| 2015-12-03 14:35:01 | 1ST REVIEW 2014 MECHANICAL |
| | PERMIT #15110977 |
| | 12/3/15 |
| | |
| | 1) THE WEST PALM BEACH CONSTRUCTION SERVICES DEPARTMENT |
| | REQUIRES A SEPARATE PERMIT FOR INSTALLATION OF THE |
| | WALK-IN BOXES AND REFRIGERATION SYSTEMS. PLEASE PLACE A |
| | NOTE ON THE PLANS ACCORDINGLY TO CLARIFY. |
| | 2) IN ACCORDANCE WITH SECTION 202 FBC-14 EXISTING |
| | BUILDING CODE, THE PROPOSED PROJECT IS DEFINED AS A |
| | CHANGE OF OCCUPANCY AND SHALL BE IN COMPLIANCE WITH THE |
| | FBC-14 ENERGY CONSERVATION CODE. PLEASE SEE SECTIONS |
| | C101.4.4 AND C101.5.1, AND SUBMIT EITHER ENERGY |
| | EFIICENCY COMPLIANCE FORM C402-2014 (PRESCRIPTIVE |
| | COMPLIANCE) OR ENERGY GAUGE FORM 506-2014 (PERFORMANCE |
| | COMPLIANCE). |
| | 3) SHEET M-1: REVISE KEYED NOTE #5 AND THE PLUMBING |
| | DRAWINGS TO SHOW CONDENSATE PIPING FROM THE AHU'S |
| | DISCHARGING TO AN APPROVED DISPOSAL PLACE- PLEASE NOTE |
| | THAT THE CONDENSATE IS PROHIBITED TO DISCHARGE INTO THE |
| | CITY SANITARY SEWER PER SECTION 90-126 WPB CODE OF |
| | ORDINANCES. |
| | 4) M-1: A MOTORIZED OR GRAVITY DAMPER IS REQUIRED FOR |
| | THE FRESH AIR DUCTS IN COMPLIANCE WITH SECTION |
| | C403.2.4.4 FBC-14 ENERGY CONSERVATION. PLEASE REVISE |
| | NOTE #17 ACCORDINGLY. |
| | 5) M-1 CLARIFY HOW AIR IS RETURNED TO AHU-1. THE UNIT |
| | IS LOCATED ABOVE THE LADIES ROOM CEILING. THE ELEVATION |
| | DRAWING ON SHEET A-6 INDICATE THE RESTROOM CEILINGS GO |
| | TO THE BOTTOM OF THE DECK: PLEASE CLARIFY. |
| | 6) M-1: PROVIDE A DETAIL INDICATING HOW THE AIR HANDLER |
| | WILL BE HUNG FROM THE DECK ABOVE. |
| | 7) M-1: INDICATE HOW THE DUCT SMOKE DETECTORS WILL BE |
| | SUPERVISED PER SECTION 606.4.1, AND IF THE ACTUATION OF |
| | A SINGLE DETECTOR WILL SHUT BOTH SYSTEMS DOWN. |
| | 8) M-2: SEE MECHANICAL SECIFICATIONS NOTE G AND |
| | INDICATE ON THE PLAN THE LOCATIONS OF THE C02 AND |
| | TEMPERATURE SENSORS. PLEASE ALSO CORRECT THE NOTE |
| | INDICATING "RTU" TO ACCURATELY INDICATE SPLIT SYSTEM |
| | AC. |
| | 9) M-2: THE REMARK AT THE BOTTOM OF THE O.S.A |
| | CALCULATIONS SCHEDULE IS INACCURATE: A) THIS PROJECT |
| | SHALL BE IN COMPLIANCE WITH THE FBC-14 MECHANICAL- |
| | REMOVE THE REFERENCE TO THE IMC CODE. B) FOOTNOTE A IS |
| | NOT APPLICABLE TO DINING ROOM VENTILATION AS SHOWN |
| | INTABLE 403.3. REVISE THE CALCULATIONS ACCORDINGLY. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |