| 2015-12-21 19:51:59 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | 1. NEC 230.2 PERMIT A SINGLE SERVICE TO EACH STRUCTURE |
| | AND THE PROPOSED ADDITION APPEARS TO BE ATTACHED TO THE |
| | EXISTING STRUCTURE, THEREFORE THE ELECTRICAL RISER |
| | DIAGRAM AS PROVIDED IS INCORRECT. |
| | 2. NEC 215.5 REQUIRES THAT YOU PROVIDE FEEDER DIAGRAM |
| | WITH PROPER LOAD CALCS FOR THE ADDED LOAD. THIS FEEDER |
| | DIAGRAM SHALL BE SITE SPECIFIC. |
| | 3. NEC 408.4 MARK ON THE FLOOR PLAN THE LOCATION OF THE |
| | ELECTRICAL PANEL. MARK ON THE PANEL THE LOCATION OF THE |
| | DISCONNECT AND POWER SOURCE. HERE IS WHERE YOU SHALL |
| | ALSO PROVIDE A SITE SPECIFIC CIRCUIT DIRECTORY. |
| | 4. FBC-E C405 HAS MANDATORY SWITCHING REQUIREMENTS FOR |
| | EVERY COMMERCIAL INSTALLATION. |
| | 5. YOU SHALL ILLUMINATE THE EXTERIOR STAIRWAYS AS |
| | REQUIRED BY CODE. |
| | 6. YOU SHALL PROVIDE THE REQUIRED EMERGENCY AND EXIT |
| | LIGHTING. |
| | 7. INCLUDE ON THE PLANS ANY ILLUMINATION OR OTHERWISE |
| | REQUIRED OR BEING INSTALLED AS PART OF THE SILOS OR |
| | DUMPSTER ENCLOSURE. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |