| Plan Review Notes For Permit 15110977 |
| Permit Number |
15110977 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-05 14:37:07 | 2ND MECHANICAL REVIEW | | | PERMIT #15110977 | | | 2/5/16 | | | | | | 1) THE REVISED PLAN INDICATES NEW AC SYSTEMS: A) | | | PROVIDE AC COOLING AND HEATING CALCULATIONS AND WIND | | | LOAD TIE-DIOWN ENGINEERING FOR MOUNTING THE EXTERIOR | | | CONDENSERS EITHER ON EXISTING OR NEW ROOF STANDS. | | | 2) THE REVISED O/A SCHEDULES IS INDICATING 948 CFM'S OF | | | O/A FOR THE DINING ROOM AND 471 CFM'S O/A FOR THE | | | KITCHEN, BUT THE AC SCHEDULE IS INDICATING AHU-1 & 2 | | | WILL ONLY PROVIDE 585 CFM'S O/A AIR. THERE APPEARS TO | | | BE AN ERROR IN SIZING OR CALCULATIONS HERE. | | | 3) IN ACCORDANCE WITH SECTION C403.2.5.1 FBC-14 ENERGY | | | CONSERVATION THE C02 DETECTORS SHALL BE LOCATED IN THE | | | DINING ROOM FOR DEMAND CONTROLLED VENTILATION PURPOSES. | | | . | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|