| Plan Review Notes For Permit 15110885 |
| Permit Number |
15110885 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-24 15:58:42 | 1ST REVIEW 2014 MECHANICAL | | | PERMIT #15110885 | | | 11/14/15 | | | | | | 1) REFER TO SECTION 809.2 FBC-14 MECHANICAL: ALTERED | | | EXISTING SYSTEMS. | | | IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL | | | VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR | | | EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER | | | MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR | | | AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION | | | AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF | | | VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY | | | PROCEDURE OF ASHRAE 62. PLEASE PROVIDE THE CALCULATIONS | | | ON THE PLAN, AND SHOW THE REQUIRED AMOUNTS OF O/A CFM'S | | | REQUIRED AND THE AMOUNT BEING PROVIDED. | | | 2) PROVIDE A SCOPE OF WORK OUTLINE ON THE PLAN FOR | | | MECHANICAL WITH CORRESPONDING DRAWINGS AND DETAILS | | | INDICATING ALL NECESSARY ALTERATIONS TO THE EXISTING AC | | | SYSTEMS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|