Plan Review Notes
Plan Review Notes For Permit 15110708
Permit Number 15110708
Review Stop P
Sequence Number 1
Notes
Date Text
2015-11-24 05:34:271) ROOM # 118 - LAUNDRY ROOM - SANITARY RISER DIAGRAM
 SHOWS A LAUNDRY SINK DISCHARGING INTO A VERTICAL WET
 VENT. ONLY FIXTURES WITHIN A BATHROOM GROUP SHALL
 DISCHARGE INTO A WET VENT. 2014 FBCP SEC.912.1.1. A
 SEPARATE BRANCH DRAIN & VENT IS REQUIRED FOR THE
 LAUNDRY SINK.
 2) SIZE THE VENT FOR THE LAVATORY IN THE CABANA BATH.
 3) THE SANITARY RISER SHOWS A FLAT, DRY VENT AT THE 3"
 STACK TO THE SECOND FLOOR. EVERY DRY VENT CONNECTING TO
 A HORIZONTAL DRAIN SHALL CONNECT THE CENTERLINE OF THE
 HORIZONTAL DRAIN PIPE. 2014 FBCP SEC. 905.3.
 4) CLEANOUTS ARE REQUIRED IN THE BASE OF THE 3" WASTE
 STACKS TO THE 2ND FLOOR. 2014 FBCR SEC.708.3.4.
 5) THE LAVATORY IN THE GUEST BATH ON THE 2ND FLOOR
 (#212) REQUIRES A VENT. 2014 FBCP SEC.901.2, 901.2.1.
 6) SIZE THE VENT FOR THE WATER CLOSET IN THE GUEST BATH
 ON THE SECOND FLOOR ( #212).
 7) THE TUB AND SHOWER IN THE MASTER BATH (#206) ARE NOT
 VENTED.2014 FBCR SEC. 901.2, 901.2.1.
 8) SHT. A 302 - PROVIDE THE DEPTH AND WIDTH DIMENSIONS
 FOR THE INTEGRAL DRAIN AND THE SQUARE FOOT AREA
 DRAINED.WPB AMEND. TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR