| 2016-02-17 07:11:42 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2008 NEC | | | COMMENTS: | | | | | | 1. PROVIDE A NOTE TO COMPLY WITH FBC EC 405.7.3, | | | 405.7.4 SEE VERBIAGE IN THE CODE AND UPDATE ALL CODE | | | REFERENCES TO NEC 2011. A NOTE WILL SUFFICE. | | | 2. ADD A NOTE TO INDICATE REQUIREMENTS OF NEC 700.12A | | | FOR THE EM FIXTURES AND THAT THEY BE AHEAD OF ANY | | | SWITCHING MECHANISM. | | | 3. LABEL POOL PUMP IN PANEL SCHEDULE TO BE GFCI | | | PROTECTED. FBC 107 NEC 680.21C | | | 4. PLEASE PROVIDE AN INTERSYSTEM BONDING TERMINATION AT | | | THE SERVICE ONE-LINE. NEC 250.94 | | | 5. FEEL FREE TO CONTACT ME DIRECTLY SHOULD YOU HAVE ANY | | | QUESTIONS OR CONCERNS. | | | | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|