Plan Review Notes
Plan Review Notes For Permit 15110978
Permit Number 15110978
Review Stop E
Sequence Number 1
Notes
Date Text
2016-01-04 14:07:231ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
 PLEASE SHOW MANUFACTURE SPECS ON UNDERGROUND SERVICE
 MODULES ?
 PROVIDE NOTES TO COMPLY WITH FBC E SECTION C405
 ELECTRICAL POWER AND LIGHTING SYSTEMS (MANDATORY)
 IN INDOOR LOCATIONS OTHER THAN DWELLINGS AND
 ASSOCIATED ACCESSORY STRUCTURES, FLUORESCENT LUMINAIRES
 THAT UTILIZE
 DOUBLE-ENDED LAMPS AND CONTAIN BALLAST(S) THAT CAN BE
 SERVICED IN PLACE SHALL HAVE A DISCONNECTING MEANS
 EITHER INTERNAL
 OR EXTERNAL TO EACH LUMINAIRE. FOR EXISTING INSTALLED
 LUMINAIRES
 WITHOUT DISCONNECTING MEANS, AT THE TIME A BALLAST IS
 REPLACED, A DISCONNECTING MEANS SHALL BE INSTALLED. THE
 LINE
 SIDE TERMINALS OF THE DISCONNECTING MEANS SHALL BE
 GUARDED. NEC 410.130 G
 FBC 1006.1 MEANS OF EGRESS ILLUMINATION.
 NEC 700.12 (F) (4)- EMERGENCY LIGHTING SHALL BE FED BY
 LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE
 LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON
 OWN CIRCUIT.
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.