| Plan Review Notes For Permit 15110949 |
| Permit Number |
15110949 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-07 11:10:04 | 1ST REVIEW 2014 MECHANICAL | | | PERMIT #15110949 | | | 12/7/15 | | | | | | 1) EXHAUST HAS BEEN PROVIDED FOR THE ENCLOSED TOILET | | | ROOM, HOWEVER NO EXHAUST IS SHOWN FOR THE REMAINDER OF | | | THE MEN'S ROOM CONTAINING THE URINALS- REFER TO TABLE | | | 403.3 AND PROVIDE A MINIMUM 50 CFM FAN. | | | 2) A DUCT SMOKE DETECTOR IS REQUIRED TO BE INSTALLED IN | | | THE RETURN AIR SYSTEM OF THE RTU- SEE SECTION 606.2.1.= | | | 3) PROVIDE A MEANS OF RETUN AIR FROM THE HALLWAY BACK | | | TO THE RTU- SEE SECTION 601.5. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|