| Plan Review Notes For Permit 15110708 |
| Permit Number |
15110708 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-24 05:34:27 | 1) ROOM # 118 - LAUNDRY ROOM - SANITARY RISER DIAGRAM | | | SHOWS A LAUNDRY SINK DISCHARGING INTO A VERTICAL WET | | | VENT. ONLY FIXTURES WITHIN A BATHROOM GROUP SHALL | | | DISCHARGE INTO A WET VENT. 2014 FBCP SEC.912.1.1. A | | | SEPARATE BRANCH DRAIN & VENT IS REQUIRED FOR THE | | | LAUNDRY SINK. | | | 2) SIZE THE VENT FOR THE LAVATORY IN THE CABANA BATH. | | | 3) THE SANITARY RISER SHOWS A FLAT, DRY VENT AT THE 3" | | | STACK TO THE SECOND FLOOR. EVERY DRY VENT CONNECTING TO | | | A HORIZONTAL DRAIN SHALL CONNECT THE CENTERLINE OF THE | | | HORIZONTAL DRAIN PIPE. 2014 FBCP SEC. 905.3. | | | 4) CLEANOUTS ARE REQUIRED IN THE BASE OF THE 3" WASTE | | | STACKS TO THE 2ND FLOOR. 2014 FBCR SEC.708.3.4. | | | 5) THE LAVATORY IN THE GUEST BATH ON THE 2ND FLOOR | | | (#212) REQUIRES A VENT. 2014 FBCP SEC.901.2, 901.2.1. | | | 6) SIZE THE VENT FOR THE WATER CLOSET IN THE GUEST BATH | | | ON THE SECOND FLOOR ( #212). | | | 7) THE TUB AND SHOWER IN THE MASTER BATH (#206) ARE NOT | | | VENTED.2014 FBCR SEC. 901.2, 901.2.1. | | | 8) SHT. A 302 - PROVIDE THE DEPTH AND WIDTH DIMENSIONS | | | FOR THE INTEGRAL DRAIN AND THE SQUARE FOOT AREA | | | DRAINED.WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|