Plan Review Notes
Plan Review Notes For Permit 15110977
Permit Number 15110977
Review Stop P
Sequence Number 1
Notes
Date Text
2015-12-07 14:09:361) SHT. A-5 - DETAILS #1 & #2 - THE HEIGHT OF THE
 ACCESSIBLE WATER CLOSET SHALL BE 17"-19" AFF MEASURED
 TO THE TOP OF THE SEAT PER 2014 FBC-ACCESS. SEC.604.4.
 2) SHT. A-5 - THE TOILET PAPER DISPENSER SHALL BE
 LOCATED 7"-9" IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. 2014 FBC-ACCESS.
 SEC.604.7.
 3) SHT. A-5- DETAILS #1 & #2 - THE GRAB BARS SHALL BE
 MEASURED TO THE TOP OF THE GRIPPING SURFACE PER THE
 2014 FBC-ACCESS. SEC. 609.4.
 4) SHT. M-1-NOTE #5 NOTES THE CONDENSATE TO DISCHARGE
 TO THE SANITARY. CITY ORDINANCE SEC. 90-126 ( B) (5).
 5) SUBMIT MANUF. SPECIFICATIONS/INSTALL MANUAL AND A
 DETAIL ON THE ZURN GREASE TRAP.WPB AMEND. TO FBC
 SEC.107.2.1.
 6) THE WATER FILTER SYSTEM SHALL BE PROTECTED AGAINST
 CONTAMINATION IN ACCORDANCE WITH 2014 FBC- PLUMBING
 SEC.608.3.
 7) THE WATER SUPPLY CONNECTION TO BEVERAGE DISPENSERS,
 COFFEE MACHINES AND NONCARBONATED BEVERAGE DISPENSERS
 SHALL BE PROTECTED AGAINST BACKFLOW BY A BACKFLOW
 PREVENTER CONFORMING TO ASSE 1022 PER 2014 FBC-PLUMBING
 SEC.608.16.1, 608.16.10.
 8) SUBMIT A DETAIL OF THE CO2 FILL BOX. WPB AMEND. TO
 FBC SEC. 107.2.1.
 9) A SAMPLING PORT SHALL BE INSTALLED ON THE EFFFLUENT
 LINE OF THE GREASE TRAP ON THE EXTERIOR OF THE BUILDING
 IN ACCORDANCE WITH CITY OF WPB ENGINEERING STANDARD
 DRAWING GS-7.1. I HAVE PLACED A LINK AT THE END OF THE
 REVIEW COMMENTS.
 10) SHT. P-3 - DOMESTIC WATER RISER SHOWS A 1/2" WATER
 LINE INCREASING TO 3/4" AT THE WATER HEATER. THE
 MINIMUM SIZE WATER SUPPLY TO THE WATER HEATER SHALL BE
 3/4".
 11) SHOW THE PIPE SIZE OF THE NEW CONNECTION OF THE
 WATER MAIN TO THE EXISTING ON THE WATER RISER.WPB
 AMEND. TO FBC SEC. 107.2.1.
 12) SHT.P-3-DETAIL "A" - THE WATER RISER SHOWS A 1/2"
 COLD WATER LINE SUPPLYING 1" LINES TO THE WATER CLOSETS
 IN THE RESTROOMS & SUPPLYING 3/4/" LINES TO OTHER
 FIXTURES. CLARIFY.
 13) THE SANITARY RISER SHOWS 2 FLAT DRY VENTS FOR THE
 GREASE INTERCEPTOR. EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE PER THE 2014 FBC-PLUMBING
 SEC.905.3.
 14) THE SANITARY RISER DIAGRAM SHOWS ALL THE FIXTURES
 AS BEING CONNECTED TO THE HORIZONTAL DRAINS BELOW THE
 SLAB. SHOW THE FIXTURES ON THE SANITARY RISER AS THEY
 WILL BE INSTALLED ( WALL MOUNTED WATER CLOSETS,
 LAVATORIES CONNECTED TO STACKS, ETC.) WPB AMEND. TO FBC
 SEC. 107.3.5.1.3.
 15) CLEANOUTS ARE REQUIRED IN THE BASE OF EACH WASTE OR
 SOIL STACK PER FBC-PLBG. SEC.708.3.4.
 16) SIZE ALL VENTS & SECTIONS OF THE VENT SYSTEM ON THE
 SANITARY RISER. SEE VENT FOR RESTROOMS AND HANDSINK.WPB
 AMEND. TO FBC SEC. 107.2.1.
 17) SIZE ALL SECTIONS OF THE UNDERSLAB PIPING AND THE
 HORIZONTAL DRAIN FOR THE RESTROOMS. WPB AMEND. TO FBC
 SEC. 107.2.1.
 18) SHOW THE 3/4" VENT FOR THE FLOW CONTROL FOR THE
 GREASE TRAP AS NOTED ON SHT. P-1, NOTE #17.
  
 GREASE TRAP DETAIL LINK: HTTP://WPB.ORG/ENGINEERING/WP-
 CONTENT/UPLOADS/SITES/7/2012/05/GS-7-AND-7_1.PDF
  
  
 PLUMBING PLAN REVIEW