Plan Review Notes
Plan Review Notes For Permit 15110885
Permit Number 15110885
Review Stop E
Sequence Number 1
Notes
Date Text
2015-12-10 08:27:361ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE OUTLET
 SHALL BE INSTALLED WITHIN 450 MM (18 IN.) OF THE TOP OF
 A
 SHOW WINDOW FOR EACH 3.7 LINEAR M (12 LINEAR FT) OR
 MAJOR
 FRACTION THEREOF OF SHOW WINDOW AREA MEASURED
 HORIZONTALLY
 AT ITS MAXIMUM WIDTH.
  
 600.5 BRANCH CIRCUITS.
 (A) REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL BUILDING
 AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE OUTLET IN AN
 ACCESSIBLE
 LOCATION AT EACH ENTRANCE TO EACH TENANT SPACE FOR SIGN
 OR
 OUTLINE LIGHTING SYSTEM USE. THE OUTLET(S) SHALL BE
 SUPPLIED
 BY A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT
 SUPPLIES
 NO OTHER LOAD. SERVICE HALLWAYS OR CORRIDORS SHALL NOT
 BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS.
  
 110.16 ARC-FLASH HAZARDWARNING. ELECTRICAL EQUIPMENT,
 SUCH AS SWITCHBOARDS, PANELBOARDS, INDUSTRIAL CONTROL
 PANELS,
 METER SOCKET ENCLOSURES, AND MOTOR CONTROL CENTERS,
 THAT
 ARE IN OTHER THAN DWELLING UNITS, AND ARE LIKELY TO
 REQUIRE
 EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE
 WHILE
 ENERGIZED SHALL BE FIELD MARKED TO WARN QUALIFIED
 PERSONS OF
 POTENTIAL ELECTRIC ARC FLASH HAZARDS. THE MARKING SHALL
 BE
 LOCATED SO AS TO BE CLEARLY VISIBLE TO QUALIFIED
 PERSONS BEFORE
 EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE OF
 THE EQUIPMENT.
  
 408.4 FIELD IDENTIFICATION REQUIRED.
 (A) CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION. EVERY
 CIRCUIT
 AND CIRCUIT MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS
 TO
 ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. THE
 IDENTIFICATION
 SHALL INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT
 TO
 BE DISTINGUISHED FROM ALL OTHERS. SPARE POSITIONS THAT
 CONTAIN
 UNUSED OVERCURRENT DEVICES OR SWITCHES SHALL BE
 DESCRIBED
 ACCORDINGLY. THE IDENTIFICATION SHALL BE INCLUDED IN
 A CIRCUIT DIRECTORY THAT IS LOCATED ON THE FACE OR
 INSIDE OF THE
 PANEL DOOR IN THE CASE OF A PANELBOARD, AND LOCATED AT
 EACH
 SWITCH OR CIRCUIT BREAKER IN A SWITCHBOARD. NO CIRCUIT
 SHALL
 BE DESCRIBED IN A MANNER THAT DEPENDS ON TRANSIENT
 CONDITIONS
 OF OCCUPANCY.
 (B) SOURCE OF SUPPLY. ALL SWITCHBOARDS AND PANELBOARDS
 SUPPLIED BY A FEEDER IN OTHER THAN ONE- OR TWO-FAMILY
 DWELLINGS
 SHALL BE MARKED TO INDICATE THE DEVICE OR EQUIPMENT
 WHERE THE POWER SUPPLY ORIGINATES.
  
  