| 2015-12-07 11:44:28 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 15110722 |
| | W. P. B. PERMIT: 15040016 |
| | ADD: 701 N. ROSEMARY AVE. |
| | CONT: ADVANCED CONSTRUCTION |
| | TEL: (561)262-6037 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. DEC. 07/2015 |
| | ACTION: DENIED |
| | |
| | NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA |
| | STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A |
| | FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE |
| | REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO |
| | CORRECT A CODE VIOLATION. |
| | |
| | 1) SHEET AD 201 SHOWS THE ACCESSIBLE RESTROOM BEING |
| | RELOCATED AND A REDUCTION IN LENGTH OF THE RESTROOM |
| | FROM 7'-9 3/4 " TO JUST 7'-0" CLEAR INSIDE DIMENSIONS. |
| | FAILURE TO COMPLY WITH 2010 FBC-ACCESSIBLITY CODE |
| | 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE |
| | 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM |
| | THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. ALSO SEE 604.2 FIGURE |
| | (A). |
| | |