| 2016-02-22 15:01:13 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15110808 | | | 2/22/16 | | | | | | 1) THE SUBMITTALS FOR THE CO AND NO2 DETECTORS DO NOT | | | INDICATE A UL LISTING NUMBER FOR THE ELECTRICAL | | | COMPONENTS OF THE DEVICES, ONLY FOR THE PLASTIC | | | ENCLOSURE. PLEASE PROVIDE UL LISTED DEVICES WITH MAKE | | | AND MODEL NUMBERS AND AND THE SENSOR RANGES OF EACH | | | DEVICE. PLEASE NOTE THAT THE FORMER 2010 FBC-10 | | | MECHANICAL REQUIRED THE CO DETECTORS TO ALARM UPON | | | DETECTION OF CO AT 25 PPM. | | | 2) THE PREVIOUSLY REQUESTED WIND LOAD ENGINEERING FOR | | | THE ROOF TOP EXHAUST FANS HAS NOT BEEN PROVIDED: A) | | | NOA'S WITH APPROVAL SIGNATURES FROM THE DESIGN | | | PROFESSIONAL WERE NOT SUBMITTED. B) THE ENGINEERING IS | | | NOT SHOWN ON THE STRUCTURAL DRAWINGS AS INDICATED IN | | | THE RESPONSE NARRATIVE FROM RICHARD TAVARRES P.E. DATED | | | 2/11/16. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|