| Plan Review Notes For Permit 15110848 |
| Permit Number |
15110848 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-20 07:41:57 | 1ST REVIEW: FBC 2014 5TH ED. | | | | | | SUPPLY MORE INFORMATION PER FBC 107 | | | | | | APPARENTLY THE PERMIT RUNNER REQUESTED EXPEDITED REVIEW | | | FOR THE SUBJECT DEMOLITION PERMIT. I CAN APPROVE IT | | | WITH CONDITIONS, BUT IT SEEMS EARLY AS THE INTERIOR | | | DRAWINGS ARE YET TO BE SUBMITTED. THERE SHOULD BE NOTES | | | ADDED TO THE DEMOLITION PLAN TO INDICATE NO EXTERIOR | | | BUILDING ENVELOPE WORK AND TO CLARIFY THE MEP SYSTEMS | | | TO BE REMOVED AND TO ALLOW FOR THE FIRE SAFETY SYSTEMS | | | TO REMAIN IN PLACE. PLEASE LET ME KNOW HOW YOU WISH TO | | | PROCEED. | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. | | | | | | FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | SHOW PROPOSE ALTERATIONS TO MEP & FIRE SAFETY SYSTEMS. | | | | | | NOTE SUB PERMITS FOR ANY MEP & FIRE SAFETY SYSTEM | | | ALTERATIONS ARE REQUIRED | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|