| Plan Review Notes For Permit 15110722 |
| Permit Number |
15110722 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-01-22 06:39:09 | 1) SUBMIT A REVISED WATER RISER FOR REVIEW. WPB AMEND. | | | TO FBC SEC. 107.3.5.1.3. 2ND REQUEST. | | | 2) SIZE ALL SECTIONS OF THE SANITARY SYTEM BELOW THE | | | SLAB. WPB AMEND. TO FBC SEC. 107.3.5.1.3. | | | 3) IDENTIFY ALL PLUMBING FIXTURES ON THE RISER. WATER | | | CLOSETS HAVE INTEGRAL TRAPS. | | | 4) FLAT, DRY VENTS ARE NOT PERMITTED PER 2014 | | | FBC-PLUMBING SEC.905.3. | | | 5) THE SANITARY RISER SHOWS A DRAIN LINE THAT CONNECTS | | | TO NOTHING. CLARIFY. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|