| 2015-12-28 17:21:18 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1. THE CURRENT APPLICABLE CODES ARE: FLORIDA FIRE |
| | PREVENTION CODE: 2012, NFPA 1: 2012, NFPA 70, (NEC): |
| | 2011, NFPA 72: 2010, NFPA 101: 2012, FBC- 5TH EDITION: |
| | 2014. CORRECT SHEET T1 ACCORDINGLY. |
| | 2. NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL |
| | EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO |
| | REQUIRE SERVICED WHILE ENERGIZED SHALL BE FIELD MARKED |
| | TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS. |
| | 3. THERE IS A CONFLICT BETWEEN THE NOMINAL VOLTAGES |
| | MENTIONED IN EQUIPMENT POWER GUIDE AND THE DEVICE |
| | REQUIREMENTS OF THE GENERAL REQUIREMENTS NOTE G. |
| | 4. ONLY YOUR KEYED NOTE 7 ADDRESSES A TIME CLOCK. FBC-E |
| | HAS MANDATORY SWITCHING REQUIREMENTS FOR COMMERCIAL |
| | LIGHTING. REVISE YOU DRAWINGS TO COMPLY. |
| | 5. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING |
| | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & UNCONDITIONED SPACES. |
| | 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 7. FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS. |
| | A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL |
| | CONNECTED LIGHTING POWER CALCULATED UNDER SECTION |
| | C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER |
| | CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING |
| | POWER DENSITY CHART TO SHOW COMPLIANCE. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |