| 2016-02-12 16:49:45 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT THE REQUESTED ITEMS AFTER |
| | THE PERMIT IS ISSUED. REVISION FEES MAY APPLY. |
| | CONTRACTOR TO ADVICE IF PROVISO OPTION IS OK OR IF |
| | RE-SUBMITTING REQUESTED ITEMS BEFORE ISSUING THE |
| | PERMIT. |
| | |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) HURRICANE SHUTTERS FOR DOORS AND WINDOWS THAT DON'T |
| | HAVE IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE INSTALLATION SCHEDULE CITY SAMPLE. OR |
| | PROVIDE COMPLETE INFORMATION ON ANY OTHER FORMAT THAT |
| | CONTAINS ALL THE REQUIRED INFORMATION. |
| | NOTE: IS NOT CLEAR IF USING IMPACT WINDOWS AND DOORS OR |
| | NON-IMPACT WINDOWS AND DOORS. PRODUCT APPROVALS |
| | SUBMITTED NOW ARE FOR IMPACT WINDOWS AND DOORS. IMPACT |
| | WINDOWS AND DOORS SUBMITTED NOW ARE VINYL. THEY MAY NOT |
| | BE APPROVED BY HISTORIC. ON THE OTHER HAND ARCHITECT |
| | SPECIFIES SHUTTERS FOR HURRICANE PROTECTION ON SHEET |
| | A1. PLEASE COORDINATE ALL THE INFORMATION TO AVOID MORE |
| | CONFUSION AND CONFLICTS. |
| | |
| | B) CLARIFY IF USING THE NON-IMPACT SINGLE HUNG WINDOWS |
| | NOA 15-0528.22 SUBMITTED THE FIRST TIME OR IF ANOTHER |
| | PRODUCT WILL BE USED. THERE WERE ANOTHER PRODUCT |
| | APPROVALS SUBMITTED FOR SLIDING GLASS DOORS AND FIXED |
| | WINDOWS WITH IMPACT GLASS. NOTE: VINYL DOORS AND |
| | WINDOWS MAY NOT BE APPROVED BY HISTORIC. |
| | |
| | C) PRECAST LINTELS AS SPECIFIED ON PLANS (REPEAT |
| | COMMENT). |
| | |
| | D) GABLE END VENT AS SPECIFIED ON WEST ELEVATION ON |
| | SHEET A2 (REPEAT COMMENT). |
| | |
| | E) ALL SIMPSON AND USP STRUCTURAL CONNECTORS SPECIFIED |
| | ON PLANS AND ALL DETAILS. PROVIDE ONLY THE FLORIDA |
| | PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE |
| | SPECIFIED CONNECTOR OR LIST THE FLORIDA PRODUCT |
| | APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR. |
| | NOTE: SOME FLORIDA PRODUCT APPROVALS LISTED ON THE |
| | CONNECTOR SCHEDULE ON SHEET S2 NEED TO BE UPDATED TO |
| | THE 2014 FLORIDA PRODUCT APPROVAL CODE VERSION. (REPEAT |
| | COMMENT). |
| | |
| | F) EXTERIOR SWING DOOR BY THE REAR DECK AS SHOWN ON |
| | PLANS (REPEAT COMMENT). |
| | |
| | G) SLIDING GLASS DOOR AS SHOWN ON PLANS. VINYL DOORS |
| | NOA 15-0409.02 NEEDS HISTORIC APPROVAL. |
| | |
| | H) FIXED WINDOWS. VINYL WINDOWS NOA 15-0415.01 |
| | SUBMITTED NEEDS HISTORIC APPROVAL. |
| | |
| | I) METAL ROOF NOA 11-0810.10 SUBMITTED. CLEARLY |
| | IDENTIFY WHICH APPROVED SYSTEM IS GOING TO BE INSTALLED |
| | TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| | R301. |
| | |
| | 2- ARCHITECT OF RECORD TO APPROVE ALL PRODUCT APPROVALS |
| | AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 3- ENERGY CALCULATIONS SUBMITTED; |
| | A) COMPLETE INFORMATION ON TOP OF FORM, INCLUDING |
| | BUILDER NAME, PERMIT OFFICE AND JURISDICTION #. SEC. |
| | R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). (REPEAT COMMENT). |
| | |
| | B) REVISE THE DESIGN LOCATION SHOWN ON PAGE 2 OF 4. |
| | THIS IS WEST PALM BEACH NOT BELLE GLADE. |
| | |
| | C) REVISE DOORS SPECIFIED ON PAGE 3 OF 5. NEED TO MATCH |
| | PLANS AND PRODUCT APPROVALS SUBMITTED. SIZE SPECIFIED |
| | FOR THE ENTRY DOOR DOESN'T MATCH PLANS. |
| | NOTE: DOORS WITH GLAZING NEED TO BE CONSIDERED ON THE |
| | GLAZING CALCULATIONS NO DOORS. SLIDING GLASS DOORS NEED |
| | TO BE CONSIDERED IN WINDOWS SECTION. SEE SEC. |
| | R405.5.3.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). (REPEAT COMMENT). |
| | |
| | D) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO |
| | MATCH PLANS. SEC. R103.2 OF FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). (REPEAT COMMENT). |
| | |
| | E) TABLE 402.4.1.1 SUBMITTED IS INCOMPLETE. THERE ARE |
| | ITEMS THAT NEED TO BE CHECKED. SEC. R103.2 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT |
| | COMMENT). |
| | |
| | F) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD. SEC. R405.4.3 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). (REPEAT COMMENT). |
| | |
| | IMPORTANT: LABEL FOR WINDOWS AND DOORS SHOWING THE |
| | U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY |
| | CALCULATIONS WILL BE REQUIRED WHEN ENERGY CALCULATIONS |
| | ARE NOT USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING. |
| | |
| | 4- THE ROOF PROJECTION ON THE SOUTH SIDE NEEDS TO |
| | COMPLY WITH THE 1 HOUR ON THE UNDERSIDE FIRE RATING AS |
| | REQUIRED BY TABLE R302.1. (1) OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). PROVIDE COMPLETE DETAIL AND |
| | SPECIFICATIONS FOR THE ROOF PROJECTION ON THE SOUTH |
| | SIDE. |
| | NOTE: KEEP IN MIND THAT VENTS ON THE UNDERSIDE OF THE |
| | ROOF PROJECTIONS DON'T COMPLY WITH THE 1 HR FIRE |
| | RATING. |
| | |
| | RESPONSE: DETAIL 4 ON SHEET A3 DOESN'T COMPLY. NEED 1 |
| | HOUR FIRE RESISTANCE ON THE UNDERSIDE OF THE |
| | PROJECTION. DETAIL SUBMITTED IS FOR A SHAFTWALL. THIS |
| | DOESN'T APPLY TO THE UNDERSIDE OF THE PROJECTION. |
| | PROVIDE COMPLETE SPECIFICATIONS FOR FIRE RATED ASSEMBLY |
| | THAT INCLUDES THE OUTRIGGERS AS SHOWN ON DETAIL 4/A3. |
| | |
| | 5- SHEET A1: ARCHITECT CALLS FOR SHUTTERS FOR HURRICANE |
| | PROTECTION. PRODUCT APPROVALS SUBMITTED ARE IMPACT |
| | GLASS. PLEASE COORDINATE PLANS AND PRODUCT APPROVALS TO |
| | AVOID MORE CONFLICTS AND DELAYS. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 6- ENTRY DOOR ON FLOOR PLAN ON SHEET A1 WAS REVISED. |
| | REVISE FRONT ELEVATION TO MATCH CHANGES. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | 7- ARCHITECT TO SPECIFY METAL ROOF FASTENING AS |
| | REQUIRED BY SEC. 107.2.1.2. SEE NOA 11-0810.10 |
| | SUBMITTED. COORDINATE WITH ITEM #1(I) ABOVE. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD |
| | DRAWINGS TO THE SET OF PLANS RESUBMITTED. SUBMITT OLD |
| | DRAWINGS FOR REFERENCE. |
| | |