Plan Review Notes
Plan Review Notes For Permit 15110708
Permit Number 15110708
Review Stop NFIP
Sequence Number 1
Notes
Date Text
2015-12-23 15:40:51CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 BUILDING IS LOCATED IN FLOOD ZONE A5. PROVIDE ELEVATION
 CERTIFICATE.
 PROVIDE DESIGN AND PRODUCT APPROVALS FOR FLOOD OPENINGS
 IN GARAGE PER FEMA TECHNICAL BULLETIN #1 (OPENINGS IN
 FOUNDATION WALLS AND WALLS OF ENCLOSURES).
  
 107.2.5.1 DESIGN FLOOD ELEVATIONS. WHERE DESIGN FLOOD
 ELEVATIONS ARE NOT SPECIFIED, THEY SHALL BE ESTABLISHED
 IN ACCORDANCE WITH SECTION 1612.3.1.
  
 1612.4 DESIGN AND CONSTRUCTION.
 THE DESIGN AND CONSTRUCTION OF BUILDINGS AND STRUCTURES
 LOCATED IN FLOOD HAZARD AREAS, INCLUDING COASTAL HIGH
 HAZARD AREAS, SHALL BE IN ACCORDANCE WITH CHAPTER 5 OF
 ASCE 7 AND WITH ASCE 24.
  