2015-11-24 15:58:421ST REVIEW 2014 MECHANICAL
 PERMIT #15110885
 11/14/15
  
 1) REFER TO SECTION 809.2 FBC-14 MECHANICAL: ALTERED
 EXISTING SYSTEMS.
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62. PLEASE PROVIDE THE CALCULATIONS
 ON THE PLAN, AND SHOW THE REQUIRED AMOUNTS OF O/A CFM'S
 REQUIRED AND THE AMOUNT BEING PROVIDED.
 2) PROVIDE A SCOPE OF WORK OUTLINE ON THE PLAN FOR
 MECHANICAL WITH CORRESPONDING DRAWINGS AND DETAILS
 INDICATING ALL NECESSARY ALTERATIONS TO THE EXISTING AC
 SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  