| 2016-01-21 13:12:39 | THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN |
| | REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC, |
| | (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1. GENERAL NOTES #12: THE WORDS ?ROMEX? & ?BX? AS USED |
| | IN THIS NOTE IS TO IDENTIFY A TYPE OF CABLE. ROMEX IS A |
| | BRAND NAME AND NOT A CABLE TYPE, REFER TO CABLE TYPES |
| | ?NM?, ?NMC? OR ?NMS? AND CORRECT THE NOTE ACCORDINGLY. |
| | 2. GENERAL NOTES #14 PROHIBIT THE USE OF FUSES. THE |
| | DISCONNECT ON THE EXTERIOR SURFACE OF THE SHELTER SHALL |
| | HAVE A PROPERLY RATED CIRCUIT BREAKER. |
| | 3. CORRECT THE UTILITY SOURCE CONDUCTOR LABELING IN THE |
| | METER DETAIL ON SHEET E4 FOR A REGULAR 120/240 SINGLE |
| | PHASE SERVICE. |
| | 4. PROVIDE LOAD CALCS FOR THE PROPOSED 800 AMP SERVICE. |
| | 5. PROVIDE A CIRCUIT DIRECTORY. |
| | 6. PROVIDE SHELTER DETAILS. IF THE SHELTER IS TO BE A |
| | SELF-CONTAINED PREMANUFACTURERD UNIT, PROVIDE THE |
| | ELECTRICAL SPEC SHEET WITH THE REQUIREMENTS. IF IT IS |
| | TO BE SITE BUILT, SUBMIT A CODE COMPLIANT ELECTRICAL |
| | FLOOR PLAN. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE |
| | NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK |
| | VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |