| 2016-01-23 09:20:01 | 1) SHOW TYPE OF PIPING MATERIAL BEING INSTALLED. THERE |
| | ARE TWO TABLES REFERENCED BUT ONLY ONE TYPE OF PIPE IS |
| | SHOWN ON THE RISER. IF PE PIPE IS BEING INSTALLED IT |
| | CAN ONLY BE USED OUTSIDE UNDERGROUND. WPB AMENDMENTS TO |
| | FBC SEC. 107.2.1. |
| | 2) INDICATE THE PSI OF THE SYSTEM. WPB AMENDMENTS TO |
| | FBC SEC. 107.2.1. |
| | 3) SHOW THE LOCATION OF ALL STEP DOWN REGULATORS ON THE |
| | SYSTEM IF APPLICABLE. |
| | 4.) TABLE 402.2 (20) IS REFERENCED ON THE PLANS. THERE |
| | IS NO SUCH TABLE IN THE GAS CODE.CLARIFY. |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL |
| | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2, AND |
| | 301.3. GAS APPLIANCES SHALL BE LISTED AND LABELED PER |
| | SEC.301.3. 2014 FBC-RES. SEC.G2404.3. |
| | 6) SIZE ALL SECTIONS OF THE GAS RISER DIAGRAM. WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. |
| | 7) THE GAS RISER REFERS TO 170 FT. BEING USED FOR |
| | SIZING. THERE IS NO 170 FT.ROW. 175 FT. SHALL BE USED. |
| | 8) IF THIS SYSTEM IS GOING TO BE ENTIRELY OF GALVANIZED |
| | PIPE IT IS UNDERSIZED. REFER TO 2014 FBCFG, TABLE |
| | 402.4(2), NOT 402.4.2 (2) AS REFERENCED ON THE PLANS. |
| | 9) SHT. P102 - THE TANKLESSS WATER HEATER SYSTEM SHOWS |
| | TWO TANKLESS WATER HEATERS AND THE GAS RISER ONLY SHOWS |
| | ONE.CLARIFY.THIS WILL ALSO AFFECT THE SYSTEM BTU LOAD |
| | AND THE PIPE SIZING. |
| | |
| | A SEPARATE IS REQUIRED FOR THE GAS. |
| | |