Plan Review Notes
Plan Review Notes For Permit 15110977
Permit Number 15110977
Review Stop M
Sequence Number 3
Notes
Date Text
2016-02-19 08:59:483RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110977
 2/19/16
  
 1) THE SUMMARY AC COOLING AND HEATING CALCULATIONS
 SUBMITTED BY ARIZADO DESIGN ARE NOT APPROVED- REFER TO
 SECTION C403.2.1 EXCEPTION FBC-14 ENERGY CONSERVATION:
 THE SUMMARY SHEET MUST BE SIGNED AND SEALED BY A
 FLORIDA LICENSED ENGINEER.
 2) ARIZADO DESIGN IS REQUIRED TO PLACE A SIGNATURE AND
 SEAL ON ALL PLAN SHEETS WHERE HIS TITLE BLOCK APPEARS,
 AND MUST ALSO BE A FLORIDA LICENSED DESIGN PROFESSIONAL
 IN ORDER TO DO SO- REFER TO SECTIONS 61G1-16.003,
 61G1-16.004, & 61G15-23.002 FLORIDA ADMINISTRATIVE
 CODE. OTHERWISE THE TITLE BLOCK MUST BE REMOVED FROM
 THE PLAN SHEETS.
 3) THE PREVIOUSLY REQUESTED TIE-DOWN ENGINEERING FOR
 THE ROOF TOP CONDENSERS HAS NOT BEEN PROVIDED- PLEASE
 COMPLY.
 4) THE SUBMITTED ENERGY CALCULATIONS ARE INDICTING
 RTU'S IN THE COMPLIANCE DATA, HOWEVER THE PLANS ARE
 INDICATING SPLIT SYSTEMS- PLEASE CORRECT, AND PLEASE
 LIST THE EFFICENCY RATINGS AND COOLING AND HEATING
 CAPACITIES OF THE SYSTEMS ON THE AC SCHEDULE ON SHEET
 M-2.
 5) M-2: THE AC EQUIPMENT SCHEDULE IS INDICATING AN
 EXCESSIVE AMOUNT OF OUTSIDE AIR CFM'S (948) FOR THE
 SELECTED 5-TON SYSTEM THAT HAS A CAPACITY OF 2000 CFM'S
 OF SUPPLY AIR. PLEASE NOTE THAT THE THE TOTAL OUTSIDE
 AIR FOR THESE TYPE OF SYSTEMS PER STANDARD ENGINEERING
 PRACTICES IS GENERALLY NO MORE THAN 20% OF THE THE
 TOTAL SUPPLY AIR- OTHERWISE TYPICALLY A DEDICATED
 OUTSIDE AIR UNIT IS SELECTED, OR AN ERV IS ADDED TO THE
 SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719