Plan Review Notes
Plan Review Notes For Permit 15110958
Permit Number 15110958
Review Stop B
Sequence Number 1
Notes
Date Text
2015-12-02 12:32:511) THE SUBMITTTED PROFLEX TEST REPORTS FOR THE SOUND
 TRANSMISSION LOST TEST AND THE IMPACT SOUND
 TRANSMISSION TEST ARE BASED ON OUTDATED STANDARDS PER
 THE FBC. THE EDITION STANDARD FOR THE SOUND
 TRANSMISSION LOST TEST FOR ASTM E 90 IS 2004 AND THE
 EDITION STANDARD FOR THE IMPACT SOUND TRANSMISSION FOR
 ASTM E 492 IS 2009. SUBMIT 2 COPIES OF A TEST REPORT
 BASED ON THE NOTED EDITIONS.WPB AMEND. TO FBC SEC.
 107.2.1.
 2) THE SUBMITTED TEST REPORTS ARE FOR AN 8 INCH SLAB
 WITH A SUSPENDED CEILING. RESEARCH OF CITY RECORDS
 APPEAR TO SHOW THAT THE SLAB THICKNESS FOR THIS
 BUILDING BETWEEN FLOORS IS 6 INCHES WITH NO SUSPENDED
 CEILING.SUBMIT CORRECT TEST REPORTS FOR THIS PRODUCT.
  