| 2015-12-08 19:24:10 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | PG. T1.1 |
| | 1. THE APPLICABLE NATIONAL ELECTRICAL CODE IS THE 2011 |
| | EDITION. PLEASE CORRECT ALL PLAN NOTES ACCORDINGLY. |
| | 2. THE APPLICABLE FIRE CODES ARE THE 2012 EDITION. |
| | PLEASE CORRECT ALL PLAN NOTES ACCORDINGLY. |
| | PG. E1.1 |
| | 1. PER FBC-B 1006.3 THIS STAIR LANDING SHALL BE |
| | ILLUMINATED IN THE EVENT OF POWER FAILURE. EMERGENCY |
| | LIGHTING REQUIRED. EXIT DISCHARGE LIGHTING REQUIRED AS |
| | WELL. |
| | 2. PER FBC-B 1006.3 THIS STAIR LANDING SHALL BE |
| | ILLUMINATED IN THE EVENT OF POWER FAILURE. EMERGENCY |
| | LIGHTING REQUIRED. |
| | 3. PER FBC-B 1011.1 AN EXIT LIGHT IS REQUIRED HERE. |
| | DEPENDING ON FINISHED FLOOR PLAN AND ISLE LAYOUT, |
| | ADDITIONAL EXIT LIGHTS MAY BE REQUIRED. |
| | PG. E2.1 |
| | 1. NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20 |
| | AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET |
| | LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF |
| | WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL |
| | 15- AND 20-AMPERE, 125- AND 250-VOLT NONLOCKING |
| | RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE |
| | ?WR?. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |