Plan Review Notes
Plan Review Notes For Permit 15110783
Permit Number 15110783
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2016-06-07 13:46:09PROVISO:
  
 ALL OF THE BELOW PREVIOUS COMMENTS STILL STAND.
 SEE BELOW.
  
 -AS PREVIOUSLY NOTED.
  
 PER FFPC, FIFTH EDITION
  
 CHAPTER 40 INDUSTRIAL OCCUPANCIES
  
 40.1 GENERAL REQUIREMENTS.
 40.1.1 APPLICATION.
 40.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY
 TO BOTH
 NEW AND EXISTING INDUSTRIAL OCCUPANCIES.
  
 40.2.5 ARRANGEMENT OF MEANS OF EGRESS. MEANS OF EGRESS,
 ARRANGED IN ACCORDANCE WITH SECTION 7.5, SHALL NOT
 EXCEED THAT
 PROVIDED BY TABLE 40.2.5
  
 THE FOLLOWING AREAS LISTED EXCEED MAXIMUM ALLOWABLE
 COMMON PATH OF TRAVLEL.
 - PACKAGING WAREHOUSE ON FLOOR 2
 - REFRIGERATED STORAGE.
 - MIX ROOM.
 - SOUTH COMP ROOM.
 - OFFICE SPACE
  
 I AM THE FIRE INSPECTOR THAT INSPECTED THIS PROPERTY.
 OUR OFFICE IS CURRENTLY WORKING WITH
 THE OWNER'S OF THE BUSINESS. THE CODE REFERENCE BEING
 USED IS APPLIED BY THE PORTIONS
 OF THE MEANS OF EGRESS AS UNSPRINKLERED AS SHOWN IN THE
 TABLE OF THE REFERENCE PROVIDED TO
 YOU PREVIOUSLY. THE OWNER'S ARE WORKING ON WHAT WAS
 AGREED UPON, ONE OF
 WHICH WAS TO HAVE A THIRD PARTY RDP EVALUATE THEIR
 FACILITYTO ENSURE COMPLIANCE WITH THE
 FLORIDA FIRE PREVENTION CODE AND PROVIDE LIFE SAFEY
 DRAWINGS. THIS IS A SEPARATE ISSUE.
 R. LINDOW 4/19/2016
  
  
2016-04-19 17:10:06AS PREVIOUSLY NOTED.
  
 PER FFPC, FIFTH EDITION
  
 CHAPTER 40 INDUSTRIAL OCCUPANCIES
  
 40.1 GENERAL REQUIREMENTS.
 40.1.1 APPLICATION.
 40.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY
 TO BOTH
 NEW AND EXISTING INDUSTRIAL OCCUPANCIES.
  
 40.2.5 ARRANGEMENT OF MEANS OF EGRESS. MEANS OF EGRESS,
 ARRANGED IN ACCORDANCE WITH SECTION 7.5, SHALL NOT
 EXCEED THAT
 PROVIDED BY TABLE 40.2.5
  
 THE FOLLOWING AREAS LISTED EXCEED MAXIMUM ALLOWABLE
 COMMON PATH OF TRAVLEL.
 - PACKAGING WAREHOUSE ON FLOOR 2
 - REFRIGERATED STORAGE.
 - MIX ROOM.
 - SOUTH COMP ROOM.
 - OFFICE SPACE
  
 I AM THE FIRE INSPECTOR THAT INSPECTED THIS PROPERTY.
 OUR OFFICE IS CURRENTLY WORKING WITH
 THE OWNER'S OF THE BUSINESS. THE CODE REFERENCE BEING
 USED IS APPLIED BY THE PORTIONS
 OF THE MEANS OF EGRESS AS UNSPRINKLERED AS SHOWN IN THE
 TABLE OF THE REFERENCE PROVIDED TO
 YOU PREVIOUSLY. THE OWNER'S ARE WORKING ON WHAT WAS
 AGREED UPON, ONE OF
 WHICH WAS TO HAVE A THIRD PARTY RDP EVALUATE THEIR
 FACILITYTO ENSURE COMPLIANCE WITH THE
 FLORIDA FIRE PREVENTION CODE AND PROVIDE LIFE SAFEY
 DRAWINGS. THIS IS A SEPARATE ISSUE.
 R. LINDOW 4/19/2016
  