2016-02-22 15:01:132ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110808
 2/22/16
  
 1) THE SUBMITTALS FOR THE CO AND NO2 DETECTORS DO NOT
 INDICATE A UL LISTING NUMBER FOR THE ELECTRICAL
 COMPONENTS OF THE DEVICES, ONLY FOR THE PLASTIC
 ENCLOSURE. PLEASE PROVIDE UL LISTED DEVICES WITH MAKE
 AND MODEL NUMBERS AND AND THE SENSOR RANGES OF EACH
 DEVICE. PLEASE NOTE THAT THE FORMER 2010 FBC-10
 MECHANICAL REQUIRED THE CO DETECTORS TO ALARM UPON
 DETECTION OF CO AT 25 PPM.
 2) THE PREVIOUSLY REQUESTED WIND LOAD ENGINEERING FOR
 THE ROOF TOP EXHAUST FANS HAS NOT BEEN PROVIDED: A)
 NOA'S WITH APPROVAL SIGNATURES FROM THE DESIGN
 PROFESSIONAL WERE NOT SUBMITTED. B) THE ENGINEERING IS
 NOT SHOWN ON THE STRUCTURAL DRAWINGS AS INDICATED IN
 THE RESPONSE NARRATIVE FROM RICHARD TAVARRES P.E. DATED
 2/11/16.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER