2016-02-05 14:37:072ND MECHANICAL REVIEW
 PERMIT #15110977
 2/5/16
  
 1) THE REVISED PLAN INDICATES NEW AC SYSTEMS: A)
 PROVIDE AC COOLING AND HEATING CALCULATIONS AND WIND
 LOAD TIE-DIOWN ENGINEERING FOR MOUNTING THE EXTERIOR
 CONDENSERS EITHER ON EXISTING OR NEW ROOF STANDS.
 2) THE REVISED O/A SCHEDULES IS INDICATING 948 CFM'S OF
 O/A FOR THE DINING ROOM AND 471 CFM'S O/A FOR THE
 KITCHEN, BUT THE AC SCHEDULE IS INDICATING AHU-1 & 2
 WILL ONLY PROVIDE 585 CFM'S O/A AIR. THERE APPEARS TO
 BE AN ERROR IN SIZING OR CALCULATIONS HERE.
 3) IN ACCORDANCE WITH SECTION C403.2.5.1 FBC-14 ENERGY
 CONSERVATION THE C02 DETECTORS SHALL BE LOCATED IN THE
 DINING ROOM FOR DEMAND CONTROLLED VENTILATION PURPOSES.
 .
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER