Plan Review Notes
Plan Review Notes For Permit 15110722
Permit Number 15110722
Review Stop P
Sequence Number 2
Notes
Date Text
2015-12-01 06:47:15COMMENTS FROM THE PREVIOUS PLUMBING REVIEW HAVE NOT
 BEEN ADDRESSED.
 1) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE
 RE-LOCATION OF THE RESTROOMS. WPB AMEND. TO FBC SEC.
 107.3.5.1.3. 2ND REQUEST.
 2) THE MINIMUM INSIDE CLEAR WIDTH OF THE ACCESSIBLE
 TOILET ROOM SHALL BE 85 INCHES IF BUILT PERFECT. 86
 INCHES ALLOWS FOR TOLERANCE. THE PLAN SHOWS A MINIMUM
 INSIDE CLEAR WIDTH OF 84 INCHES WHICH IS NON-COMPLIANT.
 2ND REQUEST.
 3) THE WATER CLOSET SHALL BE LOCATED 16"-18" FROM AN
 ADJACENT WALL, NOT 18" MINIMUM AS IS SHOWN ON THE PLAN
 VIEW DETAIL IN THE ADA REQS.ON THE PLAN. 2010
 FBC-ACCESS. SEC.604.2.
 4) THE PLANS NEED TO BE CORRECTED.
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  