| 2016-02-05 05:26:16 | 1)THE PLANS SHOW A LINE LENGTH OF 30 FT. OF PE PIPE TO | | | THE BUILDING AND ALSO A LINE LENGTH OF 60 FT. TO THE | | | 500 KW FUTURE GENERATOR WHICH IS CLOSER. CLARIFY. | | | 2) THERE IS A SECTION OF PIPE MISSING FROM THE GAS | | | RISER FROM THE 1 1/2" PE PIPE UP TO THE 5 PSI REGULATOR | | | NEAR THE EXTERIOR OF THE BUILDING. CLARIFY. | | | 3) SHT. P-2 - THERE IS A NOTE ON THE GAS RISER THAT | | | CALLS OUT A 5 PSI TO 14" W.C.REGULATOR BUT NOTHING IS | | | SHOWN. CLARIFY. | | | 4) P-1 - DRAWING NOTE #30 IS NOT SHOWN ON SHT.P-1. | | | CLARIFY.WHAT TYPE OF PIPING IS GOING TO THE 100KW | | | GENERATOR? SHOW ON GAS RISER. | | | 5) SHT. P-1 - NOTE #4 - THE PLUMBING DESIGN DATA TABLE | | | NOTES A MINIMUM OF 1 1/2" GAS LINE TO THE 100KW | | | EMERGENCY GENERATOR BUT THE GAS RIISER AND SHT. P-1 | | | SHOWS 1". CLARIFY. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|