| Notes |
| Date |
Text |
| 2016-04-15 08:53:33 | 3RD REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15110808 | | | 4/15/16 | | | | | | 1) THE AIR SUPPLIED TO THE NEW VEHICLE DELIVERY GARAGE | | | FROM RTU'S 3 & 6 CANNOT BE RETURNED TO THE UNITS AND | | | RECIRCULATED- SEE TABLE 403.3 (STORAGE OCCUPANCY- | | | ENCLOSED PARKING GARAGES) AND FOOTNOTES B AND D. | | | 2) THE MOTORIZED DAMPERS (MD-1 & MD-2) FOR THE RETURN | | | DUCTS FROM THE VEHICLE DELIVERY GARAGE ARE MISLABELED | | | O/A DAMPERS. | | | 3) THE SUBMITTED NOA FOR THE ACME ROOF-MOUNTED EXHAUST | | | FAN DOES NOT MATCH THE GREENHECK FAN THAT IS SPECIFIED | | | IN THE SCHEDULE ON SHEET M0.1. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|