| Plan Review Notes For Permit 15110958 |
| Permit Number |
15110958 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-02 12:32:51 | 1) THE SUBMITTTED PROFLEX TEST REPORTS FOR THE SOUND | | | TRANSMISSION LOST TEST AND THE IMPACT SOUND | | | TRANSMISSION TEST ARE BASED ON OUTDATED STANDARDS PER | | | THE FBC. THE EDITION STANDARD FOR THE SOUND | | | TRANSMISSION LOST TEST FOR ASTM E 90 IS 2004 AND THE | | | EDITION STANDARD FOR THE IMPACT SOUND TRANSMISSION FOR | | | ASTM E 492 IS 2009. SUBMIT 2 COPIES OF A TEST REPORT | | | BASED ON THE NOTED EDITIONS.WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 2) THE SUBMITTED TEST REPORTS ARE FOR AN 8 INCH SLAB | | | WITH A SUSPENDED CEILING. RESEARCH OF CITY RECORDS | | | APPEAR TO SHOW THAT THE SLAB THICKNESS FOR THIS | | | BUILDING BETWEEN FLOORS IS 6 INCHES WITH NO SUSPENDED | | | CEILING.SUBMIT CORRECT TEST REPORTS FOR THIS PRODUCT. | | | | | | PLAN REVIEW | | | TIM LARGE | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|