Plan Review Notes
Plan Review Notes For Permit 15110707
Permit Number 15110707
Review Stop P
Sequence Number 1
Notes
Date Text
2015-11-30 06:17:251) SUBMIT A FLOOR PLAN SHOWING THE AMOUNT, TYPE AND
 LOCATION OF THE EXISTING SANITARY FACILITIES IN THE
 STRUCTURE. THE ADDED 28,775 SQUARE FEET MAY REQUIRE
 ADDITIONAL SANITARY FACILITIES IN ACCORDANCE WITH 2014
 FBC-PLUMBING TABLE 403.1.
 2) SUBMIT CALCULATIONS FOR THE SIZING OF THE
 SCUPPERS.INDICATE ON THE PLANS THE SQUARE FOOTAGE BEING
 DRAINED BY EACH SCUPPER. THE SIZING OF THE SCUPPERS
 SHALL INCLUDE 1/2 THE AREA OF ANY VERTICAL WALLS THAT
 DIVERT RAINWATER TO THE ROOF. SCUPPERS SHALL BE SIZED
 IN ACCORDANCE WITH 2014 FBC-PLUMBING TABLE 1106.7 BASED
 ON A 5 INCH PER HOUR RAINFALL RATE. INDICATE THE DESIGN
 HEAD ( IN INCHES) FOR THE SCUPPERS.
 3) SHT. A2.5 - DETAIL # 2 - THE DOWNSPOUT SHALL
 DISCHARGE A MINIMUM OF ONE FOOT AWAY FROM THE STRUCTURE
 WALL PER 2014 FBC SEC.1503.7.
 4) THE OVERFLOW SCUPPERS SHALL BE LOCATED NO LESS THAN
 2 INCHES NOR MORE THAN 4 INCHES ABOVE THE FINISHED ROOF
 SURFACE PER 2014 FBC SEC. 1503.4.2.1.
  