Plan Review Notes
Plan Review Notes For Permit 15110808
Permit Number 15110808
Review Stop B
Sequence Number 1
Notes
Date Text
2015-12-17 10:14:54BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110808
 ADD: 6870 OKEECHOBEE BLVD
 CONT: NORTH AMERICAN AUTO SERVICES
 TEL: 772-418-1384
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: THURS. DEC.17/2015
 ACTION: DENIED
  
 1) SHEET S-1 MENTIONS SLAB ON GRADE COMPACTION, BUT THE
 PLANS DO NOT PROVIDE WHAT THE MINIMUM SAFE BEARING
 VALUE WOULD BE FOR THE ADDITION, NEITHER WAS A SOILS
 REPORT SUBMITTED REVIEWED BY THE ENGINEER OF RECORD.
 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 2) THE STRUCTURAL SHEETS INDICATE THE USE OF STRUCTURAL
 STEEL CONSTRUCTION. THIS BUILDING QUALIFIES FOR A
 RESIDENT INSPECTOR BECAUSE OF EITHER BOLTED STEEL
 CONNECTIONS OR WELDED CONNECTIONS. RESIDENT INSPECTORS
 ARE HIRED THROUGH THE OWNER AND PAID THROUGH THE OWNER.
 UNDER A RESIDENT INSPECTOR THE INSPECTIONS CAN BE
 LIMITED TO THE STRUCTURAL STEEL CONNECTIONS AND WELDED
 CONNECTIONS. FOR MORE INFORMATION PLEASE CALL KEN
 CONRAD AT 561-805-6666. THE CITY WILL SUBMIT FORMS TO
 THE OWNERS REPRESENTATIVE: [email protected]
  
 2A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT.
  
 2B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'.
 2C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
 2D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS (PLANS &
 PRODUCT APPROVALS) ARE REQUIRED
 2E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
 3) THE CONTRACTOR AND OR DESIGNER OF RECORD HAS NOT
 SUPPLIED THE PRODUCT APPROVALS FOR THE REMODEL AND
 ADDITION. THE PRODUCT APPROVALS CAN BE SUBMITTED AT THE
 NEXT REVIEW OR ON WRITTEN REQUEST BE CONSIDERED AS A
 DEFERRED SUBMITTAL.
 3A) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE
 BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 3B) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 INTAKE OR EXHAUST FANS
 (G) PRE-ENGINEERED A/C STANDS
  
  
 3C) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 4) SHEET S-1 THE WIND DESIGN CRITERIA HAVE BEEN
 PROVIDED BUT THE PRESSURES HAVE NOT BEEN PROVIDED FOR
 ZONES 1-5, NOR THE MEAN ROOF HEIGHT FOR THE BUILDING.
 PLEASE PROVIDE COMPLIANCE WITH: 2014 FBC-B 1603.1.4(5)
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
 SEE: TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 5) SHEET A1 SHOWS IN THE ADDITION AREA VEHICLE DELIVERY
 AREA AN ENCLOSED GARAGE. THE PLANS INDICATE A DETAIL 2/
 A12.0. THIS DETAIL IS FOR AN OVERHEAD IMPACT GLASS DOOR
 SYSTEM . PLEASE PROVIDE COMPLIANCE WITH SECTION : 2014
 FBC-B 2405.2 ALLOWABLE GLAZING MATERIALS AND
 LIMITATIONS.
 SLOPED GLAZING SHALL BE ANY OF THE FOLLOWING MATERIALS,
 SUBJECT TO THE LISTED LIMITATIONS.
  
 5. 1. FOR MONOLITHIC GLAZING SYSTEMS, THE GLAZING
 MATERIAL OF THE SINGLE LIGHT OR LAYER SHALL BE
 LAMINATED GLASS WITH A MINIMUM 30-MIL (0.76 MM)
 POLYVINYL BUTYRAL (OR EQUIVALENT) INTERLAYER, WIRED
 GLASS, LIGHT-TRANSMITTING PLASTIC MATERIALS MEETING THE
 REQUIREMENTS OF SECTION 2607, HEAT-STRENGTHENED GLASS
 OR FULLY TEMPERED GLASS.
  
 5.2. FOR MULTIPLE-LAYER GLAZING SYSTEMS, EACH LIGHT OR
 LAYER SHALL CONSIST OF ANY OF THE GLAZING MATERIALS
 SPECIFIED IN ITEM 1 ABOVE.
  
 ANNEALED GLASS IS PERMITTED TO BE USED AS SPECIFIED
 WITHIN EXCEPTIONS 2 AND 3 OF SECTION 2405.3.
  
 6) PLEASE SHOW COMPLIANCE WITH: 2014 FBC-B 406.6.2
 VENTILATION. A MECHANICAL VENTILATION SYSTEM SHALL BE
 PROVIDED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL. SEE MECHANICAL COMMENTS.
  
 7) SHEET THE COVERSHEET INDICATES THERE ARE COMPONENTS
 OF THIS PROJECT TO BE CONSIDERED NEW WORK (ADDITION)
 BUT THERE ARE NO FIRE SPRINKLER PLANS WITHIN THIS
 SUBMITTAL. 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR
 COMMERCIAL BUILDINGS. (5) SCHEMATIC FIRE SPRINKLERS.
  
 8) SHEET A10.0SHOWS 3 AREAS OF CONCERN FOR
 ACCESSIBILITY:
 8A) THE CAF? HAS 2 AREAS IN QUESTION; (1) 226.1
 GENERAL. WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902. IN ADDITION, WHERE WORK
 SURFACES ARE PROVIDED FOR USE BY OTHER THAN EMPLOYEES,
 AT LEAST 5 PERCENT SHALL COMPLY WITH 902.
 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 (2) THE HEIGHT OF COFFEE BAR. 904.5.1 SELF-SERVICE
 SHELVES AND DISPENSING DEVICES. SELF-SERVICE SHELVES
 AND DISPENSING DEVICES FOR TABLEWARE, DISHWARE,
 CONDIMENTS, FOOD AND BEVERAGES SHALL COMPLY WITH 308.
  
 8B) PARTS RETAIL COUNTER / 116. 904.3.2 COUNTER. THE
 COUNTER SURFACE HEIGHT SHALL BE 38 INCHES (965 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. THE TOP OF
 THE COUNTER EDGE PROTECTION SHALL BE 2 INCHES (51 MM)
 MAXIMUM ABOVE THE TOP OF THE COUNTER SURFACE ON THE
 AISLE SIDE OF THE CHECK-OUT COUNTER.
 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
  
 8C) SALES MANAGERS COUNTER 104. . THE COUNTER SURFACE
 HEIGHT SHALL BE 38 INCHES (965 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. THE TOP OF THE COUNTER EDGE
 PROTECTION SHALL BE 2 INCHES (51 MM) MAXIMUM ABOVE THE
 TOP OF THE COUNTER SURFACE ON THE AISLE SIDE OF THE
 CHECK-OUT COUNTER.
 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  