| Date |
Text |
| 2016-02-03 10:06:03 | 1) SHT. A-1 - THE NOTES STATE THAT THE TOILET ROOMS |
| | SHALL COMPLY WITH FBC SEC. 1210 BUT THE FINISH SCHEDULE |
| | SHOWS THE WALLS IN THE TOILET ROOMS TO BE PAINTEED. THE |
| | TOILET ROOMS SHALL COMPLY WITH 2014 FBC SEC. 1210.2.2. |
| | 2) SHOW THE CLEAR FLOOR SPACE FOR THE WATER CLOSET IN |
| | THE MEN'S RESTROOM. IT APPEARS THAT THE URINAL MAY |
| | ENCROACCH INTO THE CLEAR FLOOR SPACE FOR THE WATER |
| | CLOSET AND THE WATER CLOSET ENCOACH INTO THE CLEAR |
| | FLOOR SPACE FOR THE URINAL. NO OTHER FIXTURES OR |
| | OBSTRUCTIONS SHALL BE LOCATED WITHIN THE REQUIRED WATER |
| | CLOSET CLEARANCE.2014 FBC-ACCESS. SEC.604.3.2. |
| | 3) SUBMIT THE OCCUPANCY TYPE AND OCCUPANT LOAD OF THE |
| | SWIMMING POOL, THE POOL DECK, THE TOT LOT AND THE |
| | CABANA PER THE 2014 FBC SEC.303 AND TABLE 1004.1.2. |
| | 4) THE MINIMUM REQUIRED SANITARY FACILITIES SHALL BE |
| | BASED UPON THE SQUARE FOOTAGE OF THE SWIMMING POOL IN |
| | ACCORDANCE WITH THE 2014 FBC-PLUMBING SEC. 403.6. |
| | SUBMIT THE SQUARE FOOTAGE OF THE SWIMMING POOL. |
| | 5) THE DRINKING FOUNTAINS SHALL COMPLY WITH 2014 FBC- |
| | ACCESS. SEC.307.2 FOR PROTRUDING OBJECTS. THE HIGH SIDE |
| | DRINKING FOUNTAIN MAY REQUIRE A SKIRT TO HAVE THE |
| | LEADING EDGE BELOW 27 INCHES. |
| | 6) PROVIDE A KEY LEGEND FOR THE KEY NOTES ON SHEETS P-1 |
| | & P-2 . |
| | 7) HOT OR TEMPERED WATER SHALL BE SUPPLIED TO THE |
| | LAVATORIES PER THE 2014 FBC-PLUMBING SEC.607.1. |
| | 8) A SERVICE SINK MAY BE REQUIRED DEPENDING ON THE |
| | OCCUPANCY PER 2014 FBC-PLUMBING TABLE 403.1. IF ONE IS |
| | REQUIRED, HOT WATER WILL BE REQUIRED TO THE FIXTURE PER |
| | 2014 FBC-PLUMBING SEC.607.1. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |