Plan Review Notes
Plan Review Notes For Permit 15110928
Permit Number 15110928
Review Stop M
Sequence Number 2
Notes
Date Text
2015-12-10 07:20:30RESIDENTIAL (R3) ADDITION MECHANICAL REVIEW COMMENTS
 CODE: 2010 FBC.
  
 1- D. SEC. M1401.3 OF 2010 FBC-RESIDENTIAL. ALSO,
 PROVIDE THE EQUIPMENT INFORMATION FROM THE A/C PLAN ON
 THE DESIGN INFORMATION SUBMITTED
 NOTE: ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS ARE TWO DIFFERENT THINGS. THIS HOUSE IS A
 CONTRIBUTING HISTORIC HOUSE. ENERGY CALCULATIONS ARE
 NOT REQUIRED. ENERGY CALCULATIONS SUBMITTED ARE
 INCORRECT. THEY WERE DONE BASED ON THE 2014 FBC. HOUSE
 WAS REVIEWED UNDER THE 2010 FBC. THERE IS NO NEED TO
 SUBMITT THE ENERGY CALCULATIONS, BUT IF SUBMITTING THEM
 THEY NEED TO BE DONE UNDER THE CORRECT CODE VERSION AND
 THEY NEED TO MATCH PLANS.
  
 2- THERE ARE TWO DIFFERENCE A/C PLANS SUBMITTED. AND
 THEY DON'T MATCH. PROVIDE ONLY ONE PLAN (TWO COPIES) TO
 AVOID CONFLICTS. SEC. 107.3.5.3 CITY AMENDMENTS. NOTE:
 A/C PLAN DONE BY RON LAMPI LOOKS MORE COMPLETE.
  
 3- A/C PLAN DRAWN BY RON LAMPI:
 A) TRANSFER DUCT SIZE SHOWN DOESN'T COMPLY WITH THE
 BALANCED RETURN AIR SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL. THE SUPPLY FEEDING THE MASTER BEDROOM
 IS A 12" DUCT. NEED A TRANSFER DUCT SIZE OF 15" MIN. AS
 REQUIRED BY EXCEPTION #1 OF SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL. REVISE AS REQUIRED. ALSO, CLARIFY HOW
 IS A 12" TRANSFER DUCT INSTALLED ON ON A 24X10 AND 30X8
 GRILLES AS SHOWN ON PLAN.
  
 B) IT'S NOT CLEAR HOW THE 3 SUPPLY REGISTERS SHOWN ON
 THE MASTER BEDROOM ARE FED. THERE IS NOT TRANSITION
 WHEN CHANGING SIZE OF DUCT. SEC. 107.2.1 CITY
 AMENDMENTS. AND, HOW IS A 8" DUCT INSTALLED ON A 10X6
 SUPPLY GRILL?. REVISE AS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]