| 2015-12-28 14:27:58 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014) |
| | |
| | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS THAT |
| | ARE DONE WITH AN APPROVED HEATING AND COOLING |
| | CALCULATION METHOD AS REQUIRED BY SEC. R403.6.1 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | INFORMATION SUBMITTED IS NOT AN APPROVED METHOD. |
| | |
| | 2- A/C DRAWING TO HAVE THE EQUIPMENT MANUFACTURER'S |
| | NAME AND MODEL NUMBER SHOWING THE SENSIBLE AND AND |
| | TOTAL COOLING CAPACITY AS REQUIRED BY SEC. R403.6.1 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | 3- A/C PLANS SHOWING ON SHEET M.1 DOESN'T COMPLY WITH |
| | THE BALANCED RETURN AIR SEC. M1602.4 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). PROVIDE COMPLETE |
| | INFORMATION FOR THE BALANCED RETURN AIR ON ALL |
| | BEDROOMS. |
| | |
| | 4- PROVIDE ENGINEERING CALCULATIONS SHOWING THAT THE |
| | NUMBER OF CONNECTORS AS SPECIFIED ON THE CONDENSING |
| | UNIT MOUNTING DETAIL ARE ADEQUATE TO RESIST THE WIND |
| | LOADS OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). CHECK CONNECTIONS TO THE CONCRETE SLAB AND TO |
| | THE CONDENSING UNIT. ALSO, SPECIFY HOW LONG ARE THE |
| | 3/8" BOLTS AND ANCHORS SPECIFIED. |
| | |
| | 5- VERTICAL A/C UNIT DETAIL SHOWN ON SHEET M.1 DOESN'T |
| | MATCH PROPOSED INSTALLATION. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD |
| | DRAWINGS TO THE SET OF PLANS RESUBMITTED. SUBMITT OLD |
| | DRAWINGS FOR REFERENCE. |
| | |