| Plan Review Notes For Permit 15110722 |
| Permit Number |
15110722 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-12-01 06:47:15 | COMMENTS FROM THE PREVIOUS PLUMBING REVIEW HAVE NOT | | | BEEN ADDRESSED. | | | 1) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE | | | RE-LOCATION OF THE RESTROOMS. WPB AMEND. TO FBC SEC. | | | 107.3.5.1.3. 2ND REQUEST. | | | 2) THE MINIMUM INSIDE CLEAR WIDTH OF THE ACCESSIBLE | | | TOILET ROOM SHALL BE 85 INCHES IF BUILT PERFECT. 86 | | | INCHES ALLOWS FOR TOLERANCE. THE PLAN SHOWS A MINIMUM | | | INSIDE CLEAR WIDTH OF 84 INCHES WHICH IS NON-COMPLIANT. | | | 2ND REQUEST. | | | 3) THE WATER CLOSET SHALL BE LOCATED 16"-18" FROM AN | | | ADJACENT WALL, NOT 18" MINIMUM AS IS SHOWN ON THE PLAN | | | VIEW DETAIL IN THE ADA REQS.ON THE PLAN. 2010 | | | FBC-ACCESS. SEC.604.2. | | | 4) THE PLANS NEED TO BE CORRECTED. | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|