| Plan Review Notes For Permit 15110783 |
| Permit Number |
15110783 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-04-05 12:02:33 | ELECTRICAL REVIEW COMMENTS | | | REVIEWED FOR COMPLIANCE WITH: | | | 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011 | | | EDITION | | | | | | CORRECTIONS REQUIRED: | | | 1. ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN | | | SATISFACTORILY ADDRESSED, BUT FBC SECTION 107.1 | | | REQUIRES THAT YOU SUBMIT A MINIMUM OF TWO SETS OF PLANS | | | WITH EACH APPLICATION AND ONLY WAS WAS AVAILABLE AT | | | TIME OF REVIEW. ONE SET WAS SIGNED OUT TO SUPERIOR | | | CONCRETE ON 3/21/16. THIS FILE WILL REMAIN IN FAILED | | | STATUS UNTIL SUCH TIME AS THE REQUIRED SECOND SET OF | | | DRAWINGS IS PROVIDED. | | | 2. ELECTRICAL REVIEW LIMITED ONLY TO THE SILO PORTION | | | OF PROJECT. NO ELECTRIC WAS PROVIDED FOR DUMPSTER AREA. | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | | GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] | | | |
|