Plan Review Notes
Plan Review Notes For Permit 15110783
Permit Number 15110783
Review Stop E
Sequence Number 3
Notes
Date Text
2016-05-12 16:07:49REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
 PROVISO: CLARIFY THIS ISSUE ON THE RISER AND PANEL
 SCHEDULE
  
 - NEC 110.15 HIGH-LEG MARKING. ON A 4-WIRE,
 DELTA-CONNECTED SYSTEM WHERE THE MIDPOINT OF ONE PHASE
 WINDING IS GROUNDED, ONLY THE CONDUCTOR OR BUSBAR
 HAVING THE HIGHER PHASE VOLTAGE TO GROUND SHALL BE
 DURABLY AND PERMANENTLY MARKED BY AN OUTER FINISH THAT
 IS ORANGE IN COLOR OR BY OTHER
 EDITION EFFECTIVE MEANS. SUCH IDENTIFICATION SHALL BE
 PLACED AT EACH POINT ON THE SYSTEM WHERE A CONNECTION
 IS MADE IF THE GROUNDED CONDUCTOR IS ALSO PRESENT.
  
 - NEC 408.3(E)(F) PHASE ARRANGEMENT. THE PHASE
 ARRANGEMENT ON 3-PHASE BUSES SHALL BE A, B, C FROM
 FRONT TO BACK, TOP TO BOTTOM, OR LEFT TO RIGHT, AS
 VIEWED FROM THE FRONT OF THE SWITCHBOARD OR PANELBOARD.
 THE B PHASE SHALL BE THAT PHASE HAVING THE HIGHER
 VOLTAGE TO GROUND ON 3-PHASE, 4-WIRE, DELTA-CONNECTED
 SYSTEMS.
 OTHER BUSBAR ARRANGEMENTS SHALL BE PERMITTED FOR
 ADDITIONS TO EXISTING INSTALLATIONS AND SHALL BE
 MARKED. HIGH-LEG IDENTIFICATION. A SWITCHBOARD OR
 PANELBOARD CONTAINING A 4-WIRE, DELTA-CONNECTED SYSTEM
 WHERE THE MIDPOINT OF ONE PHASE WINDING IS GROUNDED
 SHALL BE LEGIBLY AND PERMANENTLY FIELD MARKED AS
 FOLLOWS:
 ?CAUTION _____ PHASE HAS _____ VOLTS TO GROUND?
  
 - RE-CONFIGURE RISER DIAGRAM AND PANEL SCHEDULE
 ACCORDINGLY TO IDENTIFY THIS HAZARD !