| Plan Review Notes For Permit 15110978 |
| Permit Number |
15110978 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-04 14:07:23 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | MIKE ALBARRAN | | | 561-805-6746 | | | [email protected] | | | | | | PLEASE SHOW MANUFACTURE SPECS ON UNDERGROUND SERVICE | | | MODULES ? | | | PROVIDE NOTES TO COMPLY WITH FBC E SECTION C405 | | | ELECTRICAL POWER AND LIGHTING SYSTEMS (MANDATORY) | | | IN INDOOR LOCATIONS OTHER THAN DWELLINGS AND | | | ASSOCIATED ACCESSORY STRUCTURES, FLUORESCENT LUMINAIRES | | | THAT UTILIZE | | | DOUBLE-ENDED LAMPS AND CONTAIN BALLAST(S) THAT CAN BE | | | SERVICED IN PLACE SHALL HAVE A DISCONNECTING MEANS | | | EITHER INTERNAL | | | OR EXTERNAL TO EACH LUMINAIRE. FOR EXISTING INSTALLED | | | LUMINAIRES | | | WITHOUT DISCONNECTING MEANS, AT THE TIME A BALLAST IS | | | REPLACED, A DISCONNECTING MEANS SHALL BE INSTALLED. THE | | | LINE | | | SIDE TERMINALS OF THE DISCONNECTING MEANS SHALL BE | | | GUARDED. NEC 410.130 G | | | FBC 1006.1 MEANS OF EGRESS ILLUMINATION. | | | NEC 700.12 (F) (4)- EMERGENCY LIGHTING SHALL BE FED BY | | | LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE | | | LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON | | | OWN CIRCUIT. | | | FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE | | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE | | | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON | | | FLOOR PLAN. |
|