| Plan Review Notes For Permit 15110789 |
| Permit Number |
15110789 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-07 10:28:07 | 1) SHT. P-01 - SUBMIT A SANITARY RISER THAT COMPLIES | | | WITH CHAPTERS 30, 31 & 32 FOR VENTING, TRAP PROTECTION | | | AND WET VENTS. | | | 2) FLAT, DRY VENT ON EXISTING VENT NOT PERMITTED PER | | | 2014 FBCR SEC.3104.3. | | | 3) VANITIY LAVS ARE NOT VENTED.2014 FBCR SEC. P3101.2, | | | P3101.2.1. | | | 4) CLEANOUTS ARE REQUIRED AT THE BASE OF SOIL AND WASTE | | | STACKS PER 2014 FBCR SEC.P3005.2.6. | | | 5) THE "HORIZONTAL WET VENT" IS CONNECTED AT TWO | | | DIFFERENT POINTS ON THE RISER AND I CANNOT INTERPRET | | | WHAT IT IS SUPPOSED TO BE. IT DOES NOT MEET CODE. | | | CLARIFY. | | | 6) A SEPARATE PERMIT AND GAS DRAWINGS & SPECIFICATIONS | | | ARE REQUIRED FOR THE TANKLESS GAS WATER HEATER. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|