| 2015-12-09 10:17:38 | 1ST REVIEW 2014 MECHANICAL | | | PERMIT #15110707 | | | 12/9/15 | | | | | | 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE | | | PROPOSED OCCUPANCY PER TABLE 403.3 FBC-14 MECHANICAL. | | | SHOW THE REQUIRED AND PROVIDED CFM'S OF O/A. | | | 2) PROVIDE ENERGY CALCULATIONS FOR THE NEW ADDITION IN | | | COMPLIANCE WITH SECTION C101.4.3 FBC-14 ENERGY | | | CONSERVATION. | | | 3) THE SUMMER DESIGN DRY BULB TEMPERATURE LISTED ON THE | | | TRACE 700 CALCULATIONS IS INCORRECT. DRY BULB TEMPS PER | | | TABLE 1A ACCA MANUAL N- (90 DEGREES F), & PER APPENDIX | | | D FBC-14 PLUMBING- (91 DEGREES F). PLEASE REVISE THE | | | CALCS ACCORDINGLY. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|