| Plan Review Notes For Permit 15110883 |
| Permit Number |
15110883 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-12-16 07:36:29 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW FROM THE PREVIOUS | | | REVIEW : | | | | | | 1) SUBMIT TWO COPIES OF A ROOF DIAGRAM FOR THE | | | STRUCTURE THAT INDICATES THE AREAS THAT ARE TO BE | | | RE-ROOFED. FBC 107.2.1 | | | | | | 2) COMMENT HAS BEEN ADDRESSED. | | | | | | 3) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE | | | GAF MODIFIED ROOF SYSTEM FOR THE FLAT ROOF THAT IS | | | SPECIFIED IN THE ENHANCED FASTENING LETTER FROM THE | | | ARCHITECT (NOA NO.14-1030.02) SPECIFY THE SYSTEM TYPE | | | AND THE PAGE NUMBER ON THE LETTER. FBC 107.2.1 | | | | | | 4) THE LETTER FOR THE ENHANCED FASTENING SPECIFIES A | | | ROOF SLOPE OF 4/12. WAS THIS SUPPOSED TO BE 1/4 PER | | | FOOT SLOPE? CARIFY. FBC 107.2.1 | | | | | | 5) ASCE 7 - 0.10 IS NOT CORRECT. THIS SHOULD BE ASCE 7 | | | - 10 OR ASCE 7 - 2010. CORRECT. FBC REFERENCED | | | STANDARDS | | | | | | 6) THE VALUATION OF THE WORK APPEARS TO BE LOW. SUBMIT | | | A COPY OF THE SIGNED CONTRACT TO VERIFY. FBC 109.3 |
|