Plan Review Notes
Plan Review Notes For Permit 15110808
Permit Number 15110808
Review Stop M
Sequence Number 3
Notes
Date Text
2016-04-15 08:53:333RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110808
 4/15/16
  
 1) THE AIR SUPPLIED TO THE NEW VEHICLE DELIVERY GARAGE
 FROM RTU'S 3 & 6 CANNOT BE RETURNED TO THE UNITS AND
 RECIRCULATED- SEE TABLE 403.3 (STORAGE OCCUPANCY-
 ENCLOSED PARKING GARAGES) AND FOOTNOTES B AND D.
 2) THE MOTORIZED DAMPERS (MD-1 & MD-2) FOR THE RETURN
 DUCTS FROM THE VEHICLE DELIVERY GARAGE ARE MISLABELED
 O/A DAMPERS.
 3) THE SUBMITTED NOA FOR THE ACME ROOF-MOUNTED EXHAUST
 FAN DOES NOT MATCH THE GREENHECK FAN THAT IS SPECIFIED
 IN THE SCHEDULE ON SHEET M0.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER