| 2016-02-25 17:07:39 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15110794 | | | 2/25/16 | | | | | | 1) DERM APPROVAL ACCEPTABLE TO BE SUBMITTED PRIOR TO | | | 1ST INSPECTION. | | | 2) COMMENT #6 FROM THE 1ST REVIEW STILL EXISTS. THE | | | EXHAUST DUCT PENETRATING THE COMBUSTIBLE ROOF SURFACE | | | SHOWN ON SHEET M101 MUST BE GUARDED IN ACCORDANCE WITH | | | SECTION 8.3.3 NFPA-37- PROVIDE A METAL VENTILATED | | | THIMBLE NOT LESS THAN 12" IN DIAMETER THAN THE EXHAUST | | | PIPE OR A METAL OR BURNED FIRE CLAY THIMBLE CONSTRUCTED | | | OF BRICKWORK OR OTHER FIREPROOFING MATERIALS PROVIDING | | | NOT LESS THAN 8" OF INSULATION BETWEEN THE THIMBLE AND | | | THE COMBUSTIBLE ROOF PLYWOOD. | | | 3) SHEET M503: THE TWO DETAILS FOR THE ROOF FAN AND THE | | | DUCT PENETRATION APPEAR TO INDICATE A FLAT ROOF | | | SURFACE, HOWEVER THE PLAN IS INDICATING A SLOPED ROOF | | | SURFACE. PLEASE PROVIDE COMPLETE MOUNTING DETAILS FOR | | | SLOPED ROOF INSTALLATIONS INDICATING HOW THE FAN AND | | | DUCT WILL BE ATTACHED TO THE CURBS, AND HOW THE CURBS | | | WILL BE ATTACHED TO THE ROOF. SUBMIT MANUFACTURER'S | | | SPECIFICATIONS AND A CURRENT PRODUCT APPROVAL/AND OR | | | MIAMI-DADE NOA FOR THE ROOF FAN REVIEWED AND APPROVED | | | BY THE EOR. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|