| Plan Review Notes For Permit 15110777 |
| Permit Number |
15110777 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-04 11:46:05 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | MIKE ALBARRAN | | | 561-805-6746 | | | [email protected] | | | | | | | | | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 | | | FEET OF EACH SLEEPING ROOM. PLEASE SHOW ON FLOOR PLANS. | | | R404.1 LIGHTING EQUIPMENT (MANDATORY). MUST BE IC RATED | | | AND SEALED TYPE RECCESSED FIXTURES. | | | A MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY | | | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY | | | LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY | | | INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH | | | EFFICACY LAMPS. | | | SHOW NEC 2011 ON STANDARDS INSTEAD OF 2008 . BOXES AT | | | CEILING-SUSPENDED (PADDLE) FAN OUTLETS. | | | OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE | | | SUPPORT | | | OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE LISTED, | | | SHALL BE | | | MARKED BY THEIR MANUFACTURER AS SUITABLE FOR THIS | | | PURPOSE, | | | AND SHALL NOT SUPPORT CEILING-SUSPENDED (PADDLE) FANS | | | THAT | | | WEIGH MORE THAN 32 KG (70 LB). FOR OUTLET BOXES OR | | | OUTLET BOX | | | SYSTEMS DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE) | | | FANS | | | THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED | | | MARKING SHALL | | | INCLUDE THE MAXIMUM WEIGHT TO BE SUPPORTED. NEC 314.28 | | | C |
|