Plan Review Notes
Plan Review Notes For Permit 15110968
Permit Number 15110968
Review Stop G
Sequence Number 2
Notes
Date Text
2016-02-05 05:26:161)THE PLANS SHOW A LINE LENGTH OF 30 FT. OF PE PIPE TO
 THE BUILDING AND ALSO A LINE LENGTH OF 60 FT. TO THE
 500 KW FUTURE GENERATOR WHICH IS CLOSER. CLARIFY.
 2) THERE IS A SECTION OF PIPE MISSING FROM THE GAS
 RISER FROM THE 1 1/2" PE PIPE UP TO THE 5 PSI REGULATOR
 NEAR THE EXTERIOR OF THE BUILDING. CLARIFY.
 3) SHT. P-2 - THERE IS A NOTE ON THE GAS RISER THAT
 CALLS OUT A 5 PSI TO 14" W.C.REGULATOR BUT NOTHING IS
 SHOWN. CLARIFY.
 4) P-1 - DRAWING NOTE #30 IS NOT SHOWN ON SHT.P-1.
 CLARIFY.WHAT TYPE OF PIPING IS GOING TO THE 100KW
 GENERATOR? SHOW ON GAS RISER.
 5) SHT. P-1 - NOTE #4 - THE PLUMBING DESIGN DATA TABLE
 NOTES A MINIMUM OF 1 1/2" GAS LINE TO THE 100KW
 EMERGENCY GENERATOR BUT THE GAS RIISER AND SHT. P-1
 SHOWS 1". CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR