| Plan Review Notes For Permit 15110722 |
| Permit Number |
15110722 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-20 12:12:48 | 1) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE | | | RE-LOCATION OF THE RESTROOMS. WPB AMEND. TO FBC SEC. | | | 107.3.5.1.3. | | | 2) THE MINIMUM INSIDE CLEAR WIDTH OF THE ACCESSIBLE | | | TOILET ROOM SHALL BE 85 INCHES IF BUILT PERFECT. 86 | | | INCHES ALLOWS FOR TOLERANCE. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|