS
 REQUIRED WITH THE UNIT INSTALLED AT 831 VILLAGE. PLEASE
 PROVIDE LITERATURE AS TO WHICH DOOR AND HARDWARE WITH
 ASSOCIATED PRESSURES .
 PLEASE PROVIDE THE TEST REPORT IN COMPLIANCE WITH 2010
 FBC-B 1715.3. I DO NOT SEE WHERE PREMIER DOORS HAS ANY
 PRODUCT LISTED WITH MIAMI-DADE OR FLORIDA WEBSITE. WE
 WILL REVIEW ANY REPORTS FROM A NATIONALLY RECOGNIZED
 AGENCY. WE DO SEE ICC REPORTS OR THE OLDER LEGACY
 REPORTS.
 NOTE PREMIER PRODUCTS HAS REAPPLIED FOR A FLORIDA
 APPROVAL # 17460 IT IS STILL APPLIED FOR PRINT OUT THE
 COVERSHEET CIRCLE THE DOOR TO BE INSTALLED AND PROVIDE
 THE INSTALLATION INSTRUCTIONS.
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 SHOP DRAWING STAMP OF APPROVED.
  
 6) THE BIG ISSUE IS THIS UNIT WAS BUILT OUT OF STATE,
 NOT UNDER ANY STATE APPROVAL SYSTEM WHERE THERE IS A
 3RD PARTY SYSTEM PROVIDING CERTIFICATION THAT THIS UNIT
 COMPLIES WITH THE 2010 FBC FAMILY OF CODES. IF YOU HAVE
 A 3RD PARTY WHO IS INDEPENDENT THAT IS GOING TO CERTIFY
 THE STRUCTURE INCLUDE THIS IN THE NEXT SUBMISSION.
 PLEASE NOTE HWC HAS SENT DOWN A FLORIDA LICENSED
 INSPECTOR TO INSPECT BOTH MECHANICAL UNITS THE 831
 VILLAGE BLVD AND 500 BELVEDERE RD JOB. PLEASE SUBMIT
 THE INSPECTION REPORT FOR CODE COMPLIANCE AS WELL AS
 THE PERSONS FLORIDA INSPECTORS LICENSE (BN) NUMBER.
  
 THERE WERE FIELD CORRECTIONS MADE WHICH WILL REQUIRE
 THE 3RD PARTY CERTIFICATION, AND NOT UNDER THE MODULAR
 BUILDING PROGRAM. HWC IS WELL AWARE OF THE ISSUES AT
 HAND AND WILL NEED TO BE CONTACTED FOR THE ADDITIONAL
 PAPERWORK.
  
 7) A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  