| 2016-02-19 08:59:48 | 3RD REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15110977 |
| | 2/19/16 |
| | |
| | 1) THE SUMMARY AC COOLING AND HEATING CALCULATIONS |
| | SUBMITTED BY ARIZADO DESIGN ARE NOT APPROVED- REFER TO |
| | SECTION C403.2.1 EXCEPTION FBC-14 ENERGY CONSERVATION: |
| | THE SUMMARY SHEET MUST BE SIGNED AND SEALED BY A |
| | FLORIDA LICENSED ENGINEER. |
| | 2) ARIZADO DESIGN IS REQUIRED TO PLACE A SIGNATURE AND |
| | SEAL ON ALL PLAN SHEETS WHERE HIS TITLE BLOCK APPEARS, |
| | AND MUST ALSO BE A FLORIDA LICENSED DESIGN PROFESSIONAL |
| | IN ORDER TO DO SO- REFER TO SECTIONS 61G1-16.003, |
| | 61G1-16.004, & 61G15-23.002 FLORIDA ADMINISTRATIVE |
| | CODE. OTHERWISE THE TITLE BLOCK MUST BE REMOVED FROM |
| | THE PLAN SHEETS. |
| | 3) THE PREVIOUSLY REQUESTED TIE-DOWN ENGINEERING FOR |
| | THE ROOF TOP CONDENSERS HAS NOT BEEN PROVIDED- PLEASE |
| | COMPLY. |
| | 4) THE SUBMITTED ENERGY CALCULATIONS ARE INDICTING |
| | RTU'S IN THE COMPLIANCE DATA, HOWEVER THE PLANS ARE |
| | INDICATING SPLIT SYSTEMS- PLEASE CORRECT, AND PLEASE |
| | LIST THE EFFICENCY RATINGS AND COOLING AND HEATING |
| | CAPACITIES OF THE SYSTEMS ON THE AC SCHEDULE ON SHEET |
| | M-2. |
| | 5) M-2: THE AC EQUIPMENT SCHEDULE IS INDICATING AN |
| | EXCESSIVE AMOUNT OF OUTSIDE AIR CFM'S (948) FOR THE |
| | SELECTED 5-TON SYSTEM THAT HAS A CAPACITY OF 2000 CFM'S |
| | OF SUPPLY AIR. PLEASE NOTE THAT THE THE TOTAL OUTSIDE |
| | AIR FOR THESE TYPE OF SYSTEMS PER STANDARD ENGINEERING |
| | PRACTICES IS GENERALLY NO MORE THAN 20% OF THE THE |
| | TOTAL SUPPLY AIR- OTHERWISE TYPICALLY A DEDICATED |
| | OUTSIDE AIR UNIT IS SELECTED, OR AN ERV IS ADDED TO THE |
| | SYSTEMS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |