| Plan Review Notes For Permit 15110707 |
| Permit Number |
15110707 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-02 14:02:58 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. RESIDENT INSPECTOR INFORMATION RECEIVED; CONTRACTOR | | | RESUME IS REQUIRED. | | | | | | 2. IMPACT FEES ARE TO BE PAID TO PALM BEACH COUNTY, | | | 561-233-5025. THIS MAY BE DONE AFTER ALL REVIEWS ARE | | | COMPLETE, PRIOR TO PERMIT ISSUANCE. | | | | | | 3. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING | | | PROVISO: | | | | | | ***PROVISOS*** | | | | | | 1. PRODUCT APPROVALS, REVIEWED BY DESIGNER OF RECORD, | | | ARE TO BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION. | | | DESIGN PRESSURES ARE TO COMPLY ON THE DESIGN PRESSURES | | | SPECIFIED BY THE ENGINEER ON SHEET S02. | | | | | | 2. A SEPARATE ROOF PERMIT APPLICATION IS REQUIRED. NO | | | PRODUCT APPROVALS HAVE BEEN SUBMITTED AT THIS TIME. | | | | | | AT TIME OF ROOF SUB PERMIT APPLICATION, PRODUCT | | | APPROVALS REVIEWED BY DESIGNER OF RECORD ARE REQUIRED. | | | THE PROPOSED ASSEMBLY SHOULD BE INDICATED AND, IF | | | ENHANCED FASTENING IS REQUIRED AND THE PRODUCT APPROVAL | | | REQUIRES THAT THE CALCULATIONS BE DONE BY A DESIGN | | | PROFESSIONAL, ENGINEERING CALCULATIONS ARE TO BE | | | PROVIDED AT TIME OF ROOF SUB PERMIT SUBMITTAL. | | | | | | THE ROOF ASSEMBLY IS TO MEET THE MINIMUM DESIGN | | | PRESSURES SPECIFIED BY THE ENGINEER OF RECORD ON SHEET | | | S02: | | | | | | ZONE 1 -44.99 | | | ZONE 2 -75.34 | | | ZONE 3 -113.39 | | | | | | 3. GMA TO APPLY FOR CERTIFICATE OF AUTHORIZATION; SEND | | | NUMBER VIA EMAIL WHEN THE AA LICENSE NUMBER IS ISSUED. | | | | | | | | | |
|