| Plan Review Notes For Permit 15110968 |
| Permit Number |
15110968 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-25 05:39:50 | 1) SHT. P-1 - IF THE LOCATION OF THE METER HAS BEEN | | | CHANGED, SHOW THE NEW DISTANCE FOR THE PE PIPE FROM THE | | | METER TO THE THE FIRST STEP DOWN REGULATOR.ENSURE PIPE | | | SIZE IS ADEQUATE FOR THE LOAD. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 2) SHOW THE TYPE OF PIPE, SIZE, PSI OF THE GAS AND THE | | | LENGTH OF ALL PIPE SECTIONS FOR THE UNDERGROUND PE | | | PIPEFROM THE GAS METER TO THE FIRST STEP DOWN | | | REGULATOR. THIS INFO CAN BE FOUND ON THE ORIGINAL GAS | | | PLAN. | | | 3) SHOW THE BTU LOAD AND SIZE THE GAS LINE FOR THE | | | FUTURE STANDBY GENERATOR. THE BTU LOAD SHALL CORRELATE | | | WITH THE BTU LOAD ON P-1. | | | 4) THE BTU LOAD FOR THE EMERGENCY GENERATOR ON SHT. P-2 | | | SHOWS 860 CFH AND SHT. P-1 SHOWS 1,353 CFH. | | | CLARIFY.ENSURE THE PIPE IS SIZED FOR THE MAXIMUM BTU | | | LOAD BASED ON THE TOTAL DEVELOPED LENGTH FROM THE POINT | | | OF DELIVERY. | | | 5) SIZE ALL PIPE SECTIONS FROM THE GAS METER UP TO | | | WHERE THE GAS PIPING PENETRATES THE EXTERIOR WALL OF | | | THE STRUCTURE. ALSO, SIZE ALL PIPE SECTIONS AND | | | INDICATE TYPE OF PIPE AND PSI OF THE GAS TO THE FUTURE | | | STANDBY GENERATOR. SHOW THE LOCATION OF ALL REGULATORS. | | | 6) SHT. C09 - CLEARLY SHOW THE LOCATION OF THE GAS | | | METER. THE PLAN SHOWS "PROPOSED 1 1/2 POLY GAS | | | SERVICE". THIS IS VAGUE. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|