Plan Review Notes
Plan Review Notes For Permit 15110977
Permit Number 15110977
Review Stop M
Sequence Number 1
Notes
Date Text
2015-12-03 14:35:011ST REVIEW 2014 MECHANICAL
 PERMIT #15110977
 12/3/15
  
 1) THE WEST PALM BEACH CONSTRUCTION SERVICES DEPARTMENT
 REQUIRES A SEPARATE PERMIT FOR INSTALLATION OF THE
 WALK-IN BOXES AND REFRIGERATION SYSTEMS. PLEASE PLACE A
 NOTE ON THE PLANS ACCORDINGLY TO CLARIFY.
 2) IN ACCORDANCE WITH SECTION 202 FBC-14 EXISTING
 BUILDING CODE, THE PROPOSED PROJECT IS DEFINED AS A
 CHANGE OF OCCUPANCY AND SHALL BE IN COMPLIANCE WITH THE
 FBC-14 ENERGY CONSERVATION CODE. PLEASE SEE SECTIONS
 C101.4.4 AND C101.5.1, AND SUBMIT EITHER ENERGY
 EFIICENCY COMPLIANCE FORM C402-2014 (PRESCRIPTIVE
 COMPLIANCE) OR ENERGY GAUGE FORM 506-2014 (PERFORMANCE
 COMPLIANCE).
 3) SHEET M-1: REVISE KEYED NOTE #5 AND THE PLUMBING
 DRAWINGS TO SHOW CONDENSATE PIPING FROM THE AHU'S
 DISCHARGING TO AN APPROVED DISPOSAL PLACE- PLEASE NOTE
 THAT THE CONDENSATE IS PROHIBITED TO DISCHARGE INTO THE
 CITY SANITARY SEWER PER SECTION 90-126 WPB CODE OF
 ORDINANCES.
 4) M-1: A MOTORIZED OR GRAVITY DAMPER IS REQUIRED FOR
 THE FRESH AIR DUCTS IN COMPLIANCE WITH SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION. PLEASE REVISE
 NOTE #17 ACCORDINGLY.
 5) M-1 CLARIFY HOW AIR IS RETURNED TO AHU-1. THE UNIT
 IS LOCATED ABOVE THE LADIES ROOM CEILING. THE ELEVATION
 DRAWING ON SHEET A-6 INDICATE THE RESTROOM CEILINGS GO
 TO THE BOTTOM OF THE DECK: PLEASE CLARIFY.
 6) M-1: PROVIDE A DETAIL INDICATING HOW THE AIR HANDLER
 WILL BE HUNG FROM THE DECK ABOVE.
 7) M-1: INDICATE HOW THE DUCT SMOKE DETECTORS WILL BE
 SUPERVISED PER SECTION 606.4.1, AND IF THE ACTUATION OF
 A SINGLE DETECTOR WILL SHUT BOTH SYSTEMS DOWN.
 8) M-2: SEE MECHANICAL SECIFICATIONS NOTE G AND
 INDICATE ON THE PLAN THE LOCATIONS OF THE C02 AND
 TEMPERATURE SENSORS. PLEASE ALSO CORRECT THE NOTE
 INDICATING "RTU" TO ACCURATELY INDICATE SPLIT SYSTEM
 AC.
 9) M-2: THE REMARK AT THE BOTTOM OF THE O.S.A
 CALCULATIONS SCHEDULE IS INACCURATE: A) THIS PROJECT
 SHALL BE IN COMPLIANCE WITH THE FBC-14 MECHANICAL-
 REMOVE THE REFERENCE TO THE IMC CODE. B) FOOTNOTE A IS
 NOT APPLICABLE TO DINING ROOM VENTILATION AS SHOWN
 INTABLE 403.3. REVISE THE CALCULATIONS ACCORDINGLY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  