| 2016-02-17 09:24:34 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | CONTRACTOR IS TO CONFIRM ALL SIGNATURE DOCUMENTS PRIOR |
| | TO SUBMITTAL. |
| | |
| | 1. 2/17/16 SOILS REPORT PREPARED BY JAIME VALEZ |
| | (PE66416), DUNKELBERGER (6870); UNABLE TO LOCATE THE |
| | ENGINEERING BUSINESS LICENSE NUMBER ON THE REPORT, SEE |
| | FAC61G15-23, WWW.FBPE.ORG. PLEASE INCLUDE. PLEASE |
| | UPLOAD AS A RESUBMITTAL (SAME NAME AS ORIGINAL SOILS |
| | REPORT FILE). |
| | |
| | 2. CIVIL SHEETS HAVE THE FOLLOWING ERRORS: |
| | C101 IS NOT DIGITALLY SIGNED AND SEALED. |
| | C102, C103 SEAL IS INVALID. |
| | OTHER SHEETS NOT CHECKED. CONTRACTOR IS TO VERIFY VALID |
| | SIGNATURE OF ALL SHEETS PRIOR TO SUBMITTAL OF SIGNATURE |
| | DOCUMENTS. |
| | CIVIL SHEETS LACK A TITLE BLOCK IN ACCORDANCE WITH |
| | FAC61G-15. |
| | |
| | 3. FIRE PROTECTION SHEET NOT SIGNED AND SEALED. NO |
| | ACTION REQUIRED; THIS SHEET HAS BEEN MARKED "FOR |
| | REFERENCE ONLY" (WORK IS UNDER A SEPARATE ISSUED |
| | PERMIT) |
| | |
| | 4. 2/17/16 SHEETS PREPARED BY LOUIS VANDELOECHT |
| | (AR95072), GMA ARCHITECTS, INC (C OF A PENDING) - OK |
| | WITH PROVISOS: |
| | OBTAIN CERTIFICATE OF AUTHORIZATION |
| | PAGE A6.3 ON INDEX PAGE WAS NOT SUBMITTED, PER |
| | APPLICANT THE INDEX IS INCORRECT. ARCHITECT TO REVISE |
| | HIS PLAN TO REMOVE THIS SHEET FROM INDEX. (EMAIL FROM |
| | ARCHITECT CONFIRMING THAT THIS SHEET WAS INCLUDED ON |
| | INDEX IN ERROR WAS ROUTED TO RECORDS) |
| | |
| | 5. REVISED MECHANICAL SHEETS TO BE RESUBMITTED WITH |
| | REVISED TITLE BLOCK INFORMATION. |
| | |
| | 6. "BUILDING ENVELOPE COMCHECK" LACK A DIGITAL |
| | SIGNATURE (ARCHITECT). PLEASE UPLOAD TO PROJECTDOX. |
| | |
| | 7. "MECHANICAL ENERGY COMPLIANCE FORM" IS SIGNED BY |
| | "TIM SCHAEFFER PE". THIS DESIGN PROFESSIONAL'S NAME |
| | DOES NOT APPEAR ON ANY OF THE CONSTRUCTION DOCUMENTS, |
| | AND THIS DOCUMENT LACKS THE INFORMATION REQUIRED BY |
| | FAC61G15-23. IF THIS IS DELEGATED ENGINEERING, ENGINEER |
| | OF RECORD IS TO REVIEW THIS DOCUMENT, SEE FAC61G-15. |
| | |
| | 8. "MECHANICAL LOAD CALCULATIONS" STATES THAT THEY ARE |
| | PREPARED BY ICON MECHANICAL, AND THERE IS NO TITLE |
| | BLOCK FOR MR. TENNILL. |
| | |
| | THE FOLLOWING DESIGN PROFESSIONALS SIGNATURE DOCUMENTS |
| | ARE IN COMPLIANCE WITH FAC61G15: |
| | |
| | 9. STRUCTURAL SHEETS, RICHARD ADAMS (PE35836), RICHARD |
| | ADAMS ENGINEERS & CONSULTANTS, PA (7565) - OK |
| | |
| | 10. ELECTRICAL SHEETS, MATTHEW OTTO (PE58722), OTTO |
| | ENGINEERING, INC. (27523) - OK |
| | |
| | |